Loading...
HomeMy WebLinkAbout049 E200 - Electrical DetailsSAND BEDDING AND BACKFILL BY CONTRACTOR CONDUITS ASPHALT, CONCRETE, LAWN, ETC FINISHED GRADE 12" 6" RED MARKER TAPE, RUN LENGTH OF TRENCH 1. IF MULTIPLE CONDUITS SHARE TRENCH, PROVIDE SPACING BETWEEN CONDUITS. PROVIDE ZIP TIES, AND TIE ALL CONDUITS TOGETHER TO ENSURE STABILITY. 2. BURIAL DEPTH TO BE VERIFIED WITH UTILITIES AND AUTHORITY HAVING JURISDICTION: ELECTRICAL FEEDERS, COMMUNICATIONS: 24" MINIMUM UNDERGROUND SECONDARY: 30" MINIMUM UNDERGROUND PRIMARY: 42" MINIMUM # 2 SYMBOL USED FOR NOTE CALLOUT. DETAIL NOTES: PATCH TO MATCH EXISTING FINISH CONDITIONS COMPACTED FILL IN 6" LIFTS OR PER SPECIFICATIONS 1 18" 30" #4 BARE COPPER BOND FROM BOLT TO REBAR WITH EXOTHERMIC WELD OR COMPRESSION FITTING BASE COVER TO MATCH POLE WITH STAINLESS SCREWS SCHEDULE 40PVC (1") TO HANDHOLE OR NEXT FIXTURE AS SHOWN. NUMBER OF FIXTURE HEADS VARY WITH TYPE OF FIXTURE SEE FIXTURE SCHEDULE CONCEALED WELDED STEEL TENON WITH STAINLESS STEEL BOLTS (ALL WITH POLE) POLE PER SCHEDULE NON-SHRINK GROUT UNDER BASE PLATE PACKED TIGHT AFTER LEVELING 30" MIN CURB LENGTH OF ANCHOR BOLTS PER MANUFACTURERS RECOMMENDATIONS. INSTALL PER FACTORY TEMPLATE. DOUBLE LUGS WITH FLAT WASHERS AT BASE PLATE. CLEAN BOLT THREADS AND SURFACES TO PROVIDE GROUNDING CONTINUITY TO POLE. #4 REBAR CAGE AT 6"O.C. EACH WAY TOP TO BOTTOM. INSTALL (3)#4 HORIZONTAL TIES WITHIN TOP 6" OF BASE. CONTRACTOR MAY USE PRE-CAST POLE BASE. SUBMIT PRE-CAST DRAWING TO ENGINEER FOR APPROVAL. HANDHOLE WITH GROUNDING LUG RUBBED BASE TO 12" BELOW GRADE. RUB CORNERS ROUND AND SIDES SMOOTH LANDSCAPED SURFACE FINAL GRADE 6'-0" MINIMUM 24" ROUND FORMED DETAIL NOTES: 1. INCREASE THE SPECIFIED HEIGHT OF THE POLE BY 2'-0" TO ENSURE UNIFORM FIXTURE MOUNTIAN HEIGHT WHERE THE 6" BASE IS USED. 2. PROTECTED AREA IMPLIES THE POLE IS INSTALLED AT LEAST 30" FROM PARKING OR DRIVE AREAS. ENERGY CODE COMMISSIONING COMPLIANCE NOTES SECTION 408 SYSTEM COMMISSIONING IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL BELOW NOTED DOCUMENTS WITHIN 90 DAYS OF CERTIFICATE OF OCCUPANCY: A. AS-BUILT DRAWINGS- DRAWINGS SHALL INCLUDE THE LOCATION AND PERFORMANCE DATA OF ALL PIECES OF MECHANICAL EQUIPMENT. B. OPERATING AND MAINTENANCE MANUALS- MANUALS SHALL INCLUDE THE FOLLOWING: 1. SUBMITTAL DATA ON ALL PIECES OF EQUIPMENT REQUIRING MAINTENANCE. 2. MANUFACTURER'S OPERATIONS AND MAINTENANCE DATA ON ALL PIECES OF EQUIPMENT. ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. 3. NAME AND ADDRESS AND PHONE NUMBER OF OF AT LEAST ONE (1) SERVICE PROVIDED. 4. LIGHTING CONTROL SYSTEMS MAINTENANCE AND CALIBRATION INFORMATION INCLUDING WIRING DIAGRAMS, EQUIPMENT AND SYSTEM SCHEMATICS, AND CONTROL SEQUENCES OF OPERATIONS. DESIRED OR FIELD DETERMINED SETPOINTS SHALL BE PERMANENTLY RECORDED ON CONTROL DRAWINGS AT ALL CONTROL DEVICES, OR FOR DIGITAL CONTROL SYSTEMS, IN THE SYSTEM PROGRAMMING INSTRUCTIONS. 5. A NARRATIVE ON HOW EACH LIGHTING SYSTEM IN INTENDED TO OPERATE, INCLUDING RECOMMENDED SETPOINTS. C. LIGHTING SYSTEM FUNCTIONAL TESTING REQUIREMENTS FUNCTIONAL TESTING - ALL AUTOMATIC LIGHTING CONTROL SYSTEM SHALL BE FULLY TESTED TO ENSURE THE CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED, ADJUSTED, P[ROGRAMMED, AND IN PROPER WORKING CONDITION IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE OCCUPANT SENSORS, TIME SWITCHES, PROGRAMMABLE CONTROLS, PHOTOSENSORS OR DAYLIGHTING CONTROLS ARE INSTALLED, THE FOLLOWING PROCEDURES SHALL BE PREFORMED: 1. CONFIRM THAT THE PLACEMENT, SENSITIVITY AND TIME-OUT ADJUSTMENTS FOR OCCUPANT SENSORS YIELD ACCEPTABLE PERFORMANCE. 2. CONFIRM THAT THE TIME SWITCHES AND PROGRAMMABLE SCHEDULE CONTROLS ARE PROGRAMMED TO TURN THE LIGHTS OFF. 3. CONFIRM THAT THE PLACEMENT AND SENSITIVITY ADJUSTMENTS FOR PHOTOSENSOR CONTROLS REDUCE ELECTRIC LIGHT BASED ON THE AMOUNT OF USABLE DAYLIGHT IN THE SPACE AS SPECIFIED. D. FINAL LIGHTING SYSTEM FUNCTIONAL REPORT- A REPORT OF TEST PROCEDURES AND RESULTS IDENTIFIED AS THE "FINAL LIGHTING CONTROL REPORT" SHALL BE DELIVERED TO THE BUILDING OWNER. THE REPORT SHALL INCLUDE THE FOLLOWING: 1. LIST OF FUNCTIONAL TESTS USED DURING THE COMMISSIONING PROCESS ON EACH PIECE OF EQUIPMENT. 2. RESULTS OF ALL FUNCTIONAL TESTS ON ALL PIECES OF EQUIPMENT. 3. LIST OF DEFICIENCIES FOUND AND CORRESPONDING CORRECTIVE MEASURES EITHER IMPLEMENTED OR PROPOSED ON EACH PIECE OF EQUIPMENT. 4. LIST OF EQUIPMENT NOT ABLE TO BE FUNCTIONALLY TESTED DUE TO CURRENT CLIMATE CONDITIONS. THESE PIECES OF EQUIPMENT WILL FUNCTIONALLY TESTED ONCE CLIMATE CHANGES ALLOW. sheet: title: D C B A D C B A 1 2 3 4 5 1 2 3 4 5 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION 601 Euclid Ave. Suite C Helena, Montana 59601 406-531-4745 unitedhousingpartners.com UHP Design LLC 406-224-8220 revisions : p r o j e c t # : d a t e : KEY PLAN project: stamp THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC. Project No.: 24-373 E200 ELECTRICAL DETAILS & SCHEDULES 03/27/2025 Bozeman, MT Hidden Creek Community NTS1SITE TRENCHING DETAIL NTS2SITE LIGHTING POLE BASE DETAIL LIGHTING FIXTURE SCHEDULE TYPE MARK DESCRIPTION MOUNTING WATTAGE LAMP MANUFACTURER MODEL OR EQUAL BY NOTES BL1 8" DIAMETER BOLLARD FIXTURE DARK BRONZE COLOR BOLLARD 30.5 LED, 2487 LUMENS, 4000K LSI MRB-LED-25L-ACR-S-UNV-DIM-40-BRZ 1 PL1 EXTERIOR POLE LIGHT WITH TYPE T3M DISTRIBUTION POLE MOUNTED +20'-0" AFF 51 LED, 7287 LUMENS, 3000K LITHONIA DSX1 LED-P1-30K-80CRI-T3M-MVOLT-SPA-DDBXD WITH POLE SSS-20'-4C-DM19AS-VD-DDBXD 1 LIGHTING FIXTURE SCHEDULE NOTES 1 SUBSTITUTIONS WILL BE ALLOWED IF SUBMITTED PRIOR TO BID DATE BY THE GREATER OF 7 BUSINESS DAYS OR THE TIME PERIOD SPECIFIED BY DIVISION 1 SPECIFICATIONS, AND IF DEEMED EQUAL BY THE ENGINEER. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING SUBSTITUTED FIXTURES MEET OR EXCEED THE SPECIFICATIONS OF THE FIXTURES SPECIFIED. 2 FIXTURE TO MATCH CITY STANDARDS AND THE CORRESPONDING FIXTURE ON THE OTHER SIDE OF THE ROAD/PATH. Legend: Total Amps:15 A 7 A 0 A Total Load:1738 VA 720 VA 0 VA 29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30 27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28 25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26 23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18 15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16 13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14 11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12 9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10 7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8 5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6 3 Lighting 20 A 1 720 VA 0 VA 1 20 A Spare 4 1 LTG-PARKING LOT 20 A 1 658 VA 1080 VA 1 20 A LTG-SITE PEDESTRIAN 2 CKT Circuit Description CKT Note Trip Poles A B C Poles Trip CKT Note Circuit Description CKT PANEL IS PART OF SEPARATE BUILDING PACKAGE Notes: Enclosure:NEMA 3R MCB Rating: Mounting:Surface Wires:4 Mains Rating:100 A Supply From: Phases:3 Mains Type: Location: Volts:120/208 Wye A.I.C. Rating: Branch Panel: HP1 1 City Comments 07/16/2025 2 City Comments 12/22/2025 2 Legend: Total Amps:8 A 0 A 0 A Total Load:960 VA 0 VA 0 VA 41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42 39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40 37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38 35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36 33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34 31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32 29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30 27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28 25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26 23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18 15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16 13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14 11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12 9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10 7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8 5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6 3 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 4 1 BOLLARD LIGHTING 20 A 1 960 VA 0 VA 1 20 A Spare 2 CKT Circuit Description CKT Note Trip Poles A B C Poles Trip CKT Note Circuit Description CKT PANEL IS PART OF SEPARATE BUILDING PACKAGE Notes: Enclosure:Type 1 MCB Rating: Mounting:Surface Wires:4 Mains Rating:100 A Supply From: Phases:3 Mains Type: Location: Volts:120/208 Wye A.I.C. Rating: Branch Panel: HP5 Legend: Total Amps:8 A 3 A 0 A Total Load:876 VA 360 VA 0 VA 41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42 39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40 37 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 38 35 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 36 33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34 31 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 32 29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30 27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28 25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26 23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18 15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16 13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14 11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12 9 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 10 7 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 8 5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6 3 REC-FUTURE LIGHTING 20 A 1 360 VA 0 VA 1 20 A Spare 4 1 LTG-PARKING LOT 20 A 1 376 VA 500 VA 1 20 A MONUMENT SIGN 2 CKT Circuit Description CKT Note Trip Poles A B C Poles Trip CKT Note Circuit Description CKT PANEL IS PART OF SEPARATE BUILDING PACKAGE Notes: Enclosure:NEMA 3R MCB Rating: Mounting:Surface Wires:4 Mains Rating:100 A Supply From: Phases:3 Mains Type: Location: Volts:120/208 Wye A.I.C. Rating: Branch Panel: HP3 12/22/2025