HomeMy WebLinkAbout05-EP5.0 - SINGLE LINE DIAGRAME5.0
SINGLE LINE DIAGRAM
2CONDUIT AND CONDUCTOR SCHEDULE SCALE
NTS
CONDUIT AND CONDUCTORS SCHEDULE
Conductors Raceway Size (Nominal Inches)
Mark
Conductors
Total Amps Phase & Neutral Min Eq Grd No.Phase, Neutral & Equip Grd With IG
No.
OCP
Device
(Amp/Poles)60d C 75d C Qty Size Type Qty/Set Size Sets EMT IMC RIGID PVC EMT IMC PVC
1 20/1 20 -2 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
2 20/2 20 -3 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
3 20/3 20 -4 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
4 25/1 30 -2 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
5 25/2 30 -3 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
6 25/3 30 -4 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
7 30/1 30 -2 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
8 30/2 30 -3 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
9 30/3 30 -4 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
10 40/1 40 -2 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
11 40/2 40 -3 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
12 40/3 40 -4 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 1.00
B1
50/1 55 -2 6 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75
50/2 55 -3 6 THHN 1 10 One 0.75 0.75 0.75 0.75 1.00 1.00 1.00
50/3 55 -4 6 THHN 1 10 One 1.00 1.00 1.00 1.00 1.00 1.00 1.00
60/1 70 -2 4 THW 1 8 One 1.00 1.00 1.00 1.00 1.25 1.00 1.25
60/2 70 -3 4 THW 1 8 One 1.25 1.00 1.25 1.25 1.25 1.25 1.25
60/3 70 -4 4 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25
70/1 70 -2 4 THW 1 8 One 1.00 1.00 1.00 1.00 1.25 1.00 1.25
70/2 70 -3 4 THW 1 8 One 1.25 1.00 1.25 1.25 1.25 1.25 1.25
70/3 70 -4 4 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25
80/2 85 -3 3 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25
80/3 85 -4 3 THW 1 8 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50
90/2 95 -3 2 THW 1 8 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50
90/3 95 -4 2 THW 1 8 One 1.50 1.25 1.50 1.50 1.50 1.50 1.50
100/2 110 -3 1 THW 1 6 One 1.50 1.50 1.50 1.50 2.00 2.00 2.00
100/3 110 -4 1 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00
110/2 -3 THW 1 6 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50
110/3 -4 THW 1 6 One 1.50 1.25 1.50 1.50 1.50 1.50 1.50
125/2 -3 THW 1 6 One 1.50 1.50 1.50 1.50 2.00 2.00 2.00
125/3 -4 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00
150/2 -150 3 1/0 THW 1 6 One 2.00 1.50 2.00 2.00 2.00 2.00 2.00
150/3 -150 4 1/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00
175/2 -175 3 2/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00
175/3 -175 4 2/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.50 2.50 2.50
200/2 -200 3 3/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.50 2.50 2.50
200/3 -200 4 3/0 THW 1 6 One 2.50 2.50 2.50 2.50 2.50 2.50 2.50
225/2 -230 3 4/0 THW 1 4 One 2.50 2.00 2.50 2.50 2.50 2.50 2.50
225/3 -230 4 4/0 THW 1 4 One 2.50 2.50 2.50 2.50 2.50 3.00 3.00
250/3 -255 4 250 THW 1 4 One 2.50 3.00 3.00 3.00 3.00 3.00 3.00
300/3 -285 4 300 THW 1 4 One 3.00 3.00 3.00 3.00 3.00 3.00 3.00
300/3 -310 4 350 THW 1 4 One 3.00 3.00 3.00 3.00 3.00 3..00 3.00
350/3 -335 4 400 THW 1 4 One 3.00 3.50 3.50 3.50 3.50 3.50 3.50
350/3 -380 4 500 THW 1 4 One 3.50 3.50 3.50 3.50 3.50 3.50 3.50
400/3 -380 4 500 THW 1 3 One 3.50 3.50 3.50 3.50 3.50 3.50 3.50
400/3 -400 4 3/0 THW 3 Two 2.50 2.50 2.50 2.50 2.50 2.50 2.50
600/3 -570 4 300 THW 1 Two 3.00 3.00 3.00 3.00 3.00 3.00 3.00
600/3 -620 4 350 THW 1 Two 3.00 3.00 3.00 3.00 3.00 3.00 3.50
800/3 -760 4 500 THW 1/0 Two 3.50 3.50 3.50 3.50 3.50 3.50 3.50
800/3 -820 4 600 THW 1/0 Two 4.00 4.00 4.00 4.00 4.00 4.00 4.00
1000/3 -1005 4 400 THW 2/0 Three 3.50 3.50 3.50 3.50 3.50 3.50 3.50
1200/3 -1240 4 350 THW 3/0 Four 3.50 3.50 3.50 3.50 3.50 3.50 4.00
1600/3 -1675 4 400 THW 4/0 Five 4.00 4.00 4.00 4.00 4.00 4.00 4.00
Notes:
Conductors are rated at 600 volt or below and are to be copper.
NEC Table 310.15(B)(16) - formerly Table 310.16 - is used for the basis of the conductor ampacities, which is
not more than three current carrying conductors in a raceway at an ambient temperature of 30 deg C with 60 deg
C rated conductors and connectors per 110.14-C-1 for up to 100 amp rated and up to #1 AWG conductors for
equipment terminations and 75 deg C rated conductors and termination connectors for larger than 100 amp or
above #1 AWG conductors.
NEC Tables 4, 5, and Appendix C is used for the basis of the conduit sizes. Table C1 for EMT, Table C4 for IMC,
Table C8 for Rigid, and Table C10 for PVC (Sch 40).
All Branch Feeders and Branch Circuits shall include a green Equipment Grounding Conductor.
Omit Grounding conductor on Service Entrance Feeders.
Omit Neutral conductor on all Delta primary transformer feeders or single-phase 2 pole loads and 3 phase loads
not requiring a neutral.
The above conductors are not calculated for Voltage Drop. Any circuits that exceed 100 feet shall be calculated
by the Installer to have less than a three percent voltage drop on feeders and five percent on branch circuits per
the NEC.
1
1
1
1
1
1
1
1
150
150
150
150
1/0
1/0
1/0
1/0
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
47
48
49
45/3 55 -6 THHN 1 10 One 1.00 1.00 1.00 1.00 1.00 1.00 1.004
42A
42B
43A
43B
44A
44B
45A
45B
46A
46B
FIVE 3" CONDUITS,
EACH WITH 4#250 KCMIL CU
PANEL MDP
1200A MCB
SA
TVSS
41; 250A 41; 250A41; 250A41; 250A
PANEL D2
250A MLO
PANEL C
250A MLO
PANEL B
250A MLO
PANEL A
250A MLO
PANEL POS
100A MLO
POWER INTERFACE BOX (PIB). PROVIDE INCOMING
J-BOX AND OUTGOING J-BOX FLUSH IN THE WALL
WITH FLEX CONDUIT CONNECTIONS TO THE PIB.
THE CONDUCTORS ARE TO CONNECT TO THE
TERMINAL BLOCKS OF THE PIB.
PROVIDE A JUMPER ON THE
LUGS OF PANEL-POS SO
THAT BOTH PHASE BARS
ARE TIED TO THE ONE 120V
PHASE CONDUCTOR FROM
THE PIB
FIELD CONNECT
SURGE ARRESTOR
TO MAIN LUGS
REFER TO THE ELECTRICAL PLAN AND/OR
SITE PLAN FOR ROUTING TO THE POWER
COMPANY'S TRANSFORMER AND THRU A
METER IF IT IS ON THE BUILDING (WITH CT
CABINET) OR ON THE TRANSFORMER.
BRANCH FEEDER MARK NUMBER WITH
AMPERAGE, REFER TO THE CONDUIT
AND CONDUCTORS SCHEDULE (THIS
SHEET) FOR REQUIREMENTS (TYP)
4; 20A 4+IG; 20A
34; 150A
TO AC-1
LAPC
PIB
J J
20/1/M
150/3
250/3
30/3
250/3/ST
250/3/ST
250/3
250/3/ST
PANEL D1
250A MLO
#4/0 MAIN
BONDING
JUMPER
GROUND BAR
(BONDED TO THE
ENCLOSURE)
NEUTRAL BAR
1#6 IN 3/4" CONDUIT TO
PHONE/ISP SERVICE
GROUND PER NEC 250; 1#3/0 MINIMUM IN 3/4"C TO MAIN WATER SERVICE
PIPE WITH 1#4 FROM THE MAIN WATER SERVICE PIPE TO THE GROUNDING
COMPONENTS (I.E. GROUND ROD, CONCRETE ENCASED ELECTRODE) AND
A #3/0 BONDING JUMPER (PER 250.53.C AND TABLE 250.66) TO THE STEEL
STRUCTURE - IF APPLICABLE.
41; 250A
THE GFCI BRANCH BREAKERS IN PANELS D1, D2 AND D3 ARE 65K
SERIES RATED WITH AN UPSTREAM BREAKER NO LARGER THAN
250 AMP. THE 250 AMP PANELS D1, D2 AND D3 ARE 55" HIGH AND
CANNOT BE STACKED.
1200/3 MCB
100% RATED
100/3 100/3
28; 100A
TO AC-2
28; 100A
TO AC-3
GROUND PER NEC 250;
1#6 IN 3/4" CONDUIT TO
GROUND ROD.
INTER SYSTEM BONDING TERMINATION
EQUAL TO ERICO #IBTB NEXT TO
SERVICE ENTRANCE OUTSIDE
TMG EQUAL TO ERICO
TGBA24L14P BELOW DEMARQ
FOR ISP/PHONE SERVICE
1#6 IN 3/4"
CONDUIT
250/3
41; 250A
PANEL D3
250A MLO
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
VERIFY SERVICE LOCATIONS AND CONFORM TO THE REQUIREMENTS OF THE
POWER COMPANY AND/OR DEVELOPER. POWER COMPANY AND/OR
DEVELOPER SHALL BE CONTACTED PRIOR TO BEGINNING CONSTRUCTION TO
ARRANGE AND VERIFY FOR THE INSTALLATION OF THE POWER COMPANY
SERVICE, METER, AND OTHER ITEMS.
GROUND ALL EQUIPMENT AND SERVICES IN ACCORDANCE WITH ARTICLE 250
OF THE NATIONAL ELECTRICAL CODE, LOCAL APPLICABLE CODES, AND ALSO AS
INDICATED ON DRAWINGS.
MAKE NECESSARY INSPECTIONS OF EXISTING SITE AND SERVICE LOCATIONS
AS REQUIRED FOR THIS WORK AND MAKE ALLOWANCE FOR EXISTING
CONDITIONS BEFORE SUBMITTING BID. VERIFY WORK REQUIRED WITH POWER
COMPANY AND TELEPHONE COMPANY.
CUT AND PATCH THE CONSTRUCTION WORK AS REQUIRED FOR PROPER
INSTALLATION OF THE ELECTRICAL WORK. ALL PATCHING SHALL MATCH THE
SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT. ALL CONDUIT
SHALL BE INSTALLED CONCEALED UNLESS SPECIFICALLY APPROVED BY THE
ARCHITECT. COORDINATE SAW CUTTING WITH LANDLORD'S OR OWNER'S
REPRESENTATIVE.
WIRE AND CABLE:
A.CONDUCTORS SHALL BE COPPER, #12 AWG, MINIMUM UNLESS
SPECIFICALLY NOTED OTHERWISE.
B.CONDUCTOR #10 AWG AND SMALLER SHALL BE SOLID AND #8 AWG AND
LARGER SHALL BE STRANDED. INSULATION SHALL BE 600 VOLT, THHN/THWN.
PROVIDE ENGRAVED LAMINATED PHENOLIC BLOCK-ON-WHITE (UNLESS NOTED
OTHERWISE) NAMEPLATES SECURED TO EQUIPMENT WITH ADHESIVE AND
SCREWS FOR PANELBOARDS, RELAY CABINETS, TRANSFORMERS,
DISTRIBUTION BOARDS, AND MAIN PANELBOARD - IDENTIFYING EQUIPMENT
DESIGNATION (CORRESPONDING WITH DESIGNATION USED ON DRAWINGS) AND
EQUIPMENT VOLTAGE. LETTERING SHALL BE 1/4" HIGH. PROVIDE LABELS FOR
CIRCUIT BREAKERS, FUSIBLE SWITCHES AND STARTERS IN PANELBOARDS AND
DISTRIBUTION BOARDS FOR EACH DEVICE IDENTIFYING EQUIPMENT
CONTROLLED. LETTERING SHALL BE 1/8" HIGH.
ALL DEVICES SHALL HAVE AN INTERRUPTING CAPACITY NOT LESS THAN THE
POWER COMPANY AVAILABLE FAULT CURRENT, OR AS INDICATED ON THE
DRAWINGS.
120/208 VOLT BRANCH CIRCUIT PANELBOARD BREAKERS SHALL HAVE A
MINIMUM U.L. SERIES RATING OF 65 KAIC WITH UP-STREAM FEEDER BREAKERS
AS NOTED.
AVAILABLE SPACE FOR MAIN PANELBOARD IS LIMITED. PANELBOARD MUST FIT
IN ALLOCATED SPACE. COORDINATE WITH CONSTRUCTION AS REQUIRED.
ALL WIRING SHALL BE IN CONDUIT, E.M.T OR RIGID. FLEXIBLE CONDUIT MAY
ONLY BE USED FOR FINAL CONNECTIONS AND WITH GREEN EQUIPMENT
GROUNDING CONDUCTORS.
SINGLE-LINE DIAGRAM NOTES
1.
2.
3.
4.
5.
PURCHASE PANELBOARDS, SURGE ARRESTOR, AND TVSS FROM AN APPROVED
NATIONAL ACCOUNTS VENDOR (SEE SHEET E-902 SECTION C16440, PANELBOARDS)
PROVIDING SQUARE-D EQUIPMENT. NO SUBSTITUTIONS ALLOWED.
PURCHASE CONTROL PANEL 'CFA-T500' FROM SUNCOAST ENVIRONMENTAL, INC. (NO
SUBSTITUTIONS ALLOWED). ALL EQUIPMENT IN THE CONTROL PANEL SHALL BE
INSTALLED, WIRED AND CONNECTED AT THE FACTORY, INCLUDING AUTOMATIC LIGHTING
CONTROL SYSTEM, LIGHTING RELAYS, HVAC STARTERS, POWER SUPPLIES,
MISCELLANEOUS RELAYS AND CONTROLS, AND THERMOSTATS.
CONTRACTOR SHALL PROVIDE PANEL FEEDERS A, B, C, D1, D2, D3, AND POS, BRANCH
CIRCUIT CONDUIT AND WIRE, AND INSTALL ALL EQUIPMENT AS REQUIRED.
ALL BREAKERS AND PANELS SHALL BE SQUARE-D.
TVSS AND SURGE ARRESTOR UNITS SHALL BE MOUNTED DIRECTLY ADJACENT TO THE
SIDE OF THE MAIN DISTRIBUTION PANEL IN NEMA 3R ENCLOSURES. CLOSE NIPPLE THE
UNITS TO THE SIDE OF THE PANEL. PROVIDE CONNECTION OF TVSS UNIT TO BREAKER IN
PANEL. CONNECT SURGE ARRESTOR TO MAIN INCOMING LUGS OF THE PANEL. CONNECT
USING MINIMUM LENGTH OF WIRE WITHOUT SHARP BENDS IN THE WIRE AND SHALL NOT
BE LENGTHENED FROM WIRE LENGTH PROVIDED WITH THE TVSS OR SURGE
SUPPRESSOR DEVICE.
SWITCHGEAR AND CONTROL EQUIPMENT NOTES
1SINGLE LINE DIAGRAM SCALE
NTS
1D:\Acies Engineering\ACIES Project\Chick-Fil-A\Bozeman\Electrical\241402_E1.1.dwg Sheet No: E5.0 Saved by: anjo - Tuesday, September 17, 2024 12:34 AM Printed by: Anjo Santos - September 17, 2024 12:34 AMChick-fil-A
5200 Buffington Road
Atlanta, Georgia
30349-2998
Information contained on this drawing and in all digital files
produced for above named project may not be reproduced in
any manner without express written or verbal consent from
authorized project representatives.
CONSULTANT PROJECT #
PRINTED FOR
DATE
SHEET
SHEET NUMBER
DRAWN BY
REVISION SCHEDULE
A
B
C
D
A
B
C
D
1
FSR#04665CHICK-FIL-ABUILDING TYPE / SIZE:
RELEASE:
234
1234 BOZEMAN FSU4500 E VALLEY CENTER DRIVE,BOZEMAN, MONTANA 59718400 N. McCarthy Blvd, ste 250
Copyright c 2024
info@acies.net
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING