HomeMy WebLinkAboutAnalytical - TAB 2 - Rotronic Hygroflex Dewpoint AnalyzerNetworkable Industrial Transmitter
Humidity, Temperature and Dew Point
or other Computed Parameter
•Unique HygroClip®technology for superior performance•Durable, field proven humidity and temperature sensors•Interchangeable probe design eliminates maintenance downtime•Wide range of probes to satisfy every application•Optional display and keypad•Available with a metal enclosureHumidity goes Digital160 E. Main Street •Huntington, NY 11743 •Ph. (631) 427-3898 •Fax. (631) 427-3902 •www.rotronic-usa.com®®
Optional metal enclosure
HygroClip IC-3
Recommended for the measurement of most processes, this
probe is easily installed through a wall (see installation below).
For high RH% and high temperature processes see IM-3.
PPS body, wire mesh filter
Probe and probe cable: min. -50°C (-58°F), max. 200ºC (392ºF)
Probe connector: min. -40°C (-40°F), max. 85°C (185°F)
HygroClip IM-1
Similar to IC-3, but with a short body, this probe is designed for full
immersion in the process to be measured.
Temperature limits: same as IC-3
HygroClip IM-3
Similar to the IC-3, this probe should be selected for use in processes that
combine high humidity and moderate to high temperature such as pasta
dryers, environmental chambers, etc. - Stainless steel body, wire mesh filter
Temperature limits: same as IC-3
HygroClip IC-1
Similar to the IC-3, but with a short body, this probe can be installed well
inside the process to be measured. The IC-1 is also used for measuring
inside ducts with a small cross section. In both cases, the probe should be
fully immersed in the environment to be measured (see installation below)
PPS body, wire mesh filter
Temperature limits: same as IC-3
HygroClip IE-3
Measurement in compressed air. This probe has a 1/2" NPT thread and can
be used at pressures up to 50 bar/725 PSI. Not suitable in applications
where there is a temperature difference across the mounting wall.
min. -40°C (-40°F), max 85ºC (185ºF) sintered steel filter
Also available with 1/2"G thread (model IE-1)
HygroClip IC-05
5mm (0.2") diameter for measurement in tight spaces
min. -50°C (-58°F), max. 100ºC (212ºF)
AC1616 Probe Extension Cable
Suitable for use with all probes - built in signal booster.
Cable length 6 to 656 ft (2 to 200m)
min. -40°C (-40°F), max. 85°C (185°F)
HygroClip IW
Area monitoring (wall mounted transmitter)
wire mesh filter. Min. -40°C (-40°F), max. 85°C (185°F)
HygroFlex Probe Selection Guide
L. 145mm (5.7”) Dia. 15mm (0.6”)
Tube L. 250mm (9.8”) Dia. 15mm (0.6”) Cable: 2m (6.5ft)
Tube L. 120mm (4.7/10.6”) Dia. 15mm (0.6”) Cable: 2m (6.5ft)
Cable: 2m (6.5ft)
Dia. 5mm (0.2”) Cable: 2m (6.5ft)
Note: we also offer intrinsically safe probes for use in hazardous areas.
Standard Probes
Special Probes
Tube L. 100mm (3.9”) Dia. 15mm (0.6”) Cable: 2m (6.5ft)
Tube L. 270mm (10.6”) Dia. 15mm (0.6”) Cable: 2m (6.5ft)
Installation of probes type IC and IM
IC-3 and IM-3 probes (long probe body): the QMA-15 adapter is convenient both for installing
and servicing the probe. The adapter is comprised of a compression fitting and a 3'' flange. The
probe should be immersed as much as possible in the process to be measured, especially when
temperature is not the same on both sides of the wall.
IC-1 and IM-1 probes (short probe body): the probe and its cable should be fully immersed in the environment to be measured (leave the
probe connector outside). In a duct of small cross section, install the probe axially. Attach the probe with a clip, a tie or a bracket at a well
ventilated location (such as a vent). Do not install the probe through or against a wall, unless temperature is the same on both sides of the
wall: insufficient probe immersion will result both in a temperature and a humidity error.
QMA-15 min. 7"
Humidity goes Digital
®
HygroFlex 2:100% Digital
•%RH and temperature and calculated value
(dew-point, mixing ratio, etc)
•RS232 output (%RH and temperature)
•Networkable (RS232 first HygroFlex to PC / RS485
between transmitters)
•Optional 2nd probe input (digital or analog)
•Fully user programmable
HygroFlex 3:Analog & Digital Outputs
•%RH, temperature and calculated value
(dew-point, mixing ratio, etc)
•Three linear analog outputs: 4-20 mA, 0-5V, etc.
•Jumper configuration of analog outputs signal type
•Simultaneous digital output
•RS232 output (%RH and temperature)
•Networkable (RS232 first HygroFlex to PC / RS485
between transmitters)
•Optional 2nd probe input (digital or analog)
•Fully user programmable PCHygroPalm
Calibrator
Analog
Outputs
RS232
RS485
PC
HygroPalm
Calibrator RS232
RS485
The HygroFlex industrial humidity and temperature
transmitter uses the very latest digital technology.
Digital signal processing significantly benefits humidity and
temperature measurement in the following key areas:
1.Measurement Accuracy
The digital circuits used both in the HygroFlex and associated
probe are inherently more stable and consistent than
conventional analog circuits. Digital processing of the sensor
signals by the probe also provides more scope and greater
flexibility when compensating sensor linearity and temperature
coefficient. The ROTRONIC HYGROMER™capacitive humidity
sensor has always been the leader both in precision and
stability. With the application of digital technology, sensor
performance is now further improved.
2. Maintenance and Calibration
Unique HygroClip®digital technology virtually eliminates
downtime during maintenance. When it is time for a scheduled
calibration, the interchangeable probe can be ‘hot swapped’ in
seconds with a calibrated replacement probe. There is no need
to remove the complete transmitter to a calibration laboratory
and there is practically no interruption of the measurement data.
The HygroClip probe can be directly calibrated while connected to
the HygroFlex (requires the optional display and keypad), or it can
be calibrated separately using either a PC or the HygroPalm
The Digital Advantage
portable calibrator. Calibration and sensor data are retained
permanently within each HygroClip probe. Software-based
calibration is both simple and precise; there are no hard-to-
reach, hard-to-adjust potentiometers. Multiple calibration points
can be selected across the full measuring range.
On-site performance verification is equally easy. Each
HygroFlex has a test connector for use with a portable
HygroPalm calibrator. The HygroPalm can display the signals
from the HygroFlex without interrupting operation and a
comparison can be made with the readings of the probe
connected to the HygroPalm.
3.Measurement of
Dew-Point and other Parameters
Digital technology makes it possible to obtain parameters
such as dew-point or the mixing ratio with economical,
versatile and easy-to-maintain instruments and probes.
Comparing the HygroFlex to existing chilled mirror technology
typical requirements and problems are eliminated: no
sampling system is required in most applications, the
uncertainty between dew and frost is eliminated, and there is
no mirror that requires frequent cleaning.
SPECIFICATIONS (inclding probe) HYGROFLEX 2 HYGROFLEX 3
Number of probe inputs 1 (standard) / 2 (option)
Probe type Digital (HygroClip)
Analog: 0...2.5V input (scalable), 15V DC, 10mA
Probe calibration requires display/keypad option (probe can also be calibrated separately)
Probe calibration via PC requires cable AC1623 and HW3 software
Calculated parameter Dew-point, wet-bulb, enthalpy, mixing ratio, specific humidity, water
vapor pressure, saturation vapor pressure.
Pressure input for calculated values 1) Fixed value Fixed value or automatic with
(user defined) analog pressure probe (requires
2nd probe input option)
User defined calculation HygroFlex can be programmed with the HW3 software to compute and output a
user defined calculation such as the difference between temperature and dew
point, a difference between two dew points, etc.
Transmitter measuring range 0…100%RH, -50…+200°C (-58…+392°F)
Temperature limits at probe see Probe Selection Guide
Accuracy (at 23°C/73°F) ± 1.0%RH ± 0.2°C (0.4°F)
Repeatability ±0.3%RH and better than 0.1°C (0.2°F)
Sensors Hygromer
®C94 capacitive humidity sensor, Pt100 1/3 DIN RTD
Transmitter operating limits 0…99%RH non-condensing, -40…+60°C (-40…140°F), -30…+60°C with display
Optional display and keypad ICD 2-line numeric, 1 line alphanumeric,
1/4" character height, membrane keypad
Resolution of optional display 0.1%RH/°C/°F
0.001 calculated parameter or pressure (depends on parameter)
Power 12...35VDC (300mA max.) / 12...24VAC or 90...264VAC
Analog outputs N/A 3
2)
Analog output type N/A 4…20mA or 0…20mA
0…1V, 0…5V, 0…10V (jumper selectable)
Load limit for analog outputs N/A current outputs ≤500 ohm
voltage outputs ≥1000 ohm
Electrical connections for power cable - standard: 1 x for power and analog signals
(power / analog outputs) cable grip, (7mm/0.275") cables - standard: 2 x cable grip,
optional: 1 x 1/2" conduit adapter (7mm/0.275")
optional: 2 x 1 /2"conduit adapter
Connection terminals 18 AWG (power) 18 AWG (power, analog outputs)
RS232 and RS485 outputs Transmitter provides data each time that a data request command is received.
5-pin receptacle common to both RS232 and RS485 – a matching
2-cable connector is provided together with the HygroFlex
Test connector allows reading the measurement data and probe calibration
with HygroPalm 3 indicator
Housing Standard ABS housing: 207 x 150 x 59mm (8.15 x 5.90 x 2.32"), 310g (0.7 lb).
Optional Aluminum housing: 245 x 135 x 75mm (9.65 x 5.32 x 2.95"), 1300g (2.86 lb)
Protection grade IP65/NEMA4
CE Conformity EN580081-2, EN50082-2
Notes
1) Barometric pressure is required as an input parameter for the computation of wet bulb temperature, mixing ratio, enthalpy and
specific humidity. When a fixed pressure value is used, this value can be set by the user by connecting the HygroFlex to a PC
with the optional HW3 software installed.
2) Any of the 3 analog outputs of the HygroFlex 3 can be set to correspond to humidity [probe 1 or 2] or temperature [probe 1 or
2] or calculated psychrometric parameter [probe 1 or 2] or user defined calculation, or to optional analog probe signal (such as
pressure).
Product Summary & Technical Data
Humidity goes Digital
®
Ordering A Hygroflex 2 or 3
Modifications reserved Rev. 08/05/02HTS
Notes
1. Calibration device: this is a small chamber that seals tightly around the tip of the probe. Using one of the available calibration standards
(such as EA35-SCS), a known humidity is generated inside the calibration device. Upon reaching equilibrium with the humidity standard,
the probe can be adjusted to match the value of the standard.
2. Probe simulator: plugs on the HygroFlex in lieu of the HygroClip probe to provide known fixed values for both humidity and temperature.
This is useful when there is a requirement to validate the electronics of the HygroFlex.
Notes
1. Output is jumper selectable and can easily be changed in the field without any required calibration. The range of the output signal (for
example 0…300°F) is not affected.
2. The range of all outputs (%RH, Temperature) can be changed using the Rotronic HW3 software.
3. Enter as a separate line item the span of the calculated value along with the units of output. i.e. g/m3 or gr/ft3.
2 HygroFlex 2: digital output Notes
3 HygroFlex 3: digital and analog outputs
1 12…35 VDC / 12…24 VAC Powered
2 90…250 VAC 50-60Hz Powered
A ABS enclosure
M Aluminum enclosure – conduit only
G = cable grips
C = 1/2" conduit fittings
D Digital Display and Keypad
N No Digital Display
1 %RH and temperature to be displayed
2 Calculated value and %RH to be displayed
3 Calculated value and temperature to be displayed
N No Digital Display
Select output and enter appropriate code
1 4…20mA 3 0…1 VDC 5 0…10 VDC 1
2 0…20mA 4 0…5 VDC
Select a Temperature Span from the following
1 0…100ºF 3 0…300ºF 5 0…200ºC 2
2 0…200ºF 4 0…100ºC 6 -50…150ºC
Select Computed Parameter. Enter an “X” if none.
1 Dew Point 4 Absolute Humidity 7 Partial Pressure 3
2 Wet Bulb Temp.5 Mixing Ratio 8 Vapor Conc. @ sat
3 Enthalpy 6 Specific Humidity
Select probe to be used.
1 IW 3 IC-3 5 IM-3 7 IC-05
2 IC-1 4 IM-1 6 IE-3
Extension cable – max. length is 656 feet
X = No extension cable
Enter length of extension cable in feet
Enter Ordering Code To Left
HTS
HTS
2
3
1
2
A
M
G
C
D
N
E
X
Enter a “S” if special temperature
range is desired. Also specify range
as separate line on purchase order
Please, also specify computed
parameter range as separate line
on purchase order
ACCESSORIES & OPTIONS
Order code: Description: Order code: Description:
OUT3-16bit 16-bit D/A converter option, allows improved resolution on AC1618/XX Probe simulator
(HygroFlex 3) a scale of more than 200 units on analog output 3 xx = 35%, 50%, 80%RH: 25°C/77°F
HW3 HW3 configuration software ERV-15 Calibration device for type ‘IW’ probes
AC1623 HygroFlex configuration cable ER-15 Calibration device for 15mm diameter probes
T7-03-WIN Calibration cable HygroClip Probe to PC ER-05 Calibration device for 5mm diameter probes
HygroPalm 3 HygroPalm, calibrator for HygroFlex EM-15 Calibration device for type ‘IE’ probes
AC1620 Cable HygroPalm 3 to HygroFlex
QMA-15 Probe adapter for HygroClip IC-3 and IM-3
EQUIVALENCE TABLE
Previous Models Configuration HygroFlex and Probe
HC321-W, HC322-W Wall mount HygroFlex 3 + IW probe
HC321A-R, HC322-R remote probe HygroFlex 3 + IC-3 probe+ QMA-15 adapter
Cal. standard, SCS Certificate, pack 5
xx = 00, 05, 10, 20, 35, 50, 65, 80 or 95 (%RH).
use EA35 and EA80 for minimum calibration
EAxx-SCS