Loading...
HomeMy WebLinkAbout050 P201 Building 1 Plumbing Details2' - 0" FIRE RISER SIZED BY FIRE SPRINKLER 11' - 0" 2' - 0"4" DCW P W W P P2' - 0"1' - 0"1' - 4"1" IRRIGATION DOUBLE CHECK BACKFLOW PREVENTOR WATER METER BY UTILITY(TYP.) STRAINER REDUCER 2' MAX1' MIN3"∅ ISOLATION VALVE (TYP.) PRESSURE GUAGE (TYP.) PRESSURE REDUCING VALVE - SET TO 60 PSI (TYP.) 1" IRRIGATION (BUILDING 3 ONLY) SEE FLOOR PLANS FOR CONTINUATION REDUCED PRESSURE BACKFLOW PREVENTOR = PIPE AIR GAP TO FLOOR DRAIN OS&Y VALVE WITH STEM; PARALLELTO FLOOR. 4" 3" SEE FLOOR PLANS FOR CONTINUATION NOTE: 1. CLEANOUTS SHALL BE PROVIDED AT EACH HORIZONTAL DRAINAGE PIPE AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING WHICH IS MORE THAN 100 FEET, AND SHALL BE PROVIDED FOR EACH 100 FEET DEVELOPED LENGTH, OR FRACTION THEREOF OF SUCH PIPING. AN ADDITIONAL CLEANOUT SHALL BE PROVIDED FOR EACH AGGREGATE HORIZONTAL CHANGE OF DIRECTION EXCEEDING ONE HUNDRED THIRTY-FIVE DEGREES, PER APPLICABLE PLUMBING CODE. THIS SHALL BE PROVIDED REGARDLESS OF WHAT IS SHOWN ON THE DRAWINGS. BALANCE OF PIPING, SEE SPECIFICATIONS FOR PIPE MATERIAL 1/8 C.I. BEND FLOOR LINE CLEANOUT AND ACCESS COVER, TOP OF COVER TO BE FLUSH WITH TIP OF FLOOR FINISH GRADE BRONZE CLEANOUT PLUG WITH COUNTER SUNK HEAD, SEE THE PLUMBING FIXTURE SCHEDULE FOR MANUFACTURER AND MODEL SAME SIZE AND MATERIAL AS THE SEWER PIPING CAP AT TERMINUS SANITARY SEWER LINE (PVC, ASTM D3033 OR D3034, SDR 35, WITH ELASTOMERIC GASKETS) FINISH PAVEMENT SCREW CAP/PLUG ROUND FLANGED HOUSING WITH HEAVY DUTY CAST IRON COVER, COVER TO BE INSCRIBED "SAN", SEE THE PLUMBING FIXTURE SCHEDULE FOR MANUFACTURER AND MODEL SAME SIZE AND MATERIAL AS THE SEWER PIPING CAP AT TERMINUS SANITARY SEWER LINE (PVC, ASTM D3033 OR D3034, SDR 35, WITH ELASTOMERIC GASKETS) SEE PLANS 6" 18" SEE PLANS PEDESTRIAN TRAFFIC AREAS / NON-PAVED AREAS 45° ELBOW 45° WYE 45° WYE 45° ELBOW VEHICULAR TRAFFIC AREAS / PAVED AREAS NOTES: A. INTERIOR EXPOSED PIPE, VALVES AND FIXTURE TRIM, INCLUDING TRIM BEHIND CASEWORK DOORS SHALL BE CHROME PLATED. B. ALL PIPING PENETRATIONS THROUGH FINISHED WALLS SHALL BE PROVIDED WITH CHROME ESCUTCHEONS. C. ALL SINK TRAPS SHALL BE PROVIDED WITH A CLEANOUT PLUG IN THE BOTTOM OF THE TRAP. D. ALL PLUMBING FIXTURES SHALL BE CAULKED AND SEALED TO SURROUNDING SURFACES. SEE PLUMBING FIXTURE SCHEDULE FOR BOWL & FAUCET SPECIFICATIONS CHROME PLATED COPPER TUBING WATER RISERS OTHER PIPING MATERIALS, SEE SPECIFICATIONS CHROME PLATED PIPING AND FITTINGS, TYPICAL ALL PIPING BELOW SINKS AND LAVATORIES, SEE NOTES BELOW CLEANOUT PLUG CHROME ESCUTCHEON NOTES: 1. MAINTAIN ONE-FOURTH (1/4) INCH PER FOOT SLOPE. 2. THE DEVELOPED LENGTH BETWEEN THE TRAP OF A WATER CLOSET OR SIMILAR FIXTURE (MEASURED FROM THE TOP OF THE CLOSET FLANGE TO THE INNER EDGE OF THE VENT) AND IT'S VENT SHALL NOT EXCEED SIX (6) FEET. 3. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ADOPTED PLUMBING CODE, AND ALL LOCAL AND STATE CODES. TRAP ARM TRAP VENT FROM FIXTURE WASTE FLOW VENT D (DIAMETER) 2'-6" (D=1-1/4") 3'-6" (D=1-1/2") 5' (D=2") 6' (D=3") 10' (D=4" OR MORE) MAXIMUM TRAP ARM DISTANCE TRAP WEIR MINIMUM TRAP ARM DISTANCE 2 X D 7/8" DISHWASHER DISCHARGE HOSE TO P-TRAP DISHWASHER LOOP HOSE UP HIGH sheet: title: D C B A D C B A 1 2 3 4 5 1 2 3 4 5 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION 601 Euclid Ave. Suite C Helena, Montana 59601 406-531-4745 unitedhousingpartners.com UHP Design LLC 406-224-8220 revisions : p r o j e c t # : d a t e : KEY PLAN project: stamp THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC. PROJECT NO. 24-373 P201 PLUMBING DETAILS 100% CD SET 11/26/25 24.0550 Boseman, MT Hidden Creek Building 1 NTS3FLOOR CLEANOUT (FCO) DETAIL NTS4GRADE CLEANOUT (GCO) DETAIL NTS5SINK/LAVATORY TAILPIECE & TRAP DETAIL NTS6TRAP ARM DETAIL 5 Revision #3 11/26/2025 NTS2DISHWASHER CONNECTION DETAIL NTS1BUILDING WATER SERVICE DETAIL 5 12/1/2025