HomeMy WebLinkAbout038 - H-5 - HVAC PLAN MECHANICAL PLAN NOTES A. VERIFY THE LOCATION OF THERMOSTATS AND SENSORS WITH THE ARCHITECT AND ENGINEER PRIOR TO INSTALLATION.INSTALL THERMOSTATS 48"ABOVE FINISHED FLOOR PER ADA REQUIREMENTS. B. PROVIDE AND INSTALL SEISMIC BRACING FOR EQUIPMENT,DUCTWORK AND PIPING PER THE REQUIREMENTS OF THE CURRENTLY ADOPTED INTERNATIONAL BUILDING CODE. C. FLEXIBLE DUCTWORK BETWEEN BRANCH DUCTS AND GRILLES,REGISTERS, OR DIFFUSERS SHALL BE LIMITED TO 5 FT.FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS. D. PROVIDE AND INSTALL FIRE,SMOKE,OR COMBINATION FIREISMOKE DAMPERS WHERE DUCTWORK PASSES THROUGH RATED ASSEMBLIES. ASSOCIATED DUCT DETECTORS SHALL BE ADDRESSABLE.SMOKE DAMPERS AND COMBINATION SMOKE/FIRE DAMPERS SHALL INCLUDE A KEYED REMOTE TEST SWITCH LOCATED IN AN ACCESSIBLE LOCATION.FIELD COORDINATE THE LOCATION OF TEST SWITCHES WITH THE ARCHITECT AND ENGINEER PRIOR TO INSTALLATION. E. SEAL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES O � WITH A UL-APPROVED FIRE STOP SYSTEM. Y'� F. MAINTAIN THE INTEGRITY OF DRAFTSTOPPING WHERE DUCTWORK AND PIPING PENETRATE DRAFTSTOPPING MATERIALS. G.PROVIDE ACCESS DOORS TO ALLOW SERVICE AND INSPECTION OF _ EQUIPMENT,VALVES,DAMPERS AND DEVICES INSTALLED IN INACCESSIBLE LOCATIONS.COORDINATE SUCH INSTALLATIONS WITH THE ARCHITECT AND 2��FUEL FILL LINE ENGINEER. f--------------------------------------3/4"NG----------------------------- I H. DUCTWORK DIMENSIONS INDICATE THE CLEAR WIDTH/HEIGHT AND HAVE g NOT BEEN INCREASED TO ACCOMMODATE DUCT LINER.INSTALLED DUCT H-3 SHALL BE INCREASED TO ACCOMMODATE LINER THICKNESS WHERE LINER EF-2 IS INDICATED IN THE DRAWINGS OR SPECIFICATIONS. 7 I. EXPOSED DUCTWORK TO BE HOT DIPPED GALVANIZED STEEL AND PAINTED CD=2A PER ARCHITECTURAL.CONTRACTOR TO CLEAN AND DRY DUCTWORK PRIOR ------ TO PAINTING. I -— -—- GD-2 J. GAS PIPING TO BE WELDED IN CONCEALED SPACES. ♦ I 5 CD-3 K. PIPING SHALL BE IDENTIFIED WITH PIPE LABELS MARKED ATA MAXIMUM OF EVERY 25 FT.VALVES SHALL BE IDENTIFIED WITH BRASS OR ALUMINUM I VALVE TAGS. L. PROVIDE AND INSTALL PIPE GUIDES,EXPANSION JOINTS,AND HANGERS PER 8 0 MANUFACTURER'S RECOMMENDATIONS. M.PIPING WALL PENETRATIONS SHALL SHALL BE FINISHED WITH ACHROME 2 ESCUTCHEON PLATE. LV-2 N. MINIMUM TERMINAL DEVICE BRANCH PIPE SIZE IS 3/4"o UNLESS OTHERWISE H-3 NOTED. O.PROVIDE HIGH POINT AIR VENTS,LOW POINT DRAINS(WITH CAPPED HOSE T CONNECTIONS),AND SLOPE PIPING AS NECESSARY TO ALLOW FOR COMPLETE DRAINAGE OF THE HYDRONIC SYSTEMS. UC-1 4 4"0 40 ® KEYNOTES: I - r— — 1. RELOCATED GEN SET AND ASSOCIATED EXHAUST SYSTEM,FUEL PIPE ----� VENTS,AND FUEL LINE. 5 2. FACTORY SUPPLIED HORIZONTAL SEPARATED COMBUSTION CONVERSION. H-3 3. RELOCATED CRITICAL CLASS MUFFLER AND 1-1/2'0 WELD-O-LET W/ CONDENSATE LEG AND 3/4"S.S.DRAIN VALVE,SPILL TO FLOOR. 4. 4"0 STAINLESS STEEL FLEX PIPE.INSULATE MUFFLER AND INTERIOR EXHAUST PIPING. 5. SHEET METAL CONNECTIONS ON RADIATOR COWLING SHALL BE BOLTED (E1 )UH-1 I TYPE JOINING SYSTEM SIMILAR AND EQUAL TO DUCT-MATE. 6. RELOCATED FUEL FILL.SLEEVE 2"0 FUEL FILL LINE THROUGH WALL. (El EF 1 7. 2"0 VENT,SLEEVE THROUGH WALL. O Ll EH-1 1 H-3 O ---------- _Cµ1_ (E)CD-1A L)��-1 .—. LV 3(E)CD-1B HVAC PLAN s AGENCY REVIEW (REVISION 2) JUNE 2025 o VERIFY SCALE! REVISIONS •,. 7•q DRAWN BY: CMH PROJECT NUMBER NO. DESCRIPTION BY DATE O • 10678.001 THESE PRINTS My BE Cr Morrison 0 9 DSGN.BY: CMH NORTON RANCH LIFT STATION UPGRADES REDUCED.LINE BELOW 2880 Technology Blvd West p JOSEPH R. * SHEET NUMBER m MEASURES ONE INCH ON ■■ Bozeman,MT 59718 G S . APPR.BY: JRH BOZEMAN MONTANA 38 ORIGINAL DRAWING. ~� Ma i e r I e ` 406.587.0721 No.41135 PE DATE: 0612025IN DRAWING NUMBER ® WWW.m-m.net �° </CENSEO �W� Q.C.REVIEW HVAC PLAN 8Z MODIFY SCALE ACCORDINGLY! engineers surveyors•planners•scientists e PS G BY: JRH H-5 PLOTTED ON:6/4/20251:55:07 PM COPYRIGHT @ MORRISON-MAIER E,2023 S•�'M N�. N DATE: 1/27/2025