HomeMy WebLinkAboutA1-5 CODE PLAN AND LEGENDWPWP
1
A
23456 7
B
E
C
D
175' - 0"80' - 0"135' - 0"40' - 0"55' - 0"25' - 0"10662 SF
S2 STORAGE
100
121 SF
OFFICE 01
103
127 SF
TOOL RM
104
121 SF
OFFICE 02
105
MENS RR
101
UNISEX RR
102
FREIGHT ELEV
106
111411123S-2
AUAUAUAUAUAU
BUSINESS 150 /GROSS
ACC STORAGE
300 /GROSS
190' - 6"
LINE OF MEZZANINE ABOVE
S2 OCCUPANCY
WAREHOUSE 500 /GROSS
10651/500=22 OCC22 OCC
PLUMBING FIXTURE CALCS PER ARM 24.301.351PLUMBING FIXTURE CALCS PER ARM 24.301.351
47 OCC TOTAL
WATER CLOSETS 1 PER 100
1 REQ'D2 PROVIDEDADDT'L 2 URINALS
LAVATORIES 1 PER 100
1 REQ'D 2 PROVIDED
DRINKING FOUNTAIN 1 PER 400
1 REQ'D 1 PROVIDED
1 SERVICE SINK
1 REQ'D 1 PROVIDED
23
53
CODE LEGEND
WITH SEPARATION PER TABLE 302.1.1. CALCULATED AS PART OF MAJOR USE FOR AREA.
INCIDENTAL USE:IU
OCCUPANCY GROUP S2
AU
WITH NO SEPARATION REQUIRED AND CALCULATED AS PART OF MAJOR USE FOR AREA IF TOTAL ACCESSORY
USES OCCUPY UNDER 10% OF MAJOR OCCUPANCY CLASSIFICATION AREA PER FLOOR SECTION 302.2.
ACCESSORY USE:
WITH OPENING, DUCT, PENETRATION, AND JOINT PROTECTION. SEE WALL TYPES AND JOINT DETAILS,
PENETRATION DETAILS, AND MECHANICAL DRAWINGS.
(E) FIRE RESISTIVE CORRIDOR 30 MIN RATED
1 HR FIRE PARTITION, HORIZ ASSEMBLY OR SMOKE BARRIER WALL:
(2)ROOM OCCUPANT LOAD (OR TOTAL FLOOR OCCUPANT LOAD) PER SECTION 1004.
MOER:2 MEANS OF EGRESS REQUIRED (QUANTITY) (ONLY DESIGNATED WHERE (2) MEANS OF EGRESS ARE REQ'D)
EXIT SIGN WITH INTEGRATED DIRECTIONAL ARROW WHERE OCCURS AT ALL EXITS, EVERY 100' IN
CORRIDORS, AND IN SPACES WHERE 2 MOE ARE REQUIRED PER SECTION 1011. SIGNS SHOWN IN
CORRIDORS ARE CEILING HUNG. SIGNS SHOWN ON WALL ARE WALL HUNG. ALL EXISTING SIGNS
COMPLIANT AND SHALL REMAIN
REQUIRED EXIT AND EXIT EGRESS DIRECTION
ACCUMULATIVE NUMBER OF OCCUPANTS SERVED WITH EGRESS DIRECTION AT ARROW
LOCATION. (DESIGNATED WHERE (2) MEANS OF EGRESS ARE REQUIRED PER TABLE 1004.1.2).
MINIMUM EGRESS WIDTH (INCHES) BASED ON ACCUMULATIVE NUMBER OF OCCUPANTS
SERVED AT INDICATED EGRESS COMPONENT, USING FACTORS FROM TABLE 1005.1.
Wmin
MAXIMUM DISTANCE FOR EACH STORY SHOWN.
COMMON PATH OF EGRESS TRAVEL DISTANCE -
MAXIMUM
OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF
EACH. SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE
RESISTIVE OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS,
AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW SCHEDULES, MECHANICAL
DRAWINGS, PENETRATION DETAILS, AND JOINT DETAILS WHERE APPLICABLE.
2 HR FIRE BARRIER
OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF
EACH. SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE
RESISTIVE OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS,
AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW SCHEDULES, MECHANICAL
DRAWINGS, PENETRATION DETAILS, AND JOINT DETAILS WHERE APPLICABLE.
30 MIN PARTITION, HORIZ ASSEMBLY OR SMOKE BARRIER WALL:
OR COMBINATION OF (WHERE OCCURS) CONFORMING TO THE MOST STRINGENT REQUIREMENTS OF
EACH. SEE CODE ANALYSIS PLANS FOR SPECIFIC NAMES OF IBC WALL DESIGNATIONS. ALL WITH FIRE
RESISTIVE OPENING PROTECTION AT DOORS, WINDOWS, DUCTS (WITH EXCEPTIONS), PENETRATIONS,
AND PROTECTION AT JOINTS. SEE WALL TYPES, DOOR AND WINDOW SCHEDULES, MECHANICAL
DRAWINGS, PENETRATION DETAILS, AND JOINT DETAILS WHERE APPLICABLE.
WORK AREA
36" WIDE ACCESSIBLE ROUTE
PFE PORTABLE FIRE EXTINGUISHER. REQUIRED AT EACH COMMON AREA, EACH FLOOR
DRAFTSTOPPING
ACCESSIBLE ENTRANCE/UNIT/ ROOM
CODE NOTES
1.
2.
3.
4.
5.
6.
7.
HIS CODE ANALYSIS PLAN IS FOR REFERENCE ONLY. SEE ALL OTHER PLAN SHEETS FOR CONTRACT DOCUMENT
INFORMATION. THIS CODE ANALYSIS IDENTIFIES SOME SPECIFIC BUILDING CODE REQUIREMENTS BUT IS NOT
INTENDED TO LIST ALL BUILDING CODE REQUIREMENTS.
SEE BUILDING CODE AREA CALCULATIONS FOR BUILDING ALLOWABLE AND ACTUAL AREAS CALCULATED PER CODE.
SEE CODE INFORMATION SHEET AND OTHER PLAN/DETAIL SHEETS FOR ACCESSIBILITY CONFORMANCE.
SEE SITE PLAN FOR EXIT DISCHARGE, PROPERTY LINE, PUBLIC WAY LOCATIONS AND COURTYARD LAYOUT (WHERE
OCCURS).
SEE SCHEDULES FOR INTERIOR AND EXTERIOR WALL TYPES AND SECTION FOR HORIZONTAL ASSEMBLIES.
ALL FIRE SUPPRESSION TO BE DESIGN BUILD. CONTRACTOR TO COORDINATE WITH LOCAL AHJ FOR REQUIREMENTS
AND PERMITTING.
EACH TRADE IS RESPONSIBLE FOR COMPLYING WITH THEIR RESPECTIVE GOVERNING CODES.EACH TRADE IS RESPONSIBLE FOR COMPLYING WITH THEIR RESPECTIVE GOVERNING CODES.
CONSTRUCTION TYPE-VB
NO SPRINKLER REQ'MENTS IN S-2 OCCUPANCY UNDER 13500SF PER
STORY
TWO STORY BUILDING-ALLOWABLE HEIGHT 2 STORIES-OK
-40' MAX-ACTUAL 32' 8"
ADA NOTES:
SECOND STORY NOT HABITABLE
EACH TOILET RM TO BE ACCESSIBLE, AT LEAST 1
URINAL
S-2 NS=MAX 13500 SF PER STORYS-2 NS=MAX 13500 SF PER STORY
PRELIM CODE NOTES
CODE NOTE WEST WALL: 10% ALLOWED
OPENINGS UP, NS
WALL=4859 SF
WDW=480 SF
9.9 % OK
CODE NOTE WEST WALL: 5' SETBACK=1
HR WALL
MAX 29 OCC 1 EXIT FOR S OCC AREAS=SECOND
STORY 1 EXIT, FIRST FLR 2 EXITS
COMMON PATH OF TRAVEL-100' NS, 100' S
EXIT PATH FOR ONE EXIT OR ACCESS-75'
SQUARE FOOTAGE
11800 SF FIRST FLOOR
7002 SF SECOND STORY
18802 SF TOTAL GROSS
1
A
23456 7
B
E
C
D
T.O.SUB FLR
115' 6 3/4"
OPEN TO BELOW
42" GUARD WALL
DN
3
175' - 0"
27' - 0"27' - 0"27' - 0"27' - 0"27' - 0"40' - 0"80' - 0"27' - 0"26' - 6"1' - 6"25' - 0"FREIGHT ELEV
106
6922 SF
S2-STORAGE
200
ACCESS STAIR
117
201A
JSTS TO BE ENGINEERED
ACCORDINGLY FOR LOAD23
SECOND STORY STORAGE 300 /GROSS
7002/500=23 OCC23 OCC
DRAWN BY:PROJECT #:REVDESCDATEPHASEPRE SDDDCDDATE1234A1-5
05.07.25CODE PLAN AND LEGENDVALLEY GLASS WAREHOUSERAWHIDE RIDGE RDBOZEMAN, MT 59718SP REVIEW24----Author-------- 3/32" = 1'-0"A1-5
1CODE PLAN-MAIN FLOOR PLAN
3/32" = 1'-0"A1-5
2SECOND FLOOR PLAN Copy 1