HomeMy WebLinkAbout04-EP5.0 - SINGLE LINE DIAGRAME5.0 SINGLE LINE DIAGRAM 2CONDUIT AND CONDUCTOR SCHEDULE SCALE NTS CONDUIT AND CONDUCTORS SCHEDULE Conductors Raceway Size (Nominal Inches) Mark Conductors Total Amps Phase & Neutral Min Eq Grd No.Phase, Neutral & Equip Grd With IG No. OCP Device (Amp/Poles)60d C 75d C Qty Size Type Qty/Set Size Sets EMT IMC RIGID PVC EMT IMC PVC 1 20/1 20 -2 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 2 20/2 20 -3 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 3 20/3 20 -4 12 THHN 1 12 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 4 25/1 30 -2 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 5 25/2 30 -3 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 6 25/3 30 -4 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 7 30/1 30 -2 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 8 30/2 30 -3 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 9 30/3 30 -4 10 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 10 40/1 40 -2 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 11 40/2 40 -3 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 12 40/3 40 -4 8 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 1.00 B1 50/1 55 -2 6 THHN 1 10 One 0.75 0.75 0.75 0.75 0.75 0.75 0.75 50/2 55 -3 6 THHN 1 10 One 0.75 0.75 0.75 0.75 1.00 1.00 1.00 50/3 55 -4 6 THHN 1 10 One 1.00 1.00 1.00 1.00 1.00 1.00 1.00 60/1 70 -2 4 THW 1 8 One 1.00 1.00 1.00 1.00 1.25 1.00 1.25 60/2 70 -3 4 THW 1 8 One 1.25 1.00 1.25 1.25 1.25 1.25 1.25 60/3 70 -4 4 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25 70/1 70 -2 4 THW 1 8 One 1.00 1.00 1.00 1.00 1.25 1.00 1.25 70/2 70 -3 4 THW 1 8 One 1.25 1.00 1.25 1.25 1.25 1.25 1.25 70/3 70 -4 4 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25 80/2 85 -3 3 THW 1 8 One 1.25 1.25 1.25 1.25 1.25 1.25 1.25 80/3 85 -4 3 THW 1 8 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50 90/2 95 -3 2 THW 1 8 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50 90/3 95 -4 2 THW 1 8 One 1.50 1.25 1.50 1.50 1.50 1.50 1.50 100/2 110 -3 1 THW 1 6 One 1.50 1.50 1.50 1.50 2.00 2.00 2.00 100/3 110 -4 1 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00 110/2 -3 THW 1 6 One 1.25 1.25 1.25 1.25 1.50 1.25 1.50 110/3 -4 THW 1 6 One 1.50 1.25 1.50 1.50 1.50 1.50 1.50 125/2 -3 THW 1 6 One 1.50 1.50 1.50 1.50 2.00 2.00 2.00 125/3 -4 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00 150/2 -150 3 1/0 THW 1 6 One 2.00 1.50 2.00 2.00 2.00 2.00 2.00 150/3 -150 4 1/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00 175/2 -175 3 2/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.00 2.00 2.00 175/3 -175 4 2/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.50 2.50 2.50 200/2 -200 3 3/0 THW 1 6 One 2.00 2.00 2.00 2.00 2.50 2.50 2.50 200/3 -200 4 3/0 THW 1 6 One 2.50 2.50 2.50 2.50 2.50 2.50 2.50 225/2 -230 3 4/0 THW 1 4 One 2.50 2.00 2.50 2.50 2.50 2.50 2.50 225/3 -230 4 4/0 THW 1 4 One 2.50 2.50 2.50 2.50 2.50 3.00 3.00 250/3 -255 4 250 THW 1 4 One 2.50 3.00 3.00 3.00 3.00 3.00 3.00 300/3 -285 4 300 THW 1 4 One 3.00 3.00 3.00 3.00 3.00 3.00 3.00 300/3 -310 4 350 THW 1 4 One 3.00 3.00 3.00 3.00 3.00 3..00 3.00 350/3 -335 4 400 THW 1 4 One 3.00 3.50 3.50 3.50 3.50 3.50 3.50 350/3 -380 4 500 THW 1 4 One 3.50 3.50 3.50 3.50 3.50 3.50 3.50 400/3 -380 4 500 THW 1 3 One 3.50 3.50 3.50 3.50 3.50 3.50 3.50 400/3 -400 4 3/0 THW 3 Two 2.50 2.50 2.50 2.50 2.50 2.50 2.50 600/3 -570 4 300 THW 1 Two 3.00 3.00 3.00 3.00 3.00 3.00 3.00 600/3 -620 4 350 THW 1 Two 3.00 3.00 3.00 3.00 3.00 3.00 3.50 800/3 -760 4 500 THW 1/0 Two 3.50 3.50 3.50 3.50 3.50 3.50 3.50 800/3 -820 4 600 THW 1/0 Two 4.00 4.00 4.00 4.00 4.00 4.00 4.00 1000/3 -1005 4 400 THW 2/0 Three 3.50 3.50 3.50 3.50 3.50 3.50 3.50 1200/3 -1240 4 350 THW 3/0 Four 3.50 3.50 3.50 3.50 3.50 3.50 4.00 1600/3 -1675 4 400 THW 4/0 Five 4.00 4.00 4.00 4.00 4.00 4.00 4.00 Notes: Conductors are rated at 600 volt or below and are to be copper. NEC Table 310.15(B)(16) - formerly Table 310.16 - is used for the basis of the conductor ampacities, which is not more than three current carrying conductors in a raceway at an ambient temperature of 30 deg C with 60 deg C rated conductors and connectors per 110.14-C-1 for up to 100 amp rated and up to #1 AWG conductors for equipment terminations and 75 deg C rated conductors and termination connectors for larger than 100 amp or above #1 AWG conductors. NEC Tables 4, 5, and Appendix C is used for the basis of the conduit sizes. Table C1 for EMT, Table C4 for IMC, Table C8 for Rigid, and Table C10 for PVC (Sch 40). All Branch Feeders and Branch Circuits shall include a green Equipment Grounding Conductor. Omit Grounding conductor on Service Entrance Feeders. Omit Neutral conductor on all Delta primary transformer feeders or single-phase 2 pole loads and 3 phase loads not requiring a neutral. The above conductors are not calculated for Voltage Drop. Any circuits that exceed 100 feet shall be calculated by the Installer to have less than a three percent voltage drop on feeders and five percent on branch circuits per the NEC. 1 1 1 1 1 1 1 1 150 150 150 150 1/0 1/0 1/0 1/0 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 47 48 49 45/3 55 -6 THHN 1 10 One 1.00 1.00 1.00 1.00 1.00 1.00 1.004 42A 42B 43A 43B 44A 44B 45A 45B 46A 46B FIVE 3" CONDUITS, EACH WITH 4#250 KCMIL CU PANEL MDP 1200A MCB SA TVSS 41; 250A 41; 250A41; 250A41; 250A PANEL D2 250A MLO PANEL C 250A MLO PANEL B 250A MLO PANEL A 250A MLO PANEL POS 100A MLO POWER INTERFACE BOX (PIB). PROVIDE INCOMING J-BOX AND OUTGOING J-BOX FLUSH IN THE WALL WITH FLEX CONDUIT CONNECTIONS TO THE PIB. THE CONDUCTORS ARE TO CONNECT TO THE TERMINAL BLOCKS OF THE PIB. PROVIDE A JUMPER ON THE LUGS OF PANEL-POS SO THAT BOTH PHASE BARS ARE TIED TO THE ONE 120V PHASE CONDUCTOR FROM THE PIB FIELD CONNECT SURGE ARRESTOR TO MAIN LUGS REFER TO THE ELECTRICAL PLAN AND/OR SITE PLAN FOR ROUTING TO THE POWER COMPANY'S TRANSFORMER AND THRU A METER IF IT IS ON THE BUILDING (WITH CT CABINET) OR ON THE TRANSFORMER. BRANCH FEEDER MARK NUMBER WITH AMPERAGE, REFER TO THE CONDUIT AND CONDUCTORS SCHEDULE (THIS SHEET) FOR REQUIREMENTS (TYP) 4; 20A 4+IG; 20A 34; 150A TO AC-1 LAPC PIB J J 20/1/M 150/3 250/3 30/3 250/3/ST 250/3/ST 250/3 250/3/ST PANEL D1 250A MLO #4/0 MAIN BONDING JUMPER GROUND BAR (BONDED TO THE ENCLOSURE) NEUTRAL BAR 1#6 IN 3/4" CONDUIT TO PHONE/ISP SERVICE GROUND PER NEC 250; 1#3/0 MINIMUM IN 3/4"C TO MAIN WATER SERVICE PIPE WITH 1#4 FROM THE MAIN WATER SERVICE PIPE TO THE GROUNDING COMPONENTS (I.E. GROUND ROD, CONCRETE ENCASED ELECTRODE) AND A #3/0 BONDING JUMPER (PER 250.53.C AND TABLE 250.66) TO THE STEEL STRUCTURE - IF APPLICABLE. 41; 250A THE GFCI BRANCH BREAKERS IN PANELS D1, D2 AND D3 ARE 65K SERIES RATED WITH AN UPSTREAM BREAKER NO LARGER THAN 250 AMP. THE 250 AMP PANELS D1, D2 AND D3 ARE 55" HIGH AND CANNOT BE STACKED. 1200/3 MCB 100% RATED 100/3 100/3 28; 100A TO AC-2 28; 100A TO AC-3 GROUND PER NEC 250; 1#6 IN 3/4" CONDUIT TO GROUND ROD. INTER SYSTEM BONDING TERMINATION EQUAL TO ERICO #IBTB NEXT TO SERVICE ENTRANCE OUTSIDE TMG EQUAL TO ERICO TGBA24L14P BELOW DEMARQ FOR ISP/PHONE SERVICE 1#6 IN 3/4" CONDUIT 250/3 41; 250A PANEL D3 250A MLO 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. VERIFY SERVICE LOCATIONS AND CONFORM TO THE REQUIREMENTS OF THE POWER COMPANY AND/OR DEVELOPER. POWER COMPANY AND/OR DEVELOPER SHALL BE CONTACTED PRIOR TO BEGINNING CONSTRUCTION TO ARRANGE AND VERIFY FOR THE INSTALLATION OF THE POWER COMPANY SERVICE, METER, AND OTHER ITEMS. GROUND ALL EQUIPMENT AND SERVICES IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE, LOCAL APPLICABLE CODES, AND ALSO AS INDICATED ON DRAWINGS. MAKE NECESSARY INSPECTIONS OF EXISTING SITE AND SERVICE LOCATIONS AS REQUIRED FOR THIS WORK AND MAKE ALLOWANCE FOR EXISTING CONDITIONS BEFORE SUBMITTING BID. VERIFY WORK REQUIRED WITH POWER COMPANY AND TELEPHONE COMPANY. CUT AND PATCH THE CONSTRUCTION WORK AS REQUIRED FOR PROPER INSTALLATION OF THE ELECTRICAL WORK. ALL PATCHING SHALL MATCH THE SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT. ALL CONDUIT SHALL BE INSTALLED CONCEALED UNLESS SPECIFICALLY APPROVED BY THE ARCHITECT. COORDINATE SAW CUTTING WITH LANDLORD'S OR OWNER'S REPRESENTATIVE. WIRE AND CABLE: A.CONDUCTORS SHALL BE COPPER, #12 AWG, MINIMUM UNLESS SPECIFICALLY NOTED OTHERWISE. B.CONDUCTOR #10 AWG AND SMALLER SHALL BE SOLID AND #8 AWG AND LARGER SHALL BE STRANDED. INSULATION SHALL BE 600 VOLT, THHN/THWN. PROVIDE ENGRAVED LAMINATED PHENOLIC BLOCK-ON-WHITE (UNLESS NOTED OTHERWISE) NAMEPLATES SECURED TO EQUIPMENT WITH ADHESIVE AND SCREWS FOR PANELBOARDS, RELAY CABINETS, TRANSFORMERS, DISTRIBUTION BOARDS, AND MAIN PANELBOARD - IDENTIFYING EQUIPMENT DESIGNATION (CORRESPONDING WITH DESIGNATION USED ON DRAWINGS) AND EQUIPMENT VOLTAGE. LETTERING SHALL BE 1/4" HIGH. PROVIDE LABELS FOR CIRCUIT BREAKERS, FUSIBLE SWITCHES AND STARTERS IN PANELBOARDS AND DISTRIBUTION BOARDS FOR EACH DEVICE IDENTIFYING EQUIPMENT CONTROLLED. LETTERING SHALL BE 1/8" HIGH. ALL DEVICES SHALL HAVE AN INTERRUPTING CAPACITY NOT LESS THAN THE POWER COMPANY AVAILABLE FAULT CURRENT, OR AS INDICATED ON THE DRAWINGS. 120/208 VOLT BRANCH CIRCUIT PANELBOARD BREAKERS SHALL HAVE A MINIMUM U.L. SERIES RATING OF 65 KAIC WITH UP-STREAM FEEDER BREAKERS AS NOTED. AVAILABLE SPACE FOR MAIN PANELBOARD IS LIMITED. PANELBOARD MUST FIT IN ALLOCATED SPACE. COORDINATE WITH CONSTRUCTION AS REQUIRED. ALL WIRING SHALL BE IN CONDUIT, E.M.T OR RIGID. FLEXIBLE CONDUIT MAY ONLY BE USED FOR FINAL CONNECTIONS AND WITH GREEN EQUIPMENT GROUNDING CONDUCTORS. SINGLE-LINE DIAGRAM NOTES 1. 2. 3. 4. 5. PURCHASE PANELBOARDS, SURGE ARRESTOR, AND TVSS FROM AN APPROVED NATIONAL ACCOUNTS VENDOR (SEE SHEET E-902 SECTION C16440, PANELBOARDS) PROVIDING SQUARE-D EQUIPMENT. NO SUBSTITUTIONS ALLOWED. PURCHASE CONTROL PANEL 'CFA-T500' FROM SUNCOAST ENVIRONMENTAL, INC. (NO SUBSTITUTIONS ALLOWED). ALL EQUIPMENT IN THE CONTROL PANEL SHALL BE INSTALLED, WIRED AND CONNECTED AT THE FACTORY, INCLUDING AUTOMATIC LIGHTING CONTROL SYSTEM, LIGHTING RELAYS, HVAC STARTERS, POWER SUPPLIES, MISCELLANEOUS RELAYS AND CONTROLS, AND THERMOSTATS. CONTRACTOR SHALL PROVIDE PANEL FEEDERS A, B, C, D1, D2, D3, AND POS, BRANCH CIRCUIT CONDUIT AND WIRE, AND INSTALL ALL EQUIPMENT AS REQUIRED. ALL BREAKERS AND PANELS SHALL BE SQUARE-D. TVSS AND SURGE ARRESTOR UNITS SHALL BE MOUNTED DIRECTLY ADJACENT TO THE SIDE OF THE MAIN DISTRIBUTION PANEL IN NEMA 3R ENCLOSURES. CLOSE NIPPLE THE UNITS TO THE SIDE OF THE PANEL. PROVIDE CONNECTION OF TVSS UNIT TO BREAKER IN PANEL. CONNECT SURGE ARRESTOR TO MAIN INCOMING LUGS OF THE PANEL. CONNECT USING MINIMUM LENGTH OF WIRE WITHOUT SHARP BENDS IN THE WIRE AND SHALL NOT BE LENGTHENED FROM WIRE LENGTH PROVIDED WITH THE TVSS OR SURGE SUPPRESSOR DEVICE. SWITCHGEAR AND CONTROL EQUIPMENT NOTES 1SINGLE LINE DIAGRAM SCALE NTS 1D:\Acies Engineering\ACIES Project\Chick-Fil-A\Bozeman\Electrical\241402_E1.1.dwg Sheet No: E5.0 Saved by: anjo - Friday, October 31, 2025 2:49 PM Printed by: Anjo Santos - October 31, 2025 2:52 PMChick-fil-A 5200 Buffington Road Atlanta, Georgia 30349-2998 Information contained on this drawing and in all digital files produced for above named project may not be reproduced in any manner without express written or verbal consent from authorized project representatives. CONSULTANT PROJECT # PRINTED FOR DATE SHEET SHEET NUMBER DRAWN BY REVISION SCHEDULE A B C D A B C D 1 FSR#04665CHICK-FIL-ABUILDING TYPE / SIZE: RELEASE: 234 1234 BOZEMAN FSU4500 E VALLEY CENTER DRIVE,BOZEMAN, MONTANA 59718400 N. McCarthy Blvd, ste 250 Copyright c 2024 info@acies.net fx: (408) 522-5260 ph: (408) 522-5255 Milpitas, CA 95035 ENGINEERING