BP BPBPBPBPBPBPBP0+000+95NEW CONNECTION TO
EXST. 6" DI WATER MAIN
STA 0+10.00
NEW 4" GATE VALVE
STA 0+15.00
NEW FIRE SERVICE CONNECTION AT BLDG
REFER TO PLUMBING DRAWINGS
STA 0+86.10
REMOVE AND DISPOSE OF ±212 SF OF ASPHALT, ±92 SF SIDEWALK,
AND ±22 SF CURB AND GUTTER. REPLACE WITH LIKE MATERIALS TO
MATCH EXISTING MATERIAL WIDTH AND THICKNESS. STRUCTURAL BASE
SECTION TO BE NO LESS THAT 3" ASPHALT, 6" OF 1-1/2" MINUS CRUSHED,
AND 12" OF 6" MINUS UNCRUSHED MATERIAL. TACK ALL ASPHALT EDGES.2.5'1.5'
FIRE RISER LOCATION
(REFER TO PLUMBING
DRAWINGS)SAW CUT ±28 LF ASPHALT,
±19 LF CONCRETE SIDEWALK,
±3 LF CURB AND GUTTER
SAW CUT ±41 LF ASPHALT,
±5 LF CONCRETE SIDEWALK,
±1 LF CURB AND GUTTER
LIMITS OF DISTURBANCE
4830
4835
4840
4845
4850
4830
4835
4840
4845
4850
FG-4844.33EG-4844.33 0+00 FG-4844.10EG-4844.10FG-EG- 0+95
FINISH FLOOR = 4841.00
STA 0+10.006X4 TEECONNECT TOEXISTING 6" WATERMAIN W/ NEW 4" GV6"INV = ±4835.95CONTRACTORTO FIELD VERIFYEXISTING GROUND
SURFACE (TYP)
EXISTING
FOUNDATION
STA 0+65.2511.25° VERT. BENDINV = ±4835.95MIN. 6.5' COVER (TYP.)
FOR OS&Y VALVE
INSTALLATION
SEE DETAIL
STA 0+75.46
11.25° VERT. BEND
INV = ±4837.99
EXISTING WATER
SERVICE CROSSING STA 0+90.1790° VERT. BENDINV = ±4837.99SEE NOTE 17
1' MIN TO 2' MAX
ABOVE FINISHED FLOOR
FLANGE TO BE THREADED ON STANDPIPE,
MJ TO FLANGE ADAPTERS NOT ACCEPTABLE
(TYPICAL FOR ALL RISER CONFIGURATIONS)
3/4" MIN. REDI ROD, INSTALLED IN EVERY OTHER
AVAILABLE MJ BOLT HOLES (TYP) -
5/8" RODS ACCEPTABLE FOR 4" LINES
FLOOR
4" OR LARGER CLASS 51
DUCTILE IRON PIPE (TYP)
MECHANICAL
JOINTMAIN
TAPPING TEE & VALVE, OR
INSTALL VALVE AT PROPERTY
LINE (TYPICAL FOR ALL
RISER CONFIGURATIONS)
THRUST
BLOCK
90° BEND WITH THRUST BLOCK
FLANGED
OS&Y
VALVE
1' MIN TO 2' MAX
ABOVE FINISHED FLOOR
FLANGED
OS&Y
VALVE
PROVIDE FLEXIBLE,
WATER-TIGHT CONNECTION
FOR ALL WALL OR FLOOR
PIPE PENETRATIONS.
MECHANICAL JOINT
90° BEND WITH
THRUST BLOCK
FLOOR
FLANGED
OS&Y VALVE
1' MIN TO 2' MAX
2' MIN TO 3' MAX
CLEARANCE ABOVE
FINISHED FLOOR
COATED STEEL
WALL PLATE,
5/16" MINIMUM
THICKNESS
CITY OF BOZEMAN REQUIREMENTS
FOR INSTALLATION OF
DOUBLE CHECK VALVE ASSEMBLY
1. THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL LISTED FLANGED
KENNEDY OR MUELLER OS&Y VALVE THE SAME SIZE AS THE FIRE SERVICE
LINE.
2. ALL DOUBLE CHECK VALVE ASSEMBLIES SHALL BE:
A. UL OR FM LISTED.
B. APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION
FOR CROSS CONNECTION CONTROL AND HYDRAULIC RESEARCH
(USCFCCCHR) FOR OPERATION IN THE PROPOSED POSITION (VERTICAL
OR HORIZONTAL) AS SHOWN ON APPROVED PLANS.
C. INSTALLED AS SHOWN ON THE APPROVED PLANS.
3. A FLOW DETECTION DEVICE SHALL BE INSTALLED IMMEDIATELY FOLLOWING
THE DOUBLE CHECK VALVE ASSEMBLY (ALARM CHECK VALVE, FLOW
SENSOR/ALARM, METER, ETC.) AS SHOWN ON THE APPROVED PLANS.
PADDLE-TYPE FLOW ALARMS NOT PERMITTED ON DRY SYSTEMS.
4. A DOUBLE DETECTOR CHECK VALVE ASSEMBLY MAY BE USED WITH A
STANDARD CITY OF BOZEMAN METER. THE METER LOOP OF THE DOUBLE
DETECTOR ASSEMBLY SHALL HAVE A DOUBLE CHECK VALVE ASSEMBLY
INSTALLED WHICH MEETS THE SAME INSTALLATION CRITERIA SPECIFIED
ABOVE IN REQUIREMENT NUMBER TWO.
5. HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF TWO FEET (2') ABOVE
THE FINISHED FLOOR.
6. THE FIRE SERVICE RISER MUST BE A MINIMUM OF TWO FEET (2') FROM ANY
OUTSIDE WALL, AND A MINIMUM OF ONE FOOT (1') FROM ANY INTERIOR WALL.
7. THE INCOMING FIRE SERVICE LINE SHALL BE A MINIMUM OF 6.5' AND A
MAXIMUM OF 7.5' BELOW THE FINISHED GRADE.
8. ALL FIRE SERVICE LINE APPURTENANCES SHALL HAVE A MINIMUM PRESSURE
RATING OF 175 PSI.
9. ALL FIRE SERVICE LINES FOUR INCHES (4") AND LARGER SHALL BE CLASS 51
DUCTILE IRON PIPE.
10. LINE SIZING: THE DOUBLE CHECK VALVE ASSEMBLY SHALL BE EQUAL IN SIZE
TO BOTH THE INCOMING PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE
DIAMETER (DOWNSTREAM).
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
NO PRESSURE GAUGES OR PRESSURE GAUGE
FITTINGS WILL BE ALLOWED ON THE TEST PORTS
OF ANY BACKFLOW PREVENTION ASSEMBLY.
ONLY FITTINGS ALLOWED BETWEEN
FIRST OS&Y VALVE AND BACKFLOW
ASSEMBLY TO BE 90° BEND
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
10'-0" MAX*
MECHANICAL
JOINTOUTSIDE WALL*PER NFPA-24
FIG A.10.6.3.1
WALLissue date
project #
phasesheet project owner revision date
7/18/2023 5:23:45 PMC1.0
09.01.2023FIRE SERVICE23015
CONSTRUCTION / BID SETGALLATIN COUNTY FARM BUREAUGALLATIN COUNTY0
VERT. SCALE IN FEET
0
HORIZ. SCALE IN FEET
1 2 2 4
10 20 20 40
FIRE SERVICE LINE
STATION 0+10 TO 0+89
INSTALL ± 79 LF OF
4" CLASS 51 DIP AWWA C151
TYPE A TRENCH BACKFILL
TYPE 1 PIPE BEDDING
NOT TO SCALE
STANDARD FIRE SERVICE LINE INSTALLATION
FOR CLASS I, II, & III SYSTEMS 02660-13
1. ALL IMPROVEMENTS ON THIS PROJECT SHALL BE COMPLETED IN ACCORDANCE WITH THE MONTANA
PUBLIC WORKS STANDARD SPECIFICATIONS, 6TH EDITION DATED APRIL 2010 (MPWSS); THE CITY OF
BOZEMAN MODIFICATIONS TO THE MPWSS; AND THE PROJECT SPECIFICATIONS.
2. A PRECONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. NO
MATERIAL CHANGES MAY BE MADE TO THIS PLAN WITHOUT THE APPROVAL OF THE CITY OF
BOZEMAN WATER/SEWER SUPERINTENDENT.
3. ALL TEXT AND FEATURES SHOWN SHADED WERE EXISTING.
4. THE LOCATION, DEPTH, AND SIZE OF THE EXISTING UTILITIES SHOWN ON THESE PLANS IS
APPROXIMATE. THE CONTRACTOR SHALL VERIFY THE EXISTENCE, LOCATION, DEPTH, AND SIZE OF
THE UTILITIES PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR
ANY DAMAGE TO THE EXISTING FACILITIES DUE TO FAILURE TO LOCATE OR PROPERLY PROVIDE
PROTECTION WHEN LOCATION IS KNOWN.
5. DIMENSIONS SHOWN FOR PIPE LENGTHS ARE MEASURED FROM CENTER-OF-JUNCTION TO
CENTER-OF-JUNCTION FOR PAYMENT PURPOSES.
6. ALL WATER VALVES OWNED AND OPERATED BY THE CITY OF BOZEMAN SHALL BE OPERATED BY
AUTHORIZED CITY OF BOZEMAN PERSONNEL ONLY. CONTRACTOR SHALL COORDINATE WITH THE
CITY ENGINEER PRIOR TO CONNECTING TO EXISTING WATER LINES OWNED AND MAINTAINED BE
THE CITY OF BOZEMAN.
7. WATER CONNECTIONS SHALL BE PERFORMED BY A LICENSED PLUMBER.
8. ALL VALVES SHALL BE INSTALLED WITH THRUST BLOCKING AND VALVE BOXES IN ACCORDANCE
WITH THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS AND CITY OF BOZEMAN STANDARD
DRAWING NO. 02660-3.
9. ALL FITTINGS REQUIRING THRUST BLOCKING, INCLUDING BENDS GREATER THAN ELEVEN AND
ONE-QUARTER DEGREES (11.25°), TEES, AND PLUGS, SHALL BE INSTALLED IN CONFORMANCE WITH
THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS AND CITY OF BOZEMAN STANDARD
DRAWING NO. 02660-1.
10. IN LIEU OF CONCRETE THRUST BLOCKS, THRUST RESTRAINT MAY BE PROVIDED UTILIZING
MEGALUG; UNI-FLANGE; MJ FIELD LOK SERIES DI; FIELD LOK 350 GASKETS FOR PUSH-ON JOINTS,
MANUFACTURED BY US PIPE; SIGMA ONE LOK SERIES SLD, MANUFACTURED BY SIGMA
CORPORATION; OR APPROVED EQUAL FOR ALL FITTINGS THAT REQUIRE THRUST RESTRAINT,
EXCEPT FOR CUT-IN OR TAPPING TEES (FOR MAINS OR SERVICES) AND BENDS ON SERVICE LINES
INSIDE BUILDING FOUNDATIONS, UNLESS SPECIFICALLY PROHIBITED BY THE CITY OF BOZEMAN. THE
MECHANICAL RESTRAINTS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS AND AT ALL JOINTS AS SPECIFIED BY THE ENGINEER.
11. INSTALL V-BIO WRAP ON ALL NEW DUCTILE IRON WATER PIPE. FOLLOW ALL MANUFACTURER'S
INSTALLATION SPECIFICATIONS.
12. DETECTABLE WARNING TAPE SHALL BE INSTALLED, CENTERED OVER ALL WATER MAINS, SERVICE
LINES, AND HYDRANT LEADS. TAPE SHALL BE INSTALLED A MINIMUM OF EIGHTEEN INCHES (18") AND
MAXIMUM OF TWENTY-FOUR INCHES (24") BELOW FINISH GRADE.
13. THE FOUR INCH (4") FIRE SERVICE LINE SHALL BE INSTALLED IN ACCORDANCE WITH THE CITY OF
BOZEMAN FIRE SERVICE LINE STANDARDS. THIS PLAN IS FOR CONSTRUCTION OF THE FOUR INCH
(4") FIRE SERVICE LINE FROM THE PROPOSED WATER MAIN TO THE OS&Y VALVE IN THE BUILDING.
14. THE FIRE SERVICE LINE SHALL BE INSTALLED, CHLORINATED, AND TESTED TO A MINIMUM OF 200 PSI
BY A SINGLE CONTRACTOR. OWNER OR OWNER'S AUTHORIZED REPRESENTATIVE SHALL PROVIDE
CONSTRUCTION OBSERVATION AND PREPARE THE RECORD DRAWINGS. CONTRACTOR SHALL FILL
OUT AND SUBMIT "CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR UNDERGROUND PIPING".
15. CONTRACTOR SHALL ADJUST ALL VALVE BOXES, CURB BOXES, AND MANHOLES TO FINAL GRADE
UPON COMPLETION OF ALL CONSTRUCTION. ANY BOXES OR MANHOLES DAMAGED OR OTHERWISE
DISTURBED BY THE CONTRACTOR OR SUBCONTRACTOR SHALL BE REPAIRED AT THE EXPENSE OF
THE CONTRACTOR. THIS WORK WAS INCIDENTAL TO THE PROJECT.
16. THE CONTRACTOR SHALL NOTIFY THE WATER DEPARTMENT A MINIMUM OF 24 HOURS PRIOR TO
BEGINNING ANY WORK.
17. CONTRACTOR TO EXCAVATE ~2-FOOT BELOW EXISTING FOOTER ADJACENT TO BUILDING AND AS
NARROW AS POSSIBLE WITH APPROPRIATE SHORING AS NECESSARY (NO MORE THAN 18 INCHES
WIDTH UNDER FOOTER TO PASS THE PIPE UNDER WITHOUT SHORING, 3 FOOT MAX WITH SHORING
THE FOOTING). CONTRACTOR TO INSTALL 4” FIRE SERVICE UNDER FOOTER, INSTALL 90° BEND WITH
MECHANICAL JOINT RESTRAINT AND THRUST BLOCKING, AND INSTALL 4” FIRE SERVICE VERTICAL UP
THROUGH FLOOR TO OS&Y VALVE. EXISTING FLOOR TO BE SAWCUT AND RE-POURED AROUND PIPE
WITH FLEXIBLE, WATER-TIGHT CONNECTION. LEAN MIX CONCRETE SHALL BE PLACED IN EXCAVATED
SPACE UNDER THE FOOTER.
GENERAL NOTES:
FARM BUREAU BUILDING
FIRE SERVICE LINE
MINOR SUB 028C, S12, T2S, R5E, PRINCIPAL MERIDIAN,
CITY OF BOZEMAN, GALLATIN COUNTY, MONTANA
ZONED: R-O
CLASS I SYSTEM
SYSTEM CLASSIFICATION:
ACCORDING TO THE NFPA 24, A FLOW RATE OF 390 GALLONS PER MINUTE IS REQUIRED FOR
FLUSHING OF A 4-INCH FIRE SERVICE LINE. THEREFORE, THE INSTALLING CONTRACTOR
MUST PROVIDE AN ORIFICE SIZE REQUIRED TO MEET THIS REQUIREMENT BASED ON THE
CURRENT PARAMETERS OF THE SYSTEM. THE INSTALLING CONTRACTOR MUST VERIFY THE
MINIMUM REQUIRED ORIFICE SIZE WITH THE CERTIFYING ENGINEER AND CITY OF BOZEMAN
PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING FLOW TEST DATA AND PREPARING
HYDRAULIC CALCULATIONS.
FLUSHING REQUIREMENTS:
DETAIL NOT APPLICABLE
PRO
P
O
S
E
D BL
D
G
FF = 484
1.
0
0
10/03/23
1 CITY REVIEW 10/03/2023
2
2 CITY REVIEW 10/19/2023
2
2
11/06/23
2023-010-IR
Gallatin County
Farm Bureau -
Fireline
6" INV = 4837.30 (A.B.)GROUND SURFACE
ELEV = 4844.35 (A.B.)
1-1/4" Copper Service
INV = +/- 4837.36 (A.B.)INV = 4837.70 (A.B.)RECORD DRAWING(JANUARY 2024)RECORD DRAWING
RECORD DRAWING NOTE:
THIS RECORD DRAWING HAS BEEN
PREPARED, IN PART, BY INFORMATION
PROVIDED BY OTHERS. THE ENGINEER
HAS NOT VERIFIED THE ACCURACY
AND/OR COMPLETENESS OF THIS
INFORMATION IN ALL INSTANCES AND
SHALL NOT BE RESPONSIBLE FOR ANY
ERRORS OR OMISSIONS THAT MAY BE
INCORPORATED AS A RESULT OF
INFORMATION PROVIDED BY OTHERS.