HomeMy WebLinkAboutMarriott Residence Inn i
CITY LIMITS
PROJECT
J LOCATION
e
1
n� NOTES: Catron St.
- - - ONLY FITTINGS ALLOWED BETWEEN aj
FIRST OS&Y VALVE AND BACKFLOW ' Burke
- ASSEMBLY TO BE 90'BEND. X
0.,.0 NO PRESSURE GAUGES OR 2.2' TO(W) WALL
PRESSURE GAUGE FITTINGS WILL 4.5' TO (N) WALL r' J
^
4T Simm I Trail
BE ALLOWED ON THE TEST PORTS `-OF ANY BACKFLOW ASSEMBLY. 3 :OS&Y VALVE
/ w \
O_
aEXISTING 12" N
W WATER MAIN Dead an
STA. D+DO MARRIOTT 14•
rC o RESIDENCE INN FUTURE FINISHED FLOOR ille Ih�a
U '2 STA. 1+62.05 -FLANGE THREADED ON STANDPIPE \
m 3/4- MIN. RED] ROD, INSTALLED
IN EVERY OTHER MJ BOLT HOLES (TYP.) VICINITY MAP
m STA. 5*BEN61 D
22.5'BEND r'
W
- 0 76' CL 51 D.I. FIRE
C SERVICE LINE STA. 1 70.03
FLANGEDOS&Y.
- 6" DI 90'BEND, MJ W/MJR
. W/ THRUST BLOCK PER COB
STD DWG 02660-13
FUTURE GENERAL NOTES:
BUILDING 1. ALL MATERIALS AND WORKMANSHIP CONFORM TO MONTANA
BY OTHERS PUBLIC WORKS STANDARDS, AND CURRENT CITY OF BOZEMAN
MODIFICATIONS.
1 BA 2. PIPE BEDDING AND CKFILL WITH ALL PIPES ARE BEDDED
1 MINIMUM 4-INCHES OF TYPE 1 PIPE BEDDING AND BACKFILLED
WITH THE SAME MATERIAL A MINIMUM OF 6-INCHES OVER THE
--- -- - TOP OF THE PIPE PER CITY OF BOZEMAN STANDARD DETAIL
02221-1.
MA'47AIN 2' CLEAR ELEVATION-FIRE SERVICE NE RISER NOT TO SCALE WATER
OF OUTSIDE WALL
AP D 1' CLEAR OF CITY OF BOZEMAN REQUIREMENTS FOR 3 HIYDRANTS, ON EXIISTINGTY FORCES TO TP BLICE ALL VMANS� INCLUDING FIRE
INSIDE WALL
4652.0 - INSTALLATION OF DOUBLE C ECK VALVE ASSEMBLY 4. ALL WATER MAINS ARE CLASS 51 DUCTILE IRON. ALL WATER
1. THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL LISTED FLANGED KENNEDY OR MUELLER MAINS AND SERVICES INSTALLED WITH A MINIMUM 6.5' OF COVER
FUTURE OS&Y VALVE THE SAME SIZE AS THE FIRE SER ICE LINE. TO FINISH GRADE UNLESS OTHERWISE NOTED OR DIRECTED.
FINISHED
GRADE FU RE
FIN ED FLOOR 2. ALL DOUBLE CHECK VALVE ASSEMBLIES SHALL BE:
4650.0 A. UL OR FM LISTED.
3 B. APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION FOR CROSS CONNECTION
- 3 CONTROL AND HYDRAULIC RESEARCH (USCFCCCHR) FOR OPERATION IN THE PROPOSED
POSITION (VERTICAL OR HORIZONTAL) AS SHOWN ON APPROVED PLANS.
C. INSTALLED AS SHOWN ON THE APPROVED PLANS,
4648.0 X v --- _ _ _ 3. A FLOW DETECTION DEVICE SHALL BE INSTALLED IMMEDIATELY FOLLOWING THE DOUBLE CHECK VALVE
ASSEMBLY (ALARM CHECK VALVE, FLOW SENSOR/ALARM, METER, ETC.) AS SHOWN ON THE APPROVED
m m EXISTING w PLANS. PADDLE-TYPE FLOW ALARMS NOT PERMITTED ON DRY SYSTEMS.
? a o a GROUND a 4. A DOUBLE DETECTOR CHECK VALVE ASSEMBLY MAY BE USED WITH A STANDARD CITY OF BOZEMAN
0 ,o METER. THE METER LOOP OF THE DOUBLE DETECTOR CHECK VALVE SHALL HAVE A DOUBLE CHECK
4646.0 o oo� in�a = '+ VALVE ASSEMBLY INSTALLED WHICH MEETS THE SAME INSTALLATION CRITERIA SPECIFIED ABOVE IN
a� a�< N`+°II +II REQUIREMENT NUMBER TWO.
ao ao o� �z�Q II o 4� o d� 5. HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF 2 ABOVE THE FINISHED FLOOR.
4644.0 6. THE FIRE SERVICE RISER MUST SHALL BE MINIMUM OF 2' FROM ANY OUTSIDE WALL, AND A MINIMUM OF
6" CL 51 D.I. 1' FROM ANY INTERIOR WALL.
FIRE SERVICE LINE 7. THE INCOMING FIRE SERVICE LINE SHALL BE A MINIMUM 6.5', AND A MAXIMUM OF 7.5' BELOW THE
FINISHED GRADE.
4642.0 , 8. ALL FIRE SERVICE LINE APPURTENANCES SHALL BE A MINIMUM PRESSURE RATING OF 175 PSI.
170 LF OF 6" DI CLASS 51 FIRE SERVICE LINE (HOT TAP TO RISER) 9. ALL FIRE SERVICE LINES 4" AND LARGER SHALL BE CLASS 51 DUCTILE IRON PIPE.
10. LINE SIZING: THE DOUBLE CHECK VALVE ASSEMBLY SHALL BE EQUAL IN SIZE TO BOTH THE INCOMING
PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE DIAMETER (DOWNSTREAM). FOR EXAMPLE, A 4" FIRE
4640.0 SERVICE LINE SHALL HAVE A 4" DOUBLE CHECK VAL ASSEMBLY.
INSTALLED CONCRETE
THRUST BLOCK PER STA. 1+70.03
C.O.B. STD DTL INV. ELEV. 4642.0
02660-1 INSTALLED 90'BEND UP WITH
4638.0 MEGA-LUG RESTRAINED JOINTS.
INSTALLED �4" MIN. REDI ROD IN
EVERY OTHER M.J. BOLT HOLES
BETWEEN BEND AND OS&Y VALVE
4650.0
w m m N
J
W
0+00 0+50 1+00 1+50 2+00 �I�-q C �f��
D�d v V V ING
NO. REVISIONS DRAWN BY DATE 0 20 40 60 T PROJECT 0: 05-001 SHEET
'Hq RESIDENCE INN BY MARRIOTT Civil Engineering 32 DISCOVERY DRIVE DATE: 03/22/2006 T�y
SCALE: 1 INCH = 20 FEET i'#m; * r 1
Land Surveying BOZEMAN,MT 59718 FIRE SERVICE
]FIRE SERVICE PHONE(406)382-0221 MARRIOTT-RESIDENCE INN
PROJECT ENGINEER: JDB DRAWN BY: LJG ,L ALLIED
Geotechnical Engineering FAX(406)582-5770
DESIGNED BY: CGB REVIEWED BY:JOB �tA."o ,�� BOZEMAN,MT ENGINEERING FIRE SERVICE
L\2M\C6-=watt
li I i
I � `
CITY LIMITS
P OJECT
LO ATION
Catron St.
ai
SURVEY CONTROL Burke
x
COORDINATE TABLE /
Simm I Trail
FITTING NORTHING EASTING
12x4 TEE 14146.44 42744.74 Dead n
22.5'BEND 14170.22 42790.91 A \
90'BEND 14201.73 42818.28 ille a 4" DI CL 51 WATER I
SERVICE LINE FUTURE
Q� LANDSCAPE DRAIN \
a 3 R(�Z�' 0+93.45 l~\J
k' RL=3� 90'BEND
STA. D+DD VICINITY MAP
a 0+52.08
53' 22.5'BEND STA. 0+9 .20
_ _ _ RISER INS ALLED PER COB
~ RL-14' DETAIL 02660-12
FUTURE
GAS SERVICE iV1ARRIOTT
\ LINE
RE$IDEi}dCE INN
b FUTURE
GUIDING
BY OTHERS
WATER SERVICE = PLAN VIEW
BACKFLOW PREVENTION ASSEMBLY MUST 4652.0 -
CONNECT DIRECTLY TO METER/ STRAINER. GENERAL NOTES:
REQUIRED BACKFLOW PREVENTION DEVICE TO 1. ALL MATERIALS AND WORKMANSHIP CONFORM TO MONTANA
BE DETERMINED BY WATER SUPERINTENDENT. APPROX. LOCATION
FUTURE LANDSCAPE PUBLIC WORKS STANDARDS, AND CURRENT CITY OF BOZEMAN
DRAIN CROSSING MODIFICATIONS.
NO PRESSURE GAUGES OR PRESSURE .-METER 4650.0 FUTURE FINISHFUTURE FINISH FLOORNISH GRADE 2. PIPE BEDDING AND BACKFILL. ALL PIPES ARE BEDDED WITH
GAUGE FITTINGS WILL BE ALLOWED ON MINIMUM 4-INCHES OF TYPE 1 PIPE BEDDING AND BACKFILLED
THE TEST PORTS OF ANY BACKFLOW 7 WITH THE SAME MATERIAL A MINIMUM OF 6-INCHES OVER THE
PREVENTION ASSEMBLY. TOP OF THE PIPE PER CITY OF BOZEMAN STANDARD DETAIL
02221-1.
_
FLANGED OSdcY VALVE 4648.0 f �
FLANGE TO BE THREADED ON STANDPIPE, EXISTING 1 6.5' MIN. COVER 3. CITY FORCES TO OPERATE ALL VALVES, INCLUDING FIRE
M.J. TO FLANGE ADAPTORS NOT ACCEPTABLE GROUND HYDRANTS, ON EXISTING PUBLIC MAINS.
(TYPICAL FOR ALL RISER CONFIGURATIONS) w
4. ALL WATER MAINS ARE CLASS 51 DUCTILE IRON, ALL WATER
14" ABOVE 4646'0 0 1 MAINS AND SERVICES INSTALLED WITH A MINIMUM 6.5' OF COVER
FINISHED FLOOR FLOOR z m w 0 TO FINISH GRADE UNLESS OTHERWISE NOTED OR DIRECTED.
a n 8m yw c0v�w
` ,r' .,r.•'� - - a� a inn m m m 5 5. ALL RESTRAINED JOINTS ON THIS PLAN (RL=RESTRAINED
a �r + +Na 4.5't + + w LENGTH) ARE MECHANICALLY RESTRAINED WITH MEGALUG OR
4644.0 :`g II Do< Do DFrn
EQUIVALENT RESTRAINT SYSTEM.
3/4" MIN. REDI-ROD, INSTALLED Nw ti, w F, rn Z RISER INSTALLED PER
MECHANICAL fIN EVERY OTHER AVAILABLE M.J. - rn�= m a In Z a COB DETAIL 02660-12
JOINT BOLT HOLE (TYPICAL) ry
,y 4642.0 \\`�
90' BEND WITH -�`V
THRUST BLOCK
42 LF LE. 4642.05
4" DI CL 51
WATER
.a • 4640.0
52 LF
1143TALLED CONCRETE V4" DI CL 51
HRUST BLOCK PER WATER W
C B DETAIL 02660-1 5
WATER SERVICE RISER DETAIL 4636.0
REFER TO COB DETAIL, 02660-12
4636.0
'a
Y
0+00 0+50 1+0o REC'0R D
WATER SERVICE - PROFILE IEW DRA , ING
8
NO. REVISIONS DRAWN BY DATE HORIZONTAL S2AOLE VERTICAL SCALE NT4 4 PROJECT M: 05-001 SHEET
RESIDENCE INN BY MARR O T 2z'm32 DISCOVERY DRIVE DATE: 03/22/2006
Civil Engineering OF
* Land Surveying BOZEMAN,MT 59718 WAT. SERVICE
1 INCH - 20 FEET 1 INCH = 2 FEET DOMESTIC WATER SERVICE. ALLIED Yl g PHONE(406)582-0221 MARRIOTT-RESIDENCE INN
PROJECT ENGINEER: JOB DRAWN BY: LJG Geotechnical Engineering FAX(406)582-5770
BOZEMAN, L:\2003\OS-001 MMRIOTT
MT ENGINEERING DOMESTIC WATER SERVICE
i1�e► sersv�cEs.wc.
DESIGNED BY: JDB REVIEWED BY: