HomeMy WebLinkAboutMill Building Renovations - Infrastructure PlansVICINITY MAP PROJECT NO: BANGTAIL PARTNERS LLC MENLO PARK, CA 94026-2652 PO BOX 2652 DEPT 35 PREPARED FOR: MILL BUILDING RENOVATIONS INFRASTRUCTURE PLANS FOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMAN BOZEMAN,MT 06020.12 RECORD DRAWING C1.1.1 FILE: PROJECT NO: CAD: QUALITY ASSURANCE: DRAWING HISTORY DATE DESCRIPTION 06020.12 -- - - - - RECORD DRAWING BP COMMENTS - - - - 09/03/2026 06/13/2025 INFRASTRUCTURE SUBMITTAL3/28/2025 DME/MGB 06020_12_COVER_PROD_INF.DWG RPE 106 East Babcock, Suite L1 Bozeman, Montana 59715 406.522.9876 sanbell.com SITE 1 2 3 4 5 6 7 8 Sheet List Table SHEET TITLE C1.1.1 COVER C1.2.1 LEGEND, NOTES & ABBREVIATIONS C2.1.1 EXISTING TOPOGRAPHY & DEMOLITION C3.1.1 SITE PLAN C4.1.1 GRADING PLAN C5.1.1 FIRE LINE PLAN & PROFILE C6.1.1 DETAILS C6.2.1 DETAILS RECORD DRAWINGEW = FINISHED GRADE AT EDGE OF WALK TC = FINISHED GRADE AT TOP BACK OF CURB BC = FINISHED GRADE AT BUILDING CORNER TW = FINISHED GRADE AT TOP OF WALL AC = FINISHED GRADE AT ASPHALT EA = FINISHED GRADE AT EDGE OF ASPHALT EC = FINISHED GRADE AT EDGE OF CONCRETE SDI = STORM DRAIN INLET SDMH = STORM DRAIN MANHOLE FL = FINISHED GRADE AT FLOWLINE FG = FINISHED GRADE EX = APPROXIMATE EXISTING ELEVATION POC = POINT ON CURVE WTR = WATER PI = POINT OF INTERSECTION PRC = POINT OF REVERSE CURVE RT = RIGHT LT = LEFT SS = SANITARY SEWER PT = POINT OF TANGENCY SD = STORM DRAIN GV = GATE VALVE BFV = BUTTERFLY VALVE RED = REDUCER LF = LINEAL FOOT FT = FEET SSMH = SANITARY SEWER MANHOLE BVC = BEGIN VERTICAL CURVE CS = CURB STOP EVC = END VERTICAL CURVE PVI = POINT OF VERTICAL INTERSECTION LINETYPES ABBREVIATIONS SYMBOLS KEYNOTE CALL OUT (SEE KEYNOTE LEGEND) SRVC = SERVICE (TYP.) = TYPICAL PC = POINT OF CURVATURE NOTE: -EXISTING UNDERGROUND INSTALLATIONS & PRIVATE UTILITIES SHOWN ARE INDICATED ACCORDING TO THE BEST INFORMATION AVAILABLE TO THE ENGINEER. THE ENGINEER DOES NOT GUARANTEE THE ACCURACY OF SUCH INFORMATION. SERVICE LINES (WATER, POWER, GAS, STORM, SEWER, TELEPHONE & TELEVISION) MAY NOT BE STRAIGHT LINES OR AS INDICATED ON THE PLANS. STATE LAW REQUIRES CONTRACTOR TO CALL ALL UTILITY COMPANIES BEFORE EXCAVATION FOR EXACT LOCATIONS. -ALL IMPROVEMENTS SHALL BE PERFORMED IN ACCORDANCE WITH MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS 7TH EDITION, APRIL, 2021, AND THE CITY OF BOZEMAN STANDARD MODIFICATIONS, DATED OCTOBER, 2024. -UNLESS OTHERWISE SPECIFIED, ALL CONSTRUCTION LAYOUT AND STAKING SHALL BE PERFORMED UNDER THE RESPONSIBLE CHARGE OF A LAND SURVEYOR LICENSED IN THE STATE WHERE THE PROJECT IS LOCATED AND BY A PARTY CHIEF OR ENGINEERING TECHNICIAN EXPERIENCED IN CONSTRUCTION LAYOUT AND STAKING TECHNIQUES AS ARE REQUIRED BY THE SPECIFIC TYPE OF WORK BEING PERFORMED. GR = EXISTING GRADE AT GROUND BRK = GRADE BREAK FIBER OPTIC GAS PIPELINE OIL PIPELINE UNDERGROUND POWER SANITARY SEWER STORM DRAIN TELEPHONE TELEVISION/CABLE WATER CONTOUR OVERHEAD POWER FENCE - VINYL FENCE - BARBED WIRE FENCE - WOOD CURB AND GUTTER EDGE OF ASPHALT EDGE OF GRAVEL FENCE - CHAINLINK/ WOVEN WIRE EXISTING PROPOSED HP = HIGH POINT FILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANLEGEND, NOTES & ABBREVIATIONSMILL BUILDING RENOVATIONINFRASTRUCTURE PLANSBOZEMAN,MTC1.2.1 RPE06020_12_COVER_PROD_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.12DEMO AREA PROPOSED ASPHALT PROPOSED CONCRETE PROPOSED GRAVEL LIQUID PROPANE PIPELINE ELECTRIC JUNCTION BOX EXISTING STORM DRAIN MANHOLE EXISTING CATCH BASIN SIGN POWER POLE EXISTING WATER VALVE EXISTING FIRE HYDRANT BOLLARD BUSH EXISTING CURB STOP FIRE DEPT. CONNECTION FIBER OPTIC PEDESTAL GAS METER GAS MANHOLE GAS VALVE GUYWIRE IRRIGATION VALVE IRRIGATION BOX LIGHT POLE POWER METER POWER MANHOLE ELECTRIC PEDESTAL PROPOSED ROOF DRAIN SIGNAL POLE EXISTING SANITARY SEWER MANHOLE PROPOSED SANITARY SEWER CLEAN OUT TELEPHONE BOX TELEPHONE MANHOLE TELEPHONE PEDESTAL TRANSFORMER CONIFEROUS TREE DECIDUOUS TREECOMMUNICATIONS MANHOLE COMMUNICATIONS PEDESTAL WELL YARD HYDRANT EXISTING WATER REDUCER GAS WELL FOUND CORNER MONUMENT AS NOTED SET CORNER MONUMENT, REBAR WITH CAP BENCHMARK SECTION QUARTER CORNER SECTION CORNER PROPOSED CATCH BASIN PROPOSED WATER REDUCER PROPOSED WATER VALVE PROPOSED FIRE HYDRANT PROPOSED CURB STOP PROPOSED SANITARY SEWER MANHOLE PROPOSED STORM DRAIN MANHOLE EXISTING MONUMENT BOX PROPOSED MONUMENT BOX EXISTING WATER MANHOLE WATER METER PROPOSED STORM DRAIN CLEAN OUT CATCH CURB SPILL CURB TRANSITION FROM CATCH TAPER CURB HEAD 3' TO SPILL CURB GRADING PLAN TOP OF CURB - 0.62' = LIP TOP OF CURB - 0.51' = FLOWLINESPILL CURB TOP OF CURB - 0.46' = LIP TOP OF CURB - 0.51' = FLOWLINECATCH CURB CP#1 CP#10 CP#200 RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANEXISTING TOPOGRAPHY & DEMOLITIONMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC2.1.1 RPE06020_12_EX_PROD_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.120 20 SCALE: 1" = 20' 401020 RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANSITE PLANMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC3.1.1 RPE06020_12_SITE_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.120 20 SCALE: 1" = 20' 401020 RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANGRADING PLANMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC4.1.1 RPE06020_12_GRADING_PROD_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.120 20 SCALE: 1" = 20' 401020 RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANFIRE LINE PLAN & PROFILEMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC5.1.1 RPE06020_12_UTILITY_PROD_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.12VERTICAL SCALE: 1"=10' 5 3 0 HORIZONTAL SCALE:1" = 5' 5 10 CITY OF BOZEMAN NOTES: 1.ALL CONSTRUCTION WILL CONFORM TO MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS (MPWSS) 7TH EDITION, APRIL, 2021, AND THE CITY OF BOZEMAN STANDARD MODIFICATIONS, DATED OCTOBER, 2024. 2.ANY EXISTING OR NEW VALVES WHICH CONTROL THE CITY OF BOZEMAN'S WATER SUPPLY SHALL BE OPERATED BY CITY OF BOZEMAN PERSONNEL ONLY. 3.THE CONTRACTOR SHALL NOTIFY THE WATER DEPARTMENT A MINIMUM OF 24-HOURS PRIOR TO BEGINNING OF WORK. 4.CONTRACTOR SHALL FIELD-VERIFY LINE AND GRADE OF EXISTING CONNECTIONS. 5.A PRE-CONSTRUCTION MEETING MUST BE SCHEDULED WITH THE CITY OF BOZEMAN WATER AND ENGINEER DEPARTMENTS PRIOR TO INSTALLATION OF THE FIRE LINE AND DOMESTIC SERVICE. 6.CONTRACTOR SHALL INSTALL NEW WATER MAIN AND FIRE LINE WITH RESTRAINED JOINT PIPE AND FITTINGS. 7.ALL DUCTILE IRON PIPE AND FITTINGS INCLUDING HYDRANTS, VALVE BOXES, CURB BOXES, AND ALL OTHER METAL PARTS AND SURFACES SHALL BE ENCASED WITH V-BIO® TM ENHANCED POLYETHYLENE ENCASEMENT. 8.THE POLYETHYLENE ENCASEMENT SHALL BE OVERLAPPED ONE FOOT IN EACH DIRECTION AT JOINTS AND SECURED IN PLACE AROUND THE PIPE, AND ANY WRAP AT TAP LOCATIONS SHALL BE TAPED TIGHTLY PRIOR TO TAPPING AND INSPECTED FOR ANY NEEDED REPAIRS FOLLOWING THE TAP. 9.NEW WATER MAIN AND FIRE LINE TO BE INSTALLED IN TYPE I PIPE BEDDING WITH TYPE A TRENCH BACKFILL AND RESTRAINED JOINTS ACCORDING TO DETAIL SHEET C6.1.1. 10.CONTRACTOR SHALL PERFORM A PRESSURE TEST AND LEAKAGE TEST ON ALL INSTALLED WATER PIPES IN ACCORDANCE WITH CITY OF BOZEMAN STANDARDS. 11.CONTRACTOR SHALL FLUSH, DISINFECT AND TEST ALL WATER PIPES IN ACCORDANCE WITH CITY OF BOZEMAN STANDARDS. RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANDETAILSMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC6.1.1 RPE06020_12_DETAILS_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.12LEGEND FLANGED OS&Y VALVE DOUBLE CHECK VALVE (MIN. REQUIREMENT) AS INDICATED ON APPROVED PLAN(S) CITY OF BOZEMAN REQUIREMENTS FOR INSTALLATION OF DOUBLE CHECK VALVE ASSEMBLY 1.THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL-LISTED FLANGED KENNEDY OR MUELLER OS&Y VALVE THE SAME SIZE AS THE FIRE SERVICE LINE. 2.ALL DOUBLE CHECK VALVE ASSEMBLIES SHALL BE: A.UL OR FM LISTED B.APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC RESEARCH (USCFCCCHR) FOR OPERATION IN THE PROPOSED POSITION (VERTICAL OR HORIZONTAL) AS SHOWN ON APPROVED PLANS. C.INSTALLED AS SHOWN ON THE APPROVED PLANS. 3.A FLOW DETECTION DEVICE SHALL BE INSTALLED IMMEDIATELY FOLLOWING THE DOUBLE CHECK VALVE ASSEMBLY (ALARM CHECK VALVE, FLOW SENSOR/ALARM, METER, ETC.) AS SHOWN ON THE APPROVED PLANS. PADDLE-TYPE FLOW ALARMS ARE NOT PERMITTED ON DRY SYSTEMS. 4.A DOUBLE DETECTOR CHECK VALVE ASSEMBLY MAY BE USED WITH A STANDARD CITY OF BOZEMAN METER. THE METER LOOP OF THE DOUBLE DETECTOR CHECK VALVE SHALL HAVE A DOUBLE CHECK VALVE ASSEMBLY INSTALLED WHICH MEETS THE SAME INSTALLATION CRITERIA SPECIFIED ABOVE IN REQUIREMENT NUMBER TWO. 5.HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF 2' ABOVE THE FINISHED FLOOR. 6.THE FIRE SERVICE RISER MUST BE A MINIMUM OF 2' FROM ANY OUTSIDE WALL, AND A MINIMUM OF 1' FROM ANY INTERIOR WALL. 7.THE INCOMING FIRE SERVICE LINE SHALL BE A MINIMUM OF 6.5', AND A MAXIMUM OF 7.5' BELOW THE FINISHED GRADE. 8.ALL FIRE SERVICE LINE APPURTENANCES SHALL HAVE A MINIMUM PRESSURE RATING OF 175 PSI. 9.ALL FIRE SERVICE LINES 4" AND LARGER SHALL BE CLASS 51 DUCTILE IRON PIPE. 10.LINE SIZING: THE DOUBLE CHECK VALVE ASSEMBLY SHALL BE EQUAL IN SIZE TO BOTH THE INCOMING PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE DIAMETER (DOWNSTREAM). ONLY FITTINGS ALLOWED BETWEEN FIRST OS&Y VALVE AND BACKFLOW ASSEMBLY TO BE 90° BEND. NO PRESSURE GAUGES OR PRESSURE GAUGE FITTINGS WILL BE ALLOWED ON THE TEST PORTS OF ANY BACKFLOW ASSEMBLY. FLANGE TO BE THREADED ON STANDPIPE, M.L. TO FLANGE ADAPTORS NOT ACCEPTABLE (TYP. FOR ALL RISER CONFIGURATIONS) 1' MIN., 2' MAX. ABOVE FINISHED FLOORFLOOR 3/4" MIN. REDI ROD, INSTALLED IN EVERY OTHER AVAILABLE M.J. BOLT HOLE (TYP.). 5/8" RODS ACCEPTABLE FOR 4" LINES. 90° BEND WITH THRUST BLOCK 4" OR LARGER CLASS 51 DUCTILE IRON PIPE (TYP.) MECHANICAL JOINT MAIN THRUST BLOCK TAPPING TEE & VALVE, OR INSTALL VALVE AT PROPERTY LINE (TYP. FOR ALL RISER CONFIGURATIONS). PROVIDE FLEXIBLE, WATER-TIGHT CONNECTION FOR ALL WALL OR FLOOR PIPE PENETRATIONS. 10' MAX. * 1' MIN., 2' MAX. ABOVE FINISHED FLOOR MECHANICAL JOINT FLOOR OUTSIDE WALL90° BEND WITH THRUST BLOCK 1' MIN., 2' MAX. 2' MIN., 3' MAX. CLEARANCE ABOVE FINISHED FLOORWALLCOATED STEEL WALL PLATE, 5/16" MIN. THICKNESS *PER NPPA-24 FIG. A.10.6.3.1. STANDARD FIRE SERVICE FOR CLASS I, II, & III SYSTEMS NO. 02660-12 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING 4' 1' 2.5' 1' 8' 11.5' (TYP.) 6" MIN. (TYPICAL EXCEPT IN SPECIAL CIRCUMSTANCES WHERE CITY HAS APPROVED ALTERNATE LOCATION) 6.5' MIN. COVER (PROVIDE 5' STATIONARY ROD IN ALL CURB BOXES) SEE DETAIL BELOW WATER MAIN TAP NOTES: 1.WATER SERVICE LINES SHALL HAVE A MINIMUM 6.5' COVER MEASURED FROM THE EXISTING GROUND SURFACE, EXCEPT THAT COVER SHALL BE MEASURED FROM CENTER LINE STREET GRADE WHEN SERVICE LINES ARE LAID TO A STREET SIDE WHICH HAS AN UPHILL SLOPE. WATER SERVICE LINES SHALL HAVE A MAXIMUM 7.5' COVER AT CURB STOP. 2.WATER SERVICE LINES SHALL BE INSTALLED WHERE SHOWN ON THE DRAWINGS OR AS SPECIFIED. 3.BEDDING SHALL BE 1" DIA. MAXIMUM WITHIN 6" OF SERVICE PIPE. 4.INSTALL CURB STOP SO THAT OPERATING KEY IS PARALLEL TO STREET IN OFF-POSITION. 5.NO COUPLINGS OR OTHER JOINTS ALLOWED ON SERVICE PIPE FROM CORPORATION STOP FOR 3/4" AND 1" SERVICES. 6.STRAIGHT COPPER PIPE SHALL BE USED FOR 1-1/2" AND 2" SERVICES. 7.TAP MAIN AT SPRINGLINE. 8.PROVIDE 5' STATIONARY ROD IN ALL CURB BOXES. 9.INSTALL DETECTABLE WARNING TAPE 18" TO 24" BELOW FINISHED GRADE OVER WATER SERVICE FROM MAIN TO CURB BOX. 10.IF TYPICAL CURB BOX LOCATIONS CANNOT BE MET (I.E. 8 FT SETBACK BEHIND PROPERTY LINE TO ACCOMMODATE DRY UTILITIES), ALTERNATE CRITERIA MAY BE APPLIED UPON APPROVAL OF THE CITY ENGINEERING DIVISION. THE FOLLOWING CONDITIONS SHOULD BE MET: -CURB BOXES ARE PREFERABLY LOCATED ON OR NEAR THE PROPERTY OR EASEMENT LINE. -SUITABLE LOCATIONS ARE PROVIDED FOR DRY UTILITIES THAT DO NOT CONFLICT WITH CURB BOXES OR ABILITY TO CONNECT TO SERVICE STUBS IN FUTURE. -CURB BOXES MUST BE A MINIMUM OF 3 FEET FROM ALL FOUNDATIONS AND STRUCTURES. -CURB BOXES ARE ACCESSIBLE TO BE TURNED ON AND OFF AT ALL TIMES AND MUST NOT BE LOCATED IN PARKING AREAS. -SERVICE STUBS FOR FUTURE CONNECTION MUST NOT BE LOCATED IN PAVED AREAS. -ALL CURB STOPS LOCATED IN PAVEMENT SHALL HAVE A VALVE BOX RISER AROUND THE TOP OF THE CURB STOP. DETAIL OF A PROPERLY INSTALLED CORPORATION STOP SELECT MATERIAL BACKFILL AREA (SEE SPECIFICATIONS) 1 2 3 4 STREET SURFACE 5.5' BOULEVARD (TYP.) 5' SIDEWALK (TYP.) PROPERTY LINE OR EASEMENT LINE GROUND SURFACE STEEL POST MARKER PAINTED BLUE CURB BOX CURB STOP BASE MATERIAL TRENCH BOTTOM 3/4" DIA. MIN. SERVICE PIPE CORPORATION STOP WATER SERVICE LINE NO. 02660-6 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING TYPE 1 PIPE BEDDING PLACED IN 6" MAX. LAYERS AND COMPACTED THOROUGHLY EXISTING STREET SURFACE VERTICAL TRENCH WALLS WITH SHORING TO CONFORM THE O.S.H.A. REGULATIONS 6" SELECT TYPE 1 BEDDING MATERIAL PLACED IN 6" LAYERS AND COMPACTED AS SPECIFIED IN SECTION 02221 TRENCH WIDTH=O.D. OF PIPE PLUS 2' MIN. TRENCH WIDTH=3.5' 4" NOTES: 1.WHERE TRENCH PASSES THROUGH EXISTING PAVEMENT THE PAVEMENT SHALL BE CUT ALONG A NEAT VERTICAL LINE A MINIIMUM OF 12" FROM THE EDGE OF THE TRENCH OPENING. WHERE NEAT LINE IS LESS THAN 3' FROM EDGE OF EXISTING PAVEMENT OR CURB AND GUTTER SECTION, REMOVE AND REPLACE ENTIRE PAVEMENT SECTION BETWEEN TRENCH AND EDGE OF PAVEMENT. 2.WHERE INTER-DUCT IS INSTALLED IN SEPARATE TRENCH USE STANDARD TRENCH DETAIL WITH 42' DEPTH OF BURY. 3.SEE CONTRACT SPECIAL PROVISIONS FOR ANY MODIFICATIONS TO STANDARD TRENCH MATERIALS AND/OR OTHER TRENCH DESIGN FEATURES. 4.EXCAVATIONS SHALL CONFORM TO O.S.H.A. CONSTRUCTION STANDARDS. TYPE 2 PIPE BEDDING WHERE REQUIRED FOR SOFT AND UNSTABLE FOUNDATION SLOPING, BENCHING OR SUPPORT SYSTEMS IN THIS AREA TO CONFORM TO O.S.H.A. REGULATIONS 12" MIN. SUBGRADE OR GROUND SURFACE INSTALL DETECTABLE WARNING TAPE 18" MIN, 24" MAX. DEPTH TYPE "A", "B", OR "C" BACKFILL. FLOWABLE FILL SHALL BE USED IN COLLECTOR AND ARTERIAL STREETS (SEE DETAIL 02221-1A). TYPICAL UTILITY TRENCH NO. 02221-1 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING WATER MAIN CURB STOP AND BOX NEAREST FOUNDATION WALL TO CURB STOP SEE DETAILS A & B BELOW 6.5' MIN. COVER 1' MIN. 2' MAX. WATER SERVICE LINE WATER SERVICE LINE STUB (SEE C.O.B. STANDARD DRAWING 02660-6) 1' MIN. INSTALLED BY CUSTOMER (SERVICE APPLICATION & PLUMBING PERMIT REQUIRED) NOTE: METER SIZED SAME AS INCOMING LINE - NO EXCEPTIONS. *METER SAME SIZE AS INCOMING LINE - NO EXCEPTIONS. METER MUST CONNECT DIRECTLY TO ANGLE OR STRAIGHT STOP AND BACKFLOW DEVICE. **DOWNSTREAM SHUT OFF VALVE MUST BE SEPARATE FROM BACKFLOW DEVICE. DETAIL A DETAIL B TYPICAL WALL PENETRATION (N.T.S)TYPICAL FLOOR PENETRATION (N.T.S) (CRAWL SPACE) QUARTER-BEND COUPLING (1-1/2" & 2" SERVICES ONLY) DOWNSTREAM SHUTOFF ** BACKFLOW PREVENTION ASSEMBLY (AS REQUIRED) ANGLE STOP METER * FOUNDATION WALL DOWNSTREAM SHUTOFF ** TO DOMESTIC FIXTURES BACKFLOW PREVENTION ASSEMBLY (AS REQUIRED) FOUNDATION WALL SERVICE LINE FLOOR METER * ANGLE STOP OR STRAIGHT STOP 1' MIN., 2' MAX. 1' MIN., 2' MAX. NOTES: 1.WATER SERVICE LINE INSTALLATIONS SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF BOZEMAN WATER SUPERINTENDENT. 2.SERVICE LINES SHALL BE TYPE K COPPER FOR 3/4", 1", 1 1/2", AND 2" SERVICES. SEE STANDARD DRAWING NO. 02660-14A AND 14B FOR 4" AND LARGER DOMESTIC SERVICE LINES. SERVICE LINES BETWEEN 2" AND 4" ARE NOT ALLOWED. 3.STRAIGHT COPPER TUBING SHALL BE USED FOR 1 1/2" AND 2" SERVICES. 4.SERVICE LINES SHALL BE BEDDED 3" UNDER AND OVER THE PIPE WITH SAND. NATIVE MATERIAL MAY BE USED AS BEDDING IF IT CONFORMS TO THE REQUIREMENTS OF MONTANA PUBLIC WORKS STANDARD DRAWING 02221-2 AND DOES NOT CONTAIN ANY MATERIAL LARGER THAN 3/4". 5.PROVIDE FLEXIBLE, WATER TIGHT CONNECTION FOR ALL WALL OR FLOOR PIPE PENETRATIONS. 6.METERS SHALL BE INSTALLED BY THE CITY WATER DEPARTMENT AT CUSTOMERS' EXPENSE. 7.NO SERVICE LINE SHALL BE BACKFILLED UNTIL IT HAS BEEN INSPECTED AND APPROVED BY THE WATER DEPARTMENT. 8.CONTACT CITY OF BOZEMAN WATER DEPARTMENT FOR APPROVED LIST OF COPPER CONNECTIONS. 9.WATER SERVICE LINE MAY BE REDUCED TO A SMALLER SIZE THAN THE WATER SERVICE STUB. REDUCTION MUST BE MADE WITHIN 18" OF CURB STOP. 10.METER, BACKFLOW PROTECTION, AND INCOMING SERVICE LINE MUST ALL BE THE SAME SIZE. 11.IF TYPICAL CURB BOX LOCATIONS CANNOT BE MET (I.e. 8 FT SETBACK BEHIND PROPERTY LINE TO ACCOMMODATE DRY UTILITIES), ALTERNATE CRITERIA MAY BE APPLIED UPON APPROVAL OF THE CITY ENGINEERING DIVISION. THE FOLLOWING CONDITIONS SHOULD BE MET: -CURB BOXES ARE PREFERABLY LOCATED ON OR NEAR THE PROPERTY OR EASEMENT LINE. -SUITABLE LOCATIONS ARE PROVIDED FOR DRY UTILITIES THAT DO NOT CONFLICT WITH CURB BOXES OR ABILITY TO CONNECT TO SERVICE STUBS IN FUTURE. -CURB BOXES MUST BE A MINIMUM OF 3 FEET FROM ALL FOUNDATIONS AND STRUCTURES. -CURB BOXES ARE ACCESSIBLE TO BE TURNED ON AND OFF AT ALL TIMES AND MUST NOT BE LOCATED IN PARKING AREAS. -SERVICE STUBS FOR FUTURE CONNECTION MUST NOT BE LOCATED IN PAVED AREAS. -ALL CURB STOPS LOCATED IN PAVEMENT SHALL HAVE A VALVE BOX RISER AROUND THE TOP OF THE CURB STOP. TO DOMESTIC FIXTURES DOMESTIC WATER SERVICE, 2" AND SMALLER (PROFILE) NO. 02660-15A 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING MJ VALVE MJ GLAND 3/4" MIN. CORROSION RESISTANT ALL THREAD RESTRAINING ROD, CONFORMING TO ASTM A242-81, INSTALLED IN HALF THE AVAILABLE MECHANICAL JOINT BOLT HOLES (TYP.). WHERE NECESSARY, CLAMPING LUGS (ROMAC "DUCTILE LUG" OR EQUAL), DESIGNED TO FIT DUCTILE IRON (D.I.) PIPE, AND CONFORMING TO ASTM 536-80, MAY BE USED IN CONJUNCTION WITH THE RESTRAINING RODS. ALL FITTINGS SHALL BE MECHANICAL JOINT WITH 3/4" TIE RODS IN EVERY OTHER AVAILABLE BOLT HOLE. MJ VALVE MJ GLAND MJ GLAND MJ GLAND CONCRETE THRUST BLOCK (TYP.) UNDISTURBED EARTH (TYP.) D.I.PIPE D.I.PIPE D.I.PIPE D.I.PIPE D.I.PIPE MJ TEE TYPICAL VALVE/TEE RESTRAINT NO. 02660-9 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING NOTES: 1.POLYETHYLENE ENCASEMENT ON ALL DUCTILE IRON PIPE AND FITTINGS AS SPECIFIED. 2."MEGALUG" OR "UNI-FLANGE" JOINT RESTRAINTS MAY BE SUBSTITUTED FOR THE RODS AND THRUST BLOCKS. STANDARD CURB & GUTTER NO. 02528-1 10/2024 SCALE: NONE CITY OF BOZEMAN STANDARD DRAWING CATCH CURB 9.5" 2" 6.10" 6" OR OTHERWISE AS REQUIRED 4"R 3"R 4% SLOPE -4% SLOPE 24" 24" 24" 6.66" 9.5" 1.51" 0.49" 9.5" 0.75" 4% SLOPE 4% SLOPE NOTES: 1.SUBGRADE OR BASE COURSE COMPACTION SHALL CONFORM TO SECTION 02230 (MPWSS). 2.CONTRACTION JOINTS SHALL BE PLACED AT 10' INTERVALS AND SHALL HAVE A MINIMUM DEPTH OF 3/4" AND MINIMUM WIDTH OF 1/8". 3.1/2" EXPANSION JOINT MATERIAL SHALL BE PLACED AT ALL P.C.S, P.T.S, CURB RETURNS AND AT NOR MORE THAN 300' INTERVALS. THE EXPANSION MATERIAL SHALL EXTEND THROUGH THE FULL DEPTH OF THE CURB AND GUTTER. 4.NO CURB AND GUTTER SHALL BE PLACED WITHOUT A FORM AND/OR STRINGLINE INSPECTION BY THE CITY ENGINEERING DIVISION. 5.CONCRETE SHALL BE M-4500. 6.CRUSHED GRAVEL BASE SHALL MEET THE REQUIREMENTS OF SECTION 02235 (MPWSS) FOR CURB AND GUTTER REPLACEMENT PROJECTS, WASHED ROCK MAY BE USED FOR THE GRAVEL BASE. 7.STANDARD CATCH CURB SHALL MATCH DIMENSIONS OF MONTANA DEPARTMENT OF TRANSPORTATION DETAILED DRAWING NUMBER 609-05. 8.STANDARD CATCH CURB MOLD MAY BE ROTATED ABOUT LIP OF GUTTER TO CONSTRUCT SPILL CURBS. CATCH DROP CURB FOR DRIVEWAYS SPILL CURB CATCH DROP CURB FOR PEDESTRIAN RAMPS 24" -4% SLOPE -4% SLOPE SPILL DROP CURB FOR DRIVEWAYS SPILL DROP CURB FOR PEDESTRIAN RAMPS 2.27" 5.52" 24" 24" 9.5" 1.51" 0.93"2.85" 2.09" 0.17" 7.42" 6.59"1.01" 9.5" CRUSHED GRAVEL BASE, 3" MIN. SUB-BASE COURSE AS REQUIRED 9" RECORD DRAWINGFILE:PROJECT NO:CAD:QUALITY ASSURANCE:DRAWING HISTORYDATE DESCRIPTIONFOR LOT C1, BLOCK 105, NORTHERN PACIFIC ADD BOZEMANDETAILSMILL BUILDING RENOVATIONRECORD DRAWINGBOZEMAN, MTC6.2.1 RPE06020_12_DETAILS_INF.DWGDME/MGB3/28/2025INFRASTRUCTURE SUBMITTAL06/13/202509/03/2026----BP COMMENTSRECORD DRAWING------06020.12