HomeMy WebLinkAboutPressure - TAB 2 - Rosemount Pressure TransProduct Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 Rosemount 3051 www.rosemount.com HART® AND FOUNDATION™ FIELDBUS PROTOCOLS • Best-in-Class performance, 0.04% High Accuracy option • Industry first five-year stability under actual process conditions • Unmatched Dynamic Performance • Coplanar ™ platform enables integrated pressure, flow, and level solutions • Advanced PlantWeb ® Functionality Rosemount 3051 Pressure Transmitter Contents Product Offering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 4 Product Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 12 HART Protocol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 12 Fieldbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 15 Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 17 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 25 HART Protocol C1 Option Configuration Data Sheet . . . . . . . . . . . . . . . . . . . . . . .page 39 Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 2 Setting the Standard for Pressure Measurement Industry’s best total performance, a flexible Coplanar platform, and guaranteed 5- year stability, has made the Rosemount 3051 the standard in pressure measurement. Industry’s best total performance of ±0.15% Total performance is the true measure of “real-world” transmitter performance. Using superior sensor technology and engineered for optimal performance, the 3051 delivers unprecedented ±0.04% reference accuracy, resulting in total operating performance of ±0.15%. Superior total performance equates to reduced variability and improved plant safety. Five year installed stability of ±0.125% Transmitter stability is a critical measure of transmitter performance over time. Through aggressive simulation testing beyond standard IEC 770 testing, the 3051 has proven its ability to maintain performance over a five year period under the most demanding process conditions. Superior transmitter stability reduces calibration frequency to save operation and maintenance costs. Unmatched dynamic performance In dynamic applications, speed of measurement is as important as repeatability. The 3051 responds up to eight times faster than the typical pressure transmitter to detect and control variations quickly and efficiently. Superior dynamic response yields more accurate measurements to reduce variability and increase profitability. Coplanar platform enables complete point solutions The versatile Coplanar platform design enables the best process connection for pressure, flow and level applications. Right out of the box, the solution arrives factory calibrated, pressure-tested, and ready to install. Only the 3051 has a flexible design to reduce engineering and inventory costs. Advanced PlantWeb Functionality The 3051 powers the PlantWeb architecture by delivering the best sensor and transmitter, best installation practices, and best in class field intelligence. One component is the enhanced diagnostic capabilities in FOUNDATION fieldbus that provide an increase in process visibility, enabling proactive maintenance and improving process availability. Rosemount Pressure Solutions Rosemount 3051S Series of Instrumentation Scalable pressure, flow and level measurement solutions improve installation and maintenance practices. Rosemount 3095MV Mass Flow Transmitter Accurately measures differential pressure, static pressure and process temperature to dynamically calculate fully compensated mass flow. Rosemount 305 and 306 Integral Manifolds Factory-assembled, calibrated and seal-tested manifolds reduce on-site installation costs. Rosemount 1199 Diaphragm Seals Provides reliable, remote measurements of process pressure and protects the transmitter from hot, corrosive, or viscous fluids. Orifice Plate Primary Element Systems: Rosemount 1495 and 1595 Orifice Plates, 1496 Flange Unions and 1497 Meter Sections A comprehensive offering of orifice plates, flange unions and meter sections that is easy to specify and order. The 1595 Conditioning Orifice provides superior performance in tight fit applications. Annubar® Flowmeter Series: Rosemount 3051SFA, 3095MFA, and 485 The state-of-the-art, fifth generation Rosemount 485 Annubar combined with the 3051S or 3095MV MultiVariable transmitter creates an accurate, repeatable and dependable insertion-type flowmeter. Compact Orifice Flowmeter Series: Rosemount 3051SFC, 3095MFC, and 405 Compact Orifice Flowmeters can be installed between existing flanges, up to a Class 600 (PN100) rating. In tight fit applications, a conditioning orifice plate version is available, requiring only two diameters of straight run upstream. ProPlate® Flowmeter Series: Rosemount ProPlate, Mass ProPlate, and 1195 These integral orifice flowmeters eliminate the inaccuracies that become more pronounced in small orifice line installations. The completely assembled, ready to install flowmeters reduce cost and simplify installation. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 3 Rosemount 3051 Product Offering Rosemount 3051C Differential, Gage, and Absolute See ordering information on page 25. • Performance up to 0.04% accuracy • Five year installed stability of 0.125% •Coplanar platform enables integrated manifold, primary element and diaphragm seal solutions • Calibrated spans/ranges from 0.1 inH2O to 4000 psi (0,25 mbar to 276 bar) • 316L SST, Hastelloy® C276, Monel®, Tantalum, Gold-plated Monel, or Gold-plated 316L SST process isolators Rosemount 3051T Gage and Absolute See ordering information on page 29. • Performance up to 0.04% accuracy • Five year installed stability of 0.125% • Calibrated spans from 0.3 to 10000 psi (10,3 mbar to 689 bar) • Multiple process connections available • 316L SST and Hastelloy C276 process isolators Rosemount 3051L Liquid Level See ordering information on page 31. • Performance up to 0.075% accuracy • Welded fill fluid system provides best-in-class system reliability • Flush and extended diaphragms • Multiple fill fluids and wetted materials available Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 4 Specifications Reference Accuracy(1) Models Standard High Accuracy Option 3051CD, 3051CG Range 0 (CD) ±0.10% of span For spans less than 2:1, accuracy = ±0.05% of URL Range 1 ±0.10% of span For spans less than 15:1, accuracy = Ranges 2-5 ±0.065% of span For spans less than 10:1, accuracy = Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy = 3051T Ranges 1-4 ±0.065% of span For spans less than 10:1, accuracy = Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy = Range 5 ±0.075% of span For spans less than 10:1, accuracy = 3051CA Ranges 1-4 ±0.065% of span For spans less than 10:1, accuracy = Ranges 2-4 High Accuracy Option, P8 ±0.04% of span For spans less than 5:1, accuracy = 3051H/3051L All Ranges ±0.075% of span For spans less than 10:1, accuracy = (1) For FOUNDATION fieldbus transmitters, use calibrated range in place of span. For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange (3051C) or 1/2 in. - 18 NPT (3051T) process connections, digital trim values set to equal range points. 0.025 0.005+URL Span---------------⎝⎠⎛⎞% of Span± 0.015 0.005+URL Span---------------⎝⎠⎛⎞% of Span± 0.015 0.005+URL Span---------------⎝⎠⎛⎞% of Span± 0.0075 URL Span---------------⎝⎠⎛⎞% of Span± 0.0075 URL Span---------------⎝⎠⎛⎞% of Span± 0.0075 URL Span---------------⎝⎠⎛⎞% of Span± 0.0075 URL Span---------------⎝⎠⎛⎞% of Span± 0.0075 URL Span---------------⎝⎠⎛⎞% of Span± 0.025 0.005+URL Span---------------⎝⎠⎛⎞% of Span± PERFORMANCE SPECIFICATIONS Total Performance is based on combined errors of reference accuracy, ambient temperature effect, and static pressure effect. This product data sheet covers both HART and fieldbus protocols unless specified. Conformance To Specification (±3σ (Sigma)) Technology leadership, advanced manufacturing techniques and statistical process control ensure specification conformance to at least ±3σ. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 5 Rosemount 3051 Total Performance Long Term Stability Dynamic Performance Line Pressure Effect per 1000 psi (6,9 MPa) For ±50 °F (28 °C) temperature changes, up to 1000 psi (6,9 MPa) line pressure (CD only), from 1:1 to 5:1 rangedown. Models Total Performance 3051C Ranges 2-5 ±0.15% of span 3051T Ranges 1-4 ±0.15% of span Models Long Term Stability 3051C Ranges 2-5 ±0.125% of URL for 5 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure. 3051CD Low/Draft Range Ranges 0-1 ±0.2% of URL for 1 year 3051T Ranges 1-4 ±0.125% of URL for 5 years ±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure. Rosemount 3051H Ranges 2-3 Ranges 4-5 ±0.1% of URL for 1 year ±0.2% of URL for 1 year 4 - 20 mA (HART protocol)(1) Fieldbus protocol(3)Typical HART Transmitter Response Time Total Response Time (Td + Tc)(2): 3051C, Ranges 2-5: Range 1: Range 0: 3051T: 3051H/L: 100 ms 255 ms 700 ms 100 ms Consult factory 152 ms 307 ms 752 ms 152 ms Consult factory Dead Time (Td)45 ms (nominal) 97 ms Update Rate 22 times per second 22 times per second (1) Dead time and update rate apply to all models and ranges; analog output only (2) Nominal total response time at 75 °F (24 °C) reference conditions. (3) Transmitter fieldbus output only, segment macro-cycle not included. TcTd Td = Dead Time Tc = Time Constant Pressure Released Response Time = Td+Tc 63.2% of Total Step Change Time0% 100% 36.8% Transmitter Output vs. Time 3051-3051_17A For line pressures above 2000 psi (13,7 MPa), see user manual (Rosemount publication number 00809-0100-4001). Models Line Pressure Effect 3051CD Zero Error(1) ±0.125% of URL/100 psi (6,89 bar)Range 0 Range 1 ±0.25% of URL/1000 psi (68,9 bar) Ranges 2-3 ±0.05% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa) Range 0 Span Error ±0.15% of reading/100 psi (6,89 bar) Range 1 ±0.4% of reading/1000 psi (68,9 bar) Ranges 2-3 ±0.1% of reading/1000 psi (68,9 bar) 3051HD Zero Error(1) ±0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)All Ranges All Ranges Span Error ±0.1% of reading/1000 psi (68,9 bar) (1) Can be calibrated out at line pressure. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 6 Ambient Temperature Effect per 50°F (28°C) Mounting Position Effects Vibration Effect All Models Measurement effect due to vibrations is negligible except at resonance frequencies. When at resonance frequencies, vibration effect is less than ±0.1% of URL per g when tested between 15 and 2000 Hz in any axis relative to pipe-mounted process conditions. Power Supply Effect All Models Less than ±0.005% of calibrated span per volt. RFI Effects All Models ±0.1% of span from 20 to 1000 MHz and for field strength up to 30 V/m. Transient Protection (Option Code T1) All Models: Meets IEEE C62.41, Category B 6 kV crest (0.5 μs - 100 kHz) 3 kV crest (8 × 20 microseconds) 6 kV crest (1.2 × 50 microseconds) Meets IEEE C37.90.1, Surge Withstand Capability SWC 2.5 kV crest, 1.25 MHz wave form General Specifications: Response Time: < 1 nanosecond Peak Surge Current: 5000 amps to housing Peak Transient Voltage: 100 V dc Loop Impedance: < 25 ohms Applicable Standards: IEC61000-4-4, IEC61000-4-5 NOTE: Calibrations at 68 °F (20 °C) per ASME Z210.1 (ANSI) Models Ambient Temperature Effect 3051CD/CG Range 0 ±(0.25% URL + 0.05% span) Range 1 ±(0.1% URL + 0.25% span) Ranges 2-5 ±(0.0125% URL + 0.0625% span) from 1:1 to 5:1 ±(0.025% URL + 0.125% span) from 5:1 to 100:1 3051T Range 1 ±(0.025% URL + 0.125% span) from 1:1 to 10:1 ±(0.05% URL + 0.125% span) from 10:1 to 100:1 Range 2-4 ±(0.025% URL + 0.125% span) from 1:1 to 30:1 ±(0.035% URL + 0.125% span) from 30:1 to 100:1 Range 5 ±(0.1% URL + 0.15% span) 3051CA All Ranges ±(0.025% URL + 0.125% span) from 1:1 to 30:1 ±(0.035% URL + 0.125% span) from 30:1 to 100:1 3051H All Ranges ±(0.025% URL + 0.125% span + 0.35 inH2O) from 1:1 to 30:1 ±(0.035% URL + 0.125% span + 0.35 inH2O) from 1:1 to 30:1 3051L See Rosemount Inc. Instrument Toolkit™ software. Models Mounting Position Effects 3051C Zero shifts up to ±1.25 inH2O (3,11 mbar), which can be calibrated out. No span effect. 3051H Zero shifts up to ±5 inH2O (12,43 mbar), which can be calibrated out. No span effect. 3051L With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (2,49 mbar). With diaphragm in horizontal plane, zero shift of up to 5 inH2O (12,43 mbar) plus extension length on extended units. All zero shifts can be calibrated out. No span effect. 3051T/CA Zero shifts up to 2.5 inH2O (6,22 mbar), which can be calibrated out. No span effect. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 7 Rosemount 3051 FUNCTIONAL SPECIFICATIONS Range and Sensor Limits TABLE 1. 3051CD, 3051CG, 3051L, and 3051H Range and Sensor Limits RangeMinimum Span Range and Sensor Limits 3051CD(1), CG, L, H Upper (URL) Lower (LRL) 3051C Differential 3051C/ Gage 3051L Differential 3051L Gage 3051H Differential 3051H Gage 0 0.1 inH2O (0,25 mbar) 3.0 inH2O (7,47 mbar) –3.0 inH2O (-7,47 mbar) NA NA NA NA NA 1 0.5 inH2O (1,2 mbar) 25 inH2O (62,3 mbar) –25 inH2O (–62,3 mbar) –25 inH2O (–62,3 mbar) NA NA NA NA 2 2.5 inH2O (6,2 mbar) 250 inH2O (0,62 bar) –250 inH2O (–0,62 bar) –250 inH2O (–0,62 bar) –250 inH2O (–0,62 bar) –250 inH2O (–0,62 bar) –250 inH2O (–0,62 bar) –250 inH2O (–0,62 bar) 3 10 inH2O (24,9 mbar) 1000 inH2O (2,49 bar) –1000 inH2O (–2,49 bar) 0.5 psia (34,5 mbar abs) –1000 inH2O (–2,49 bar) 0.5 psia (34,5 mbar abs) –1000 inH2O (–2,49 bar) 0.5 psia (34,5 mbar abs) 4 3 psi (0,20 bar) 300 psi (20,6 bar) –300 psi (–20,6 bar) 0.5 psia (34,5 mbar abs) –300 psi (–20,6 bar) 0.5 psia (34,5 mbar abs) –300 psi (–20,6 bar) 0.5 psia (34,5 mbar abs) 5 20 psi (1,38 bar) 2000 psi (137,9 bar) – 2000 psi (–137,9 bar) 0.5 psia (34,5 mbar abs) NA NA – 2000 psi (–137,9 bar) 0.5 psia (34,5 mbar abs) (1) Range 0 only available with 3051CD. Range 1 only available with 3051CD or 3051CG. TABLE 2. Range and Sensor Limits 3051CA Range3051T RangeMinimum Span Range and Sensor Limits Minimum Span Range and Sensor Limits Lower(1) (LRL) (Gage) Upper (URL) Lower (LRL) Upper (URL) Lower (LRL) 1 0.3 psia (20,6 mbar) 30 psia (2,07 bar) 0 psia (0 bar) 1 0.3 psi (20,6 mbar) 30 psi (2,07 bar) 0 psia (0 bar) –14.7 psig (–1,01 bar) 2 1.5 psia (0,103 bar) 150 psia (10,3 bar) 0 psia (0 bar) 2 1.5 psi (0,103 bar) 150 psi (10,3 bar) 0 psia (0 bar) –14.7 psig (–1,01 bar) 3 8 psia (0,55 bar) 800 psia (55,2 bar) 0 psia (0 bar) 3 8 psi (0,55 bar) 800 psi (55,2 bar) 0 psia (0 bar) –14.7 psig (–1,01 bar) 4 40 psia (2,76 bar) 4000 psia (275,8 bar) 0 psia (0 bar) 4 40 psi (2,76 bar) 4000 psi (275,8 bar) 0 psia (0 bar) –14.7 psig (–1,01 bar) 5 2000 psi (137,9 bar) 10000 psi (689,4 bar) 0 psia (0 bar) –14.7 psig (–1,01 bar) (1) Assumes atmospheric pressure of 14.7 psig. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 8 Zero and Span Adjustment Requirements (HART and Low Power) Zero and span values can be set anywhere within the range limits stated in Table 1 and Table 2. Span must be greater than or equal to the minimum span stated in Table 1 and Table 2. Service Liquid, gas, and vapor applications 4–20 mA (Output Code A) Output Two-wire 4–20 mA, user-selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host that conforms to the HART protocol. Power Supply External power supply required. Standard transmitter (4–20 mA) operates on 10.5 to 55 V dc with no load. Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply, as described by: FOUNDATION fieldbus (output code F) and Profibus (output code W) Power Supply External power supply required; transmitters operate on 9.0 to 32.0 V dc transmitter terminal voltage. Current Draw 17.5 mA for all configurations (including LCD display option) FOUNDATION fieldbus Function Block Execution Times FOUNDATION fieldbus Parameters Standard Function Blocks Resource Block Contains hardware, electronics, and diagnostic information. Transducer Block Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults. LCD Block Configures the local display. 2 Analog Input Blocks Processes the measurements for input into other function blocks. The output value is in engineering units or custom and contains a status indicating measurement quality. PID Block Contains all logic to perform PID control in the field including cascade and feedforward. Backup Link Active Scheduler (LAS) The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment. Advanced Control Function Block Suite (Option Code A01) Input Selector Block Selects between inputs and generates an output using specific selection strategies such as minimum, maximum, midpoint, average or first “good.” Arithmetic Block Provides pre-defined application-based equations including flow with partial density compensation, electronic remote seals, hydrostatic tank gauging, ratio control and others. Signal Characterizer Block Characterizes or approximates any function that defines an input/output relationship by configuring up to twenty X, Y coordinates. The block interpolates an output value for a given input value using the curve defined by the configured coordinates. Integrator Block Compares the integrated or accumulated value from one or two variables to pre-trip and trip limits and generates discrete output signals when the limits are reached. This block is useful for calculating total flow, total mass, or volume over time. FOUNDATION fieldbus Diagnostics Suite (Option Code D01) The 3051C FOUNDATION fieldbus Diagnostics provide Abnormal Situation Prevention (ASP) indictation. The integral statistical process monitoring (SPM) technology calculates the mean and standard deviation of the process variable 22 times per second. The 3051C ASP algorithm uses these values and highly flexible configuration options for customization to many user-defined or application specific abnormal situations. The detection of plugged impulse lines is the first available predefined application. Block Execution Time Resource - Transducer - LCD Block - Analog Input 1, 2 30 milliseconds PID 45 milliseconds Input Selector 30 milliseconds Arithmetic 35 milliseconds Signal Characterizer 40 milliseconds Integrator 35 milliseconds Voltage (V dc)Load (Ohms)Communication requires a minimum loop resistance of 250 ohms. (1) For CSA approval, power supply must not exceed 42.4 V. Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) Operating Region Schedule Entries 7 (max.) Links 20 (max.) Virtual Communications Relationships (VCR) 12 (max.) Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 9 Rosemount 3051 Low Power (Output Code M) Output Three wire 1–5 V dc or 0.8–3.2 V dc (Option Code C2) user-selectable output. Also user selectable for linear or square root output configuration. Digital process variable superimposed on voltage signal, available to any host conforming to the HART protocol. Low-power transmitter operates on 6–12 V dc with no load. Power Consumption 3.0 mA, 18–36 mW Minimum Load Impedance 100 kΩ (Vout wiring) Indication Optional 5-digit LCD display Overpressure Limits Rosemount 3051CD/CG • Range 0: 750 psi (51,7 bar) • Range 1: 2000 psig (137,9 bar) • Ranges 2–5: 3626 psig (250 bar) 4500 psig (310,3 bar) for option code P9 Rosemount 3051CA • Range 1: 750 psia (51,7 bar) • Range 2: 1500 psia (103,4 bar) • Range 3: 1600 psia (110,3 bar) • Range 4: 6000 psia (413,7 bar) Rosemount 3051H • All Ranges: 3626 psig (25 MPa) Rosemount 3051TG/TA • Range 1: 750 psi (51,7 bar) • Range 2: 1500 psi (103,4 bar) • Range 3: 1600 psi (110,3 bar) • Range 4: 6000 psi (413,7 bar) • Range 5: 15000 psi (1034,2 bar) For 3051L or Level Flange Option Codes FA, FB, FC, FD, FP, and FQ, limit is 0 psia to the flange rating or sensor rating, whichever is lower. Static Pressure Limit Rosemount 3051CD Only Operates within specifications between static line pressures of 0.5 psia and 3626 psig (4500 psig for Option Code P9). Range 0: 0.5 psia and 750 psig Range 1: 0.5 psia and 2000 psig Burst Pressure Limits Burst pressure on Coplanar, traditional, or 3051H process flange is 10000 psig (69 MPa). Burst pressure for the 3051T is Ranges 1–4: 11000 psi (75,8 MPa) Range 5: 26000 psig (179 MPa) Failure Mode Alarm Output Code A If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 3.75 mA or to 21.75 mA to alert the user. NAMUR-compliant values are available, option code C4. High or low alarm signal is user-selectable by internal jumper. Output Code M If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 0.94 V or above 5.4 V to alert the user (below 0.75 V or above 4.4 V for Option C2). High or low alarm signal is user-selectable by internal jumper. Output Code F and W If self-diagnostics detect a gross transmitter failure, that information gets passed as a status along with the process variable. Temperature Limits Ambient –40 to 185 °F (–40 to 85 °C) With integral meter: –4 to 175 °F (–20 to 80 °C) Storage –50 to 230 °F (–46 to 110 °C) With integral meter: –40 to 185 °F (–40 to 85 °C) Process At atmospheric pressures and above. See Table 4 TABLE 3. 3051L and Level Flange Rating Limits Standard Type CS Rating SST Rating ANSI/ASME Class 150 285 psig 275 psig ANSI/ASME Class 300 740 psig 720 psig ANSI/ASME Class 600 1480 psig 1440 psig At 100 °F (38 °C), the rating decreases with increasing temperature. DIN PN 10–40 40 bar 40 bar DIN PN 10/16 16 bar 16 bar DIN PN 25/40 40 bar 40 bar At 248 °F (120 °C), the rating decreases with increasing temperature. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 10 Humidity Limits 0–100% relative humidity Turn-On Time Performance within specifications less than 2.0 seconds (10.0 s for Profibus protocol) after power is applied to the transmitter Volumetric Displacement Less than 0.005 in3 (0,08 cm3) Damping Analog output response to a step input change is user-selectable from 0 to 36 seconds for one time constant. This software damping is in addition to sensor module response time. PHYSICAL SPECIFICATIONS Electrical Connections 1/2–14 NPT, PG 13.5, G1/2, and M20 × 1.5 (CM20) conduit. HART interface connections fixed to terminal block. Process Connections All Models except 3051L and 3051T 1/4–18 NPT on 21/8-in. centers 1/2–14 NPT on 2-, 21/8-, or 21/4-in. centers Rosemount 3051L High pressure side: 2-, 3-, or 4-in., ASME B 16.5 (ANSI) Class 150, 300 or 600 flange; 50, 80 or 100 mm, PN 40 or 10/16 flange Low pressure side: 1/4–18 NPT on flange 1/2–14 NPT on adapter Rosemount 3051T 1/2–14 NPT female. A DIN 16288 Male (available in SST for Range 1–4 transmitters only), or Autoclave type F-250-C (Pressure relieved 9/16–18 gland thread; 1/4 OD high pressure tube 60° cone; available in SST for Range 5 transmitters only). Process-Wetted Parts Drain/Vent Valves 316 SST, Hastelloy C276, or Monel material (Monel not available with 3051L or 3051H) Process Flanges and Adapters Plated carbon steel, SST cast CF-8M (cast version of 316 SST, material per ASTM-A743), C-Type cast alloy CW12MW, or Monel cast alloy M30C Wetted O-rings Glass-filled PTFE or Graphite-filled PTFE Process Isolating Diaphragms TABLE 4. 3051 Process Temperature Limits 3051CD, 3051CG, 3051CA Silicone Fill Sensor(1) (1) Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio (0.6:1 ratio for the 3051H). with Coplanar Flange –40 to 250 °F (–40 to 121 °C)(2) (2) 220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5 psia. with Traditional Flange –40 to 300 °F (–40 to 149 °C)(2)(3) (3) 3051CD0 process temperature limits are –40 to 212 °F (–45 to 100 °C) with Level Flange –40 to 300 °F (–40 to 149 °C)(2) with 305 Integral Manifold –40 to 300 °F (–40 to 149 °C)(2) Inert Fill Sensor(1) 0 to 185 °F (–18 to 85 °C)(4)(5) (4) 160 °F (71 °C) limit in vacuum service. (5) Not available for 3051CA. 3051H (Process Fill Fluid) D.C.® Silicone 200(1)–40 to 375 °F (–40 to 191 °C) Inert(1)–50 to 350 °F (–45 to 177 °C) Neobee M-20®(1) 0 to 375 °F (–18 to 191 °C) 3051T (Process Fill Fluid) Silicone Fill Sensor(1)–40 to 250 °F (–40 to 121 °C)(2) Inert Fill Sensor(1)–22 to 250 °F (–30 to 121 °C)(2) 3051L Low-Side Temperature Limits Silicone Fill Sensor(1)–40 to 250 °F (–40 to 121 °C)(2) Inert Fill Sensor(1) 0 to 185 °F (–18 to 85 °C)(2) 3051L High-Side Temperature Limits (Process Fill Fluid) Syltherm® XLT –100 to 300 °F (–73 to 149 °C) D.C. Silicone 704® 60 to 400 °F (15 to 205 °C) D.C. Silicone 200 –40 to 400 °F (–40 to 205 °C) Inert –50 to 350 °F (–45 to 177 °C) Glycerin and Water 0 to 200 °F (–18 to 93 °C) Neobee M-20 0 to 400 °F (–18 to 205 °C) Propylene Glycol and Water 0 to 200 °F (–18 to 93 °C) Isolating Diaphragm Material 3051CD/CG3051T3051CA3051H316L SST •••• Hastelloy C276 •••• Monel •• Tantalum •• Gold-plated Monel •• Gold-plated SST •• Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 11 Rosemount 3051 Rosemount 3051L Process Wetted Parts Flanged Process Connection (Transmitter High Side) Process Diaphragms, Including Process Gasket Surface •316L SST, Hastelloy C276, or Tantalum Extension • CF-3M (Cast version of 316L SST, material per ASTM-A743), or Hastelloy C276. Fits schedule 40 and 80 pipe. Mounting Flange • Zinc-cobalt plated CS or SST Reference Process Connection (Transmitter Low Side) Isolating Diaphragms • 316L SST or Hastelloy C276 Reference Flange and Adapter • CF-8M (Cast version of 316 SST, material per ASTM-A743) Non-Wetted Parts Electronics Housing Low-copper aluminum or CF-3M (Cast version of 316L SST, material per ASTM-A743). NEMA 4X, IP 65, IP 66 Coplanar Sensor Module Housing CF-3M (Cast version of 316L SST, material per ASTM-A743) Bolts ASTM A449, Type 1 (zinc-cobalt plated carbon steel) ASTM F593G, Condition CW1 (Austenitic 316 SST) ASTM A193, Grade B7M (zinc plated alloy steel) Monel K-500 Sensor Module Fill Fluid Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or Fluorinert® FC-43 for 3051T) Process Fill Fluid (3051L and 3051H only) 3051L: Syltherm XLT, D.C. Silicone 704, D.C. Silicone 200, inert, glycerin and water, Neobee M-20 or propylene glycol and water 3051H: inert, Neobee M-20, or D.C. Silicone 200 Paint Polyurethane Cover O-rings Buna-N Shipping Weights Refer to “Shipping Weights” on page 38 Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 17 Rosemount 3051 Dimensional Drawings 3051 Exploded View Certification Label Span and Zero Adjustments(1) (Standard) Electronics Housing Terminal Block Cover O-ring Cover Electronics Board Nameplate Sensor Module Housing Rotation Set Screw (180° Maximum Housing Rotation without Further Disassembly) Flange Alignment Screw (Not Pressure Retaining) Flange Bolts Flange Adapters Drain/Vent Valve Coplanar Flange Flange Adapter O-Ring Process O-Ring 3031B08A1) Span and Zero Adjustments are not available with fieldbus or profibus protocols. Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 20 3051T Dimensional Drawings Terminal Connections Transmitter Circuitry Nameplate 5.0 (127) 4.3 (110) 0.75 (20) Clearance for Cover Removal 0.75 (20) Clearance for Cover Removal 1/2–14 NPT Conduit Connection (Two Places, Other Sizes Available) Certification Label Housing Rotation Set Screw 7.2 (183) 4.1 (105)3051-3051TC6A, TB6A 3051T Typical Mounting Configurations with Optional Mounting Bracket Pipe Mounting Panel Mounting Dimensions are in inches (millimeters) 3.5 (90) 6.3 (160) 2 (50) 6.2 (156) 2.9 (72) 4.3 (110) 2.8 (71) 4.8 (120) 6.9 (175) 5.1 (130) Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007 29 Rosemount 3051 TABLE 12. 3051T Gage and Absolute Pressure Transmitter Model Transmitter Type 3051T Pressure Transmitter Code Pressure Type G Gage A Absolute Code Pressure Ranges (Range/Min. Span) 3051TG(1)3051TA 1 –14.7 to 30 psi/0.3 psi (–1,01 to 2,1 bar/20,7 mbar)0 to 30 psia/0.3 psia (0 to 2,1 bar/20,7 mbar) 2 –14.7 to 150 psi/1.5 psi (–1,01 to 10,3 bar/103,4 mbar) 0 to 150 psia/1.5 psia (0 to 10,3 bar/103,4 mbar) 3 –14.7 to 800 psi/8 psi (–1,01 to 55,2 bar/0,55 bar)0 to 800 psia/8 psia (0 to 55,2 bar/0,55 bar) 4 –14.7 to 4000 psi/40 psi (–1,01 to 275,8 bar/2,8 bar)0 to 4000 psia/40 psia (0 to 275,8 bar/2,8 bar) 5 –14.7 to 10000 psi/2000 psi (–1,01 to 689,5 bar/138 bar)0 to 10000 psia/2000 psia (0 to 689,5 bar/138 bar) Code Output A 4–20 mA with Digital Signal Based on HART Protocol M Low-Power 1–5 V dc with Digital Signal Based on HART Protocol (See Option Code C2 for 0.8–3.2 V dc Output) (Not available with hazardous certification Option Codes I1, N1, E4, K6 or K8) F FOUNDATION fieldbus Protocol W Profibus — PA Code Process Connection Style 2B 1/2–14 NPT Female 2C G½ A DIN 16288 Male (Available in SST for Range 1–4 only) 2F Coned and Threaded, Compatible with Autoclave Type F-250-C (Only available in SST for Range 5) Code Isolating Diaphragm Process Connection Wetted Parts Material 2(2)316L SST 316L SST 3(2)Hastelloy C276 Hastelloy C276 Code Fill Fluid 1 Silicone 2 Inert (Fluorinert® FC-43) Code Housing Material Conduit Entry Size A Polyurethane-covered Aluminum ½–14 NPT B Polyurethane-covered Aluminum M20 × 1.5 (CM20) C Polyurethane-covered Aluminum PG 13.5 D Polyurethane-covered Aluminum G½ J SST ½–14 NPT K SST M20 × 1.5 (CM20) L SST PG 13.5 M SST G½ Code PlantWeb Functionality A01 Advanced Control Function Block Suite D01 FOUNDATION fieldbus Diagnostics Suite Code Integral Mount Manifold (Optional) S5 Assemble to Rosemount 306 Integral Manifold (specified separately, see the Rosemount 305 and 306 Integral Manifolds PDS (document number 00813-0100-4733)) (Requires 1/2-in. process connection code 2B) Code Remote Diaphragm Seals Assemblies (Optional) S1 One remote diaphragm seal (Direct Mount or Capillary Connection Type) (Requires Process Connection Style code 2B) Code Mounting Brackets (Optional) B4 Bracket for 2-in. Pipe or Panel Mounting, All SST Product Data Sheet 00813-0100-4001, Rev GA Catalog 2006 - 2007Rosemount 3051 30 Code Hazardous Locations Certifications (Optional) E5 FM Explosion-proof Approval I5 FM Non-incendive and Intrinsic Safety Approval K5 FM Explosion-proof and Intrinsic Safety Approval C5 Measurement Canada accuracy approval (Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative) C6 CSA Explosion-proof and Intrinsic Safety Approval K6(3)CSA and ATEX Explosion-proof and Intrinsic Safety Approval (combination of C6 and K8) KB FM and CSA Explosion-proof and Intrinsic Safety Approvals (combination of K5 and C6) K7 SAA Flame-proof and Intrinsic Safety Approvals (combination of I7, N7, and E7) K8(3)ATEX Flame-proof and Intrinsic Safety Approvals (combination of I1 and E8) KD(3)CSA, FM, and ATEX Explosion-proof and Intrinsic Safety Approval (combination of K5, C6, I1, and E8) I7 SAA Intrinsic Safety Certification E4(3)JIS Flame-proof Certification E7 SAA Flame-proof Certification N7 SAA Type N Certification I1(3)ATEX Intrinsic Safety and Dust Certification N1(3)ATEX Type N and Dust Certification E8 ATEX Flame-proof and Dust Certification DW NSF drinking water approval IA ATEX Intrinsic Safety for FISCO; for FOUNDATION fieldbus protocol only Code Other Options Q4 Calibration Data Sheet Q8 Material Traceability Certification per EN 10204 3.1.B NOTE: This option applies to the process connection only. Q16 Surface finish certification for sanitary remote seals QP Calibration certification and tamper evident seal QS Certificate of FMEDA Data J1(4)(5)Local Zero Adjustment Only J3(4)(5)No Local Zero or Span Adjustment M5 LCD display for Aluminum Housing (Housing Codes A, B, C, and D only) M6 LCD display for SST Housing (Housing Codes J, K, L and M only) T1 Transient Protection Terminal Block C1(4)Custom Software Configuration (Completed CDS 00806-0100-4001 required with order) C2(4)0.8–3.2 V dc Output with Digital Signal Based on HART Protocol (Output Code M only) C4(4)(6)Analog Output Levels Compliant with NAMUR Recommendation NE 43, 27-June-1996. CN(4)(6)Analog Output Levels Compliant with NAMUR Recommendation NE 43: Low Alarm Configuration P1 Hydrostatic Testing with Certificate P2 Cleaning for Special Service P3 Cleaning for <1 PPM Chlorine/Fluorine P8 0.04% accuracy to 5:1 turndown (Range 1-4) V5(7)External Ground Screw Assembly Typical Model Number:3051T G 5 F 2A 2 1 A B4 (1) 3051TG lower range limit varies with atmospheric pressure. (2) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. (3) Not available with low-power Option Code M. (4) Not available with fieldbus (output code F) or Profibus protocols (output code W). (5) Local zero and span adjustments are standard unless Option Code J1 or J3 is specified. (6) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field. (7) The V5 option is not needed with T1 option; external ground screw assembly is included with the T1 option. TABLE 12. 3051T Gage and Absolute Pressure Transmitter