HomeMy WebLinkAbout014-SP2.0-Specifications Docusign Envelope ID:OB8B83E5-B8B3-4B58-A2DC-E6EFCF2DDOFD STAMP: ELECTRICAL 3. CONDUIT CLAMPS, STRAPS AND SUPPORTS SHALL BE STEEL OR MALLEABLE •..•• PART 1: GENERAL p N•• IRON. ALL FITTINGS SHALL BE COMPRESSION TYPE AND WATERTIGHT. "A/-V 2/2026 ''� T N•••. Lz ~ 4. NON-METALLIC CONDUIT AND FITTINGS SHALL BE SCHEDULE 40 PVC, '' 9 1.1 GENERAL CONDITIONS: *; *''•• w�N HEAVY-WALL RIGID WITH SOLVENT-CEMENT-TYPE JOINTS AS RECOMMENDED BY w A. THE CONTRACTOR SHALL INSPECT THE SITE WHERE THIS WORK IS TO BE THE MANUFACTURER. SHELTON DOUGLAS PERFORMED AND FULLY FAMILIARIZE HIMSELF WITH ALL CONDITIONS RELATED TO B. WIRE AND CABLE: KEISLING THIS PROJECT. ' 1. WIRE AND CABLE SHALL BE FLAME-RETARDANT, MOISTURE AND HEAT B. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND LICENSES AND No.PEL-PE-LIC-86951 SHALL MAKE ALL DEPOSITS AND PAY ALL FEES REQUIRED FOR THE PERFORMANCE RESISTANT THERMOPLASTIC, SINGLE CONDUCTOR, COPPER, TYPE THHN/THWN, OF WORK UNDER THIS SECTION. 600 VOLT, SIZES AS INDICATED, #12 AWG MINIMUM. % 1 C. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF ALL SYSTEMS AND COMPONENTS 2. L#A1R0G AWG AND ER CONDUCTORS SHALL CONDUCTORS S� SDE SHALL BE SOLID AND #8 AWG AND �FS;S�CENSN�\?:' COVERED UNDER THIS SECTION. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS. DO signAd.py.ONAL w a DRAWINGS SHALL NOT BE SCALED TO DETERMINE DIMENSIONS. ....• Q 3. SOLDERLESS, PRESSURE-TYPE CONNECTORS CONSTRUCTED OF 1.2 LAWS, REGULATIONS, ORDINANCES. STATUTES AND CODES: HIGH-STRENGTH, NON-CORRODIBLE, TIN-PLATED COPPER DESIGNED TO FURNISH HIGH-PULLOUT STRENGTH AND HIGH CONDUCTIVITY JOINTS SHALL BE A. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL USED. ENG STATE OF MONTANA CODE, AND ALL APPLICABLE LOCAL LAWS, REGULATIONS, ORDINANCES, STATUTES AND CODES. 4. SUPPORT GRIPS SHALL BE SINGLE WEAVE, CLOSED MESH, HIGH-GRADE, NON- ENGINEER: PE#: DISCIPLINE: MAGNETIC, TIN-COATED BRONZE CAPABLE OF SUPPORTING TEN TIMES THE CG CHRISTOPHERGIANNOTTI 105865PE CIVIL C 1.3 REFERENCES: CABLE DEAD WEIGHT, HUBBELL KELLEMS OR APPROVED EQUAL. SDK SHELTON D.KEISLING 86951PE ELECTRICAL E w DJW DAVID J.WALDRON 104827PE ELECTRICAL E U TMS TERRANCE M.SUPER 17412PE ELECTR CAL E a A. THE PUBLICATIONS LISTED BELOW FORM PART OF THIS SPECIFICATION. EACH C. DISCONNECT SWITCHES: z 5 PUBLICATION SHALL BE THE LATEST REVISION AND ADDENDUM IN EFFECT ON THE DATE THIS SPECIFICATION IS ISSUED FOR CONSTRUCTION UNLESS NOTEDDUTY,1. DISCONNECT SWITCHES SHALL BE HEAVY DEAD-FRONT, QUICK-MAKE, N OTHERWISE. EXCEPT AS MODIFIED BY THE REQUIREMENTS SPECIFIED HEREIN OR QUICK-BREAK, EXTERNALLY OPERABLE, HANDLE LOCKABLE AND INTERLOCKED THE DETAILS OF THE DRAWINGS, WORK INCLUDED IN THIS SPECIFICATION SHALL WITH COVER IN CLOSED POSITION, RATING AS INDICATED, UL LABELED CONFORM TO THE APPLICABLE PROVISIONS OF THESE PUBLICATIONS. FURNISHED IN NEMA 3R ENCLOSURE, SQUARE D CLASS 3110 OR APPROVED EQUAL. ' 1. ANSI/IEEE (AMERICAN NATIONAL STANDARDS INSTITUTE) D. SYSTEM GROUNDING: 2. IEEE (INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS) 1. GROUNDING CONDUCTOR SHALL BE SOLID TINNED BARE COPPER, SIZE AS N 3. ASTM (AMERICAN SOCIETY FOR TESTING AND MATERIALS) INDICATED, EXCEPT ABOVE GROUND GROUNDING CONDUCTORS SHALL BE s STRANDED INSULATED. w 4. ICEA (INSULATED CABLE ENGINEERS ASSOCIATION) 2. GROUND BUSSES SHALL BE GALVANIZED STEEL BARS OF RECTANGULAR CROSS w SECTION. a 5. NEMA (NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION) 3. CONNECTORS SHALL BE HIGH-CONDUCTIVITY, HEAVY DUN, LISTED AND 6. NFPA (NATIONAL FIRE PROTECTION ASSOCIATION) LABELED AS GROUNDING CONNECTORS FOR THE MATERIALS USED. USE PLANS PREPARED FOR: TWO-HOLE COMPRESSION LUGS WITH HEAT SHRINK FOR MECHANICAL 7. OSHA (OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION) CONNECTIONS. ■ 8. UL (UNDERWRITERS LABORATORIES, INC.) 4. EXOTHERMIC WELDED CONNECTIONS SHALL BE PROVIDED IN KIT FORM AND ���I�O SELECTED FOR THE SPECIFIC TYPES, SIZES, AND COMBINATIONS OF 1.4 SCOPE OF WORK: CONDUCTORS AND OTHER ITEMS TO BE CONNECTED. A. WORK UNDER THIS SECTION SHALL CONSIST OF FURNISHING ALL LABOR, MATERIAL 5. GROUND RODS SHALL BE COPPER-CLAD STEEL WITH HIGH-STRENGTH STEEL PLANS PREPARED BY: AND ASSOCIATED SERVICES REQUIRED TO COMPLETELY CONSTRUCT AND LEAVE CORE AND ELECTROLYTIC-GRADE COPPER OUTER SHEATH, MOLTEN WELDED TO -- READY FOR OPERATION SYSTEMS AS SHOWN ON THE DRAWINGS AND HEREIN CORE, 3/4" x 10'-0". DESCRIBED. V�wsc B. ALL ELECTRICAL EQUIPMENT UNDER THIS CONTRACT SHALL BE PROPERLY TESTED, E. OTHER MATERIALS: ADJUSTED, AND ALIGNED BY THE CONTRACTOR. 1. THE CONTRACTOR SHALL PROVIDE OTHER MATERIALS, THOUGH NOT SPECIFICALLY DESCRIBED, WHICH ARE REQUIRED FOR A COMPLETELY C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EXCAVATING, DRAINING, OPERATIONAL SYSTEM AND PROPER INSTALLATION OF THE WORK. DRAWING NOTICE: THIS DRAWING HAS NOT BEEN PUBLISHED AND IS THE SOLE TRENCHES, BACKFILLING, AND REMOVAL OF EXCESS DIRT. PROPERTY OF BBC,INC.AND IS LENT TO THE BORROWER FOR z THEIR CONFIDENTIAL USE ONLY,AND IN CONSIDERATION OF w D. THE CONTRACTOR SHALL FURNISH TO THE OWNER, CERTIFICATES OF FINAL THELOANO F THIS DRAWING,THE BORROWER PROMISES AND z AGREES TO RETURN IT UPON REQUEST AND AGREES THAT IT a INSPECTION AND APPROVAL FROM THE INSPECTION AUTHORITIES HAVING WILL NOT BE REPRODUCED,COPIED,LENT OR OTHERWISE JURISDICTION. DISPOSED OF DIRECTLY OR INDIRECTLY,NOR USED FOR ANY PURPOSE OTHER THAN FOR WHICH IT IS FURNISHED. ' PART 2: PRODUCTS SUBMITTALS: 2.1 GENERAL• DESCRIPTION DATE BY REV ADDED TOWER OPTIONS 04/04/25 AWD B REVISED LAT LONG 10/17/25 AWD C A. ALL ITEMS OF MATERIALS AND EQUIPMENT SHALL BE NEW, FREE FROM DEFECTS REVISED PER CLIENT COMMENTS 11/20/25 JDH D AND OF THE BEST QUALITY NORMALLY USED FOR THE PURPOSE IN GOOD m COMMERCIAL PRACTICE. ISSUED FOR CONSTRUCTION 12/16/25 DSL 0 REVISED LAT LONG 03/18/26 DSL 1 B. ALL MATERIALS AND EQUIPMENT SHALL BE ACCEPTABLE TO THE AUTHORITY HAVING REISSUED FOR CONSTRUCTION 05/08/26 CAL 2 JURISDICTION AS SUITABLE FOR THE USE INTENDED. APPLICANT SITE NAME: C. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL OF ' APPROVAL, AND SHALL CONFORM TO REQUIREMENTS OF THE NATIONAL ELECTRICAL MT8 HERO-A CODE. D. ALL OVERCURRENT DEVICES SHALL HAVE AN INTERRUPTING RATING EQUAL TO OR MDG LOCATION ID: GREATER THAN THE SHORT CIRCUIT CURRENT TO WHICH THEY ARE SUBJECTED, a z 10,000 AIC MINIMUM. VERIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT 5000979700 0 o EXCEED THE RATING OF ELECTRICAL EQUIPMENT. ao 2.2 MATERIALS AND EQUIPMENT: SITE ADDRESS: A. CONDUIT: 106 E OAK ST ' 1. RIGID GALVANIZED STEEL CONDUIT (RGS) SHALL BE HOT-DIP GALVANIZED BOZEMAN,MT 59715 INSIDE AND OUTSIDE INCLUDING ENDS AND THREADS AND ENAMELED OR LACQUERED INSIDE IN ADDITION TO GALVANIZING. SHEET DESCRIPTION: sHEET#: m 2. FLEXIBLE METAL CONDUIT SHALL BE GALVANIZED, ZINC-COATED STEEL, PVC SPECIFICATIONS m COATED FOR OUTDOOR APPLICATIONS. (3 OF 4) SP-2. .o 0