HomeMy WebLinkAbout014_Appendix M - Water Engineering Design ReportEngineering Report
Water Main Extension
South University District
Phase 3 - Block 3
Preliminary Plat
Updated May 2026
Submitted to:
City of Bozeman Engineering Department
20 East Olive
Bozeman, MT 59715
Prepared by:
Stahly Engineering and Associates
851 Bridger Drive, Suite 1
Bozeman, MT 59715
(406) 522-8594
Water Mains 1 5/26/2026
Engineering Report
Contents
Note: The Engineering Report format follows DEQ-1 organization. Additional
information required by the City of Bozeman Design Standards is added where
required.
Report Narrative
1.1.1 General Information
1.1.2 Extent of water works system
1.1.3 Alternate plans
1.1.4 Site conditions
1.1.5 Water use data
1.1.6 Flow requirements
1.1.7 Sources of water supply
1.1.8 Proposed treatment processes
1.1.9 Sewage system available
1.1.10 Waste disposal
1.1.11 Automation
1.1.12 Project Sites
1.1.13 Financing
1.1.14 Future Extensions
Figures and Tables
Figure 1. Vicinity Map
Figure 2. C2.0 - Water Plan
Table 1. SUD Phase 3 Block 3 Estimated Water Design Flows
Appendices
WaterCAD Analysis Exhibit – To be provided with infrastructure submittal.
WaterCAD Fire Flow Table – To be provided with infrastructure submittal.
WaterCAD Junction Table – To be provided with infrastructure submittal.
WaterCAD Pipe Table – To be provided with infrastructure submittal.
Water Mains 2 5/26/2026
1.1.1 General Information
The proposed South University District Phase 3 Block 3 Subdivision
consists of 17.51 Acres located southeast of the intersection of 19th
Avenue and Stucky Road. The Block 3 subdivision will consist of 2 lots
with the north lot being approximately 8.84 acres and the south lot being
8.65 acres. The total subdivision area including required offsite
improvements is 23.26 acres.
This Block 3 Subdivision is designed with the intention of there being 256
residential units between the two lots to create a diversified neighborhood
in a growing part of town, adjacent to the Montana State University
Campus.
The project will be served by extension of City of Bozeman water and
sewer mains throughout the project. City of Bozeman water and sewer
mains currently exist along the west side of the project site.
The developer’s contact information is:
RTR Holdings II, LLC
Randy Hecht
22 Turtle Rock Court
Tiburon, CA 94920
Water supply and wastewater treatment will be provided by the City of
Bozeman’s municipal systems. The system owner’s contact information is:
City of Bozeman Public Service Department
PO Box 1230
Bozeman, MT 59771-1230
Water Mains 3 5/26/2026
The location of the SUD Phase 3 Block 3 development is shown on the
Vicinity Map in Figure 1.
Figure 1. Vicinity Map, Bozeman, Montana
1.1.2 Extent of Water Works System
Water supply to the area is from an existing 24” water main in S 19th Ave,
and an existing 12” water main in Stucky Road. There is an existing 8”
water main in S 17th Ave that will be extended south from Stucky Road
along with new 8” water mains in the proposed Arnold Street and Student
Dr. that will be installed as part of the off-site subdivision improvements to
service the new development.
It is anticipated that future lot development will require on-site main
extensions in combined 30-foot-wide water and sewer easements. 8”
water main stubs are provided to lot lines for both lots where the on-site
main extensions are envisioned.
Water Mains 4 5/26/2026
1.1.3 Alternate Plans
Due to the project’s location within the City of Bozeman, extension of
public mains was the only water supply alternative. Distribution
alternatives were explored, and the proposed design was selected to
increase looping and minimize dead ends. The use of an on-site well as a
source for irrigation usage is not feasible due to the previously allocated
water rights in the Phase 2 subdivision park.
1.1.4. Site Conditions
The SUD Phase 3 Block 3 site is typical of Bozeman with fine-grained
soils overlying gravel deposits. Geotechnical borings have determined the
depth to gravel ranges from 2.5 to 6.5 feet. Estimated depth to
groundwater obtained from the geotechnical borings is variable from 4 to 9
feet. If mains are installed during periods of high groundwater, dewatering
may be required.
1.1.5. Water Use Data
The estimated residential water use was based on the City of Bozeman
design standards for wastewater generation. The estimated flow was
determined based on 2.17 people per unit and an average daily flow rate
of 64.4 gpd/person in accordance with the City of Bozeman Design
Standards Utility Design Criteria. For the purposes of analysis, Block 3, lot
1 and Block 3, lot 2 were treated as one lot and are both encompassed in
this report by being referenced under “Block 3”. Further analysis of each
individual lot is to be conducted during their respective site plans.
The anticipated Subdivision irrigation is based on previous designs and
calculations by the Landscape Architect as show in the landscape plans.
Irrigation is the only water demand for the offsite development of the
subdivision and is estimated to be an annual use of 194,985 Gallons. This
covers the irrigation on the South side of Stucky Road and the East Side
of S 19th Avenue.
The anticipated site irrigation is also based on previous designs and
calculations by the Landscape Architect as show in the landscape plans.
The following table displays the combined residential, commercial, and
irrigation water design flows. The design max day peak hour flow for the
proposed Block 3 is 140.24 gpm.
Water Mains 5 5/26/2026
Table 1: SUD Phase 3 Block 3 Estimated Water Design Flows
1.1.6. Flow Requirements
As stated previously, the peak hour water demand is estimated to be
140.24 gallons per min (gpm). Fire flows have not been determined yet
but will be in accordance with the City of Bozeman adopted Uniform Fire
Code. It is anticipated that a fire flow of 1,500 gpm will be required. The
fire flow requirement will be the dominant design constraint for system
design.
As part of the Phase 3 Subdivision process, a hydraulic analysis was
completed to determine the available fire flow in this area. According to
this analysis, Phase 3 hydrants – including those in Block 3 – will have fire
flows ranging from 2,800 gpm to 3,100 gpm, with a system residual
pressure of 20 psi.
Fire flow requirements are based on the Uniform Fire Code. The required
hydrant flow is determined using Table H.5.1 of the Uniform Fire Code.
For example, a 48,000 sq ft Type V-A building requires a fire flow of 4,000
gpm. In consideration of the planned use of sprinkler systems in future
Phase 3 site developments projects, the fire department is allowing a 75%
reduction in required fire flows, reducing the hydrant flow down to the
anticipated minimum required fire flow of 1500 gpm. The fire flow required
will be determined by the fire department at the time of infrastructure
design. The total fire flow available will allow for the use of the hydrant and
the sprinkler while maintaining the required 20 psi residual pressure.
The Phase 3 Subdivision Engineer’s report is available upon request.
Water Mains 6 5/26/2026
1.1.7. Sources of Water Supply
This section is not applicable.
1.1.8. Proposed Treatment Process
This section is not applicable.
1.1.9 Sewage System Available
Sewer service is provided by new City mains extended through the site
from the existing sewer main running along Stucky Rd. and 19th Ave.
Sewers will be approximately 8.5 feet deep and primarily cross below
water mains and services.
1.1.10 Waste Disposal
This section is not applicable.
1.1.11 Automation
This section is not applicable.
1.1.12 Project Sites
This section is not applicable.
1.1.13 Financing
This section is not applicable.
1.1.14 Future Extensions
The water system layout accommodates future water main extensions as
required to complete future system improvements in this area.
SSSSSSSSSSSSSSW W W WSSSS SS SS
WSDSDSDSDSDSD
SDSDSDWWWWWSOUTH 14TH AVESS
HC HC
HC HC
OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHESSSSSSSSSS
SSSSSSW WSSSSSSSSSSSSOHEOHEOHESDSDSDWWWY3
Y3
Y3
Y3Y3
P3
P3
P3
SDSDSDSDSD SDSDSDSDSDSDSDSDSDSD STUCKY RDSOUTH 14TH AVESTUCKY RD(48' WIDTH - 90' ROW)W W W W W W W W W W W WOHEOHEOHE (48' WIDTH - 90' ROW)**WWWWWWWWWWWWWWWWWWWWWWWSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSWWSSSSSSSTATE ST(35' WIDTH - 60' ROW)SD(47' WIDTH - 70' ROW)SSSS SOUTH 17TH AVE(EXISTING 70'
ROW)
STUCKY RD(48' WIDTH - 90' ROW)
ARNOLD ST(36' WIDTH - 105' ROW)
SD
SOUTH 14TH AVESOUTH 17TH AVE(47' WIDTH - 70' ROW)S 19TH AVE(ROW WIDTH VARIES)S 19TH AVE(ROW WIDTH VARIES)OHEOHEOHEOHEOHEOHEOHEOHEOHEOHEOHEEXISTINGTRAILS (TYP)SSSSSSSSSSSSSSSSSSWWWWWWWWWWSTORM BASINS
T
O
RM
BA
S
IN (47' WIDTH - 70' ROW)STUDENT DRIVES 19TH AVE(ROW WIDTH VARIES)EXISTINGSTORM BASIN CITY PARK 14.41 ACRESPLAT J-605Tract 3ACOS 2661B
CITY PARK 2
9.64 ACRES
PLAT J-605
CITY PARK 41.83 ACRESPLAT J-695COMMON OPEN SPACELOT 2, BLOCK 1, 0.07 ACPLAT J-695COMMON OPEN SPACELOT 1, BLOCK 2, 0.07 ACPLAT J-695 COMMON OPEN SPACELOT 2, BLOCK 2, 0.07 ACPLAT J-695 BLOCK 3 , LOT 1A8.840 ACRES(385,071 SF)CITY PARK 3
13.36 ACRES
PLAT J-695
LOT 2 "PHASE 1"6.41 ACRESPLAT J-518
BLOCK 3 SUBDIVISIONINFRASTRUCTURE EXTENTSBLOCK 3 SUBDIVISIONINFRASTRUCTUREEXTENTSARNOLD ST
STUDENT DRIVE
SOUTH 17TH AVES 19TH AVESTUCKY RD
YELLOWSTONE THEOLOGICAL
INSTITUTE MINOR SUBDIVISION
RESTRICTED LOT 4
10.519 ACRES
YELLOWSTONE THEOLOGICAL
INSTITUTE MINOR SUBDIVISION
COMMON OPEN SPACE LOT 2
1.826 ACRES
YELLOWSTONE THEOLOGICAL
INSTITUTE MINOR SUBDIVISION
LOT 3
7.644 ACRES
YELLOWSTONE THEOLOGICAL
INSTITUTE MINOR SUBDIVISION
LOT 1
15.069 ACRES
ALLISON
SUBDIVISION, PH 4A
BLOCK 1, LOT 1
22.50 ACRES
W WWW
SDBLOCK 3, LOT 1B8.636 ACRES(376,169 SF)WWWWW(36' WIDTH - 62' ROW)SSWWWWWW W SSSSSSSSSSSS SSWW SSSSW WSSSSSDSDSDSDSDSDSDSDSDSDSD SDSDSD SDSDSD SDWW WSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDWWWWW WWWWSDSDSDSDSSSS EXISTING
TRAILS (TYP)
EXISTING
TRAILS (TYP)SSSSSSSSLOT 1, BLOCK 2"PHASE 3"8.60 ACRESPLAT J-695
WWSDSDSDSDSDSDSSWWWWSSSSSSSS(27' WIDTH - 70' ROW+29.5' EASE)ARNOLD ST
SCALE IN FEETC2.0WATER PLAN1 12/15/2025 PRELIMINARY PLAT ZWL CDP
2 5/26/2026 PRELIMINARY PLAT RC1 JWF CDP PROFESSIONALENGINEERS &SURVEYORSSTAHLYENGINEERING& ASSOCIATESSUD PH. 3 BLOCK 3SUBDIVISION