HomeMy WebLinkAbout027 Water Design Report WATER MAIN
DESIGN REPORT
FOR:
Blackwood Groves
Infrastructure Improvements
Bozeman, MT
Prepared By:
NOW A PART OF
MADISON
ENGINEERING
ENGINEERING
WWC Engineering
895 Technology Drive, Suite 203
Bozeman, MT 59718
(406) 586-0262
December 2024
WATER MAIN
DESIGN REPORT
FOR:
Blackwood Groves
Infrastructure Improvements
Bozeman, MT
x rnis
" Iv
oIle
p�N j1j 0 iit��i�
WWC Engineering
895 Technology Blvd Ste 203
Bozeman, MT 59718
(406) 586-0262
DECEMBER 2024
BLACKWOOD GROVES
WATER SYSTEM DESIGN REPORT
A. General
This design report will give an overview of the proposed water main for the Blackwood Groves
multi-unit residential development. The 7.84-acre proposed development consists of two lots
located in the Residential Emphasis Mixed Use (REMU) zoning district in Bozeman, Montana,
located on Lot 1, Block 1 and Lot 1, Block 13 of the Blackwood Grove Subdivision. The
development will consist of 11 buildings (9 residential buildings, a clubhouse, and a maintenance
building) comprised of 216 units. The proposed infrastructure is anticipated to be constructed
during the spring of 2025. No phasing is proposed for the water system; however,the units within
the development will be phased. The water infrastructure will be constructed in Phase 1. Once the
water main is constructed and approved, the main will become a part of the City of Bozeman
system.
The following references were used in the preparation of this report:
a. COB Design Standards and Specifications Policy, 2017. Addendum 47
b. COB Modifications to Montana Public Works Standard Specifications (MPWSS).
c. MDEQ Circular No. 1
d. City of Bozeman Zoning Map
e. City of Bozeman Water Facility Plan
B. Existing Water System
The proposed water main extensions will be looped into the existing City of Bozeman water
distribution system. The four connection locations are two existing stubs on Canter Avenue, an
existing stub on Victoria Street, and a hot tap of the main on Victoria Street. These connections
create two water main loops to serve the north and south lots. Appendix 2 shows a site overview
of the existing and proposed infrastructure.
The connection to the city system was modeled using a pump curve provided by C & H
Engineering. This pump curve was used to model flow for the existing Blackwood Groves
development just east of this site (shown in Appendix 1). Due to limited flow data near this site,
the provided pump curve was assumed to be the same for hydrants of closer proximity. For this
reason, the hydrants used in the model have different elevations than the hydrant with the
associated pump curve. Due to this assumption, we recommend the fire flow capacity be verified
by the fire suppression engineer. The hydraulic models for both the north and south lots and their
flow results are shown in Appendix 3.
C. Existing Groundwater
The geotechnical report conducted by Allied Engineering dated November 2023 states that the
subsurface soils consist of native silt/clay underlain by native sandy gravel. Native silt/clay soils
were encountered in various tests pits at a depth of 1.5 to 5.0 feet below the surface. The gravels
Blackwood Groves
Water Design Report
Pagel of 3
extend to depths of at least 10 feet. Groundwater was encountered in all thirteen test pits at depths
ranging from 2.1 to 8.5 feet below the ground surface.The presence or absence of observed ground
water may be directly related to the time of the subsurface investigation. Numerous factors
contribute to seasonal ground water occurrences and fluctuations, and the evaluation of such
factors is beyond the scope of Allied Engineering(geotechnical engineer).Additional groundwater
monitoring information is shown in Appendix 5.
D. Proposed Water System
The proposed water main extensions for the project consists of approximately 1,244 linear feet of
8" ductile iron pipe. The main located on the north lot will connect to an existing water main stub
off Canter Avenue and will also connect to an existing water main stub on Victoria Street. The
main located on the south lot will connect to the water main on Victoria Street through a hot tap
and will connect to an existing stub off Canter Avenue. The layout of the proposed water main
meets the COB design criteria and will be located within the easements/right of way and separated
from the proposed sanitary sewer main by a minimum of 10 feet horizontally. Fire hydrants will
be installed within COB design criteria and will not exceed the recommended distance.
E. Capacity Analysis
An estimation of the water flow rate was based on the City of Bozeman's design standards and
specification policy, which suggests using an average daily flow rate of 2.11 people per dwelling
unit and 170-gallons per capita per day. Applied to the 216 units, the required water flow rate is
calculated:
(
residents gallons 216 units * 2.11 unit * 170 capita
day) = 77,479 gpd
ca
p
Based on these parameters, the development at full build out (216 units) will have an estimated
77,479 gpd(53.81 gpm).
In addition to the average daily demand, the water main extension must account for peak periods
of daily use. Peaking factors are applied to the demand and account for these peak periods in daily
use. The peaking factors used are maximum daily use and peak hour and are obtained from the
City of Bozeman Design Standards. Table 1 shows the peaking factors and the resultant flows
from those factors when applied to the average daily demand of 53.81 gpm.
TABLE 1
PEAKING FACTORS
Flow Designation Peaking Factor Flow (gpm)
Average Day Demand 1 53.81
Maximum Day Demand 2.3 123.75
Maximum Hour 3 161.42
Demand
Maximum Hour and - 1500
Fire Flow Demand
Blackwood Groves
Water Design Report
Page 2 of 3
Based on communication with the architect,the nine apartment buildings will be built and installed
with Type V-A (Protected Wood Frame) construction. The apartment buildings consist of three
different building types (01, 02 & 03). The type 01 buildings have an area of 20,965 SF, the type
02 buildings 24,935 SF, and type 03 24,811 SF. The flow capacity for the largest building type,
type 02, was used for a conservative estimate. A type V-A construction consisting of 24,935 SF
requires 3,000 gpm for a 3-hour flow duration per the 2015 International Fire Code, Table
B 105.1(2). Based on the fire sprinkler system designed for the buildings, the 2015 International
Fire Code's Table B 105.2, the 3,000 gpm fire flow can be reduced but shall not be less than the
minimum of 1,500 gpm.
E. Results
Based on the analysis outlined above,the maximum hour flow of 1,661.42 gpm, is required (Max
Hour Demand + Max Fire Flow). The flow analysis shows that an 8-inch ductile iron pipe can
provide the development with the required flow and remain above the minimum residual pressure
of 20 psi. It is important to note that this analysis relies on the assumption that the pump curve
provide by C & H is reflective of the site conditions for this project. Because of this assumption,
the fire flow capacity should be verified by the fire suppression engineer. See attached flow
analysis in Appendix 3.
F. Conclusion
Based on this analysis and the assumed verification of fire flow capacity by the fire suppression
engineer, the proposed 8-inch ductile iron water main serving Blackwood Groves provides
adequate service to meet the 216-unit, clubhouse, and maintenance building peak hour demand
requirements for the development. The water main was designed on conservative premise for
future development. The water main design is consistent with the City of Bozeman Water Facility
Plan.
This project will require the approval of the City of Bozeman Engineer and MDEQ.
Appendix:
1. Hydrant Pump Curve
2. Site Overview
3. WaterCAD Fire Flow Report
4. Water Main Capacity Analysis
5. Ground Water Monitoring
6. Master Subdivision Water Design Report
7. City of Bozeman Correspondence
Blackwood Groves
Water Design Report
Page 3 of 3
Appendix 1 - Hydrant Pump Curve
Hydrant Curve: Obtained from C&H Engineering Subdivision Report
Hydrant Curve GIS Hydrant#
Available Flow (gpm) Residual Pressure (psi) 2680
Hydrant Curve
0 48.55
200 48.22
400 47.68
600 46.95
800 46.03
1,000.00 44.94
50
1,200.00 43.68 _
1,400.00 42.27
1,600.00 40.7
1,800.00 38.97
2,000.00 37.1 40
2,200.00 35.1
2,400.00 32.95 a
2,600.00 30.65
V)
2,800.00 28.2 V)
v 30
3,000.00 25.6 a
2680
3,200.00 22.84
3,400.00 19.95
3,600.00 16.91
3,800.00 13.72 20
4,000.00 10.4
4,200.00 6.94
4,400.00 3.33
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Available Flow(gpm)
Data Disclaimer:Water distribution information is calculated using hydraulic modeling software and is subject to variation.Actual
field conditions may vary.This information is provided to the requestor for evaluation purposes only,without warranty of any
kind, including, but not limited to any expressed or implied warranty arising by contract, stature,or law. In no event regardless of
cause, shall the City be liable for any direct, indirect, special, punitive or consequential damages of any kind whether such
damages arise under contract,tort, strict liability or inequity.
= �
I
�-
Site T
ALDER CREEK DR
IfT
j 1
f F
ITS
ri
ro
., n r-rrr, ` I
Site -
_ •4
Appendix 2 — Site Overview
c�
Z
; a
as
ra
z z
z ¢�
N.T.S. ffi
V
I EXISTING FIRE HYDRA 4Y
�EXBTMGFIRE M'DRANT v
�IXBTING FIRE NY DR4 Nr
_ - - - - - - - --- - -- �-- L —
- -s - - - s - -S --� - - — - -e� -- - m
-W -—- - - - -'A - -W --—- -'/i �- —L -'A' - CAN lER AVE --—- - �--w - --'A' - - — - - -I -IX 6TMG FIRE Hr DRAM - - - - - — - - - _ - — - - - -- - W
I I I I � '� I uj
I �
1 - a
PROPOSED!-o E. I I mmur I ° -
WATER MIN
I I I IIII I � �• p CLUB iId III
EM
NG_ iIIIiI F
ILfI`I. 30-•W-r.I DiHauSE PBUDur—a�r
A IOU
.5 JO'WbE BUILDING _w
LL
3---Y BBU UII
7NG
rrr
EASEMEM iEULONG
E
CLUB 11 9 I PiPOS ED IRE HFOUSE I, 1 101 1 1 1 1 1 1 DRM
PROPOSED•"Pvc
PROPOSED!"PVC SEWER MAIN
SEWER MAIN -J
I , Pro
PRD ED FIRE B WATER M W W w
SERVPCE(TYP) I '
U /P{p POSED FIRE IYDRAf t
[ItL
IL � . JI -
W
q
S I-4 �_I T S S [S 5 5 5 I I O
} BUILDING BUILDING W Q
M M M M M _
Q I I I I U �Oy N
ui
PRO
SERVI E"M
� — — — = m (� W op
BU B NG - - - _ BUILDING - - BUILDING -
i IX6TING FIRE Hf DRaM O O
W
:400
49 1 V ~
34 a N
� � J
S 197H AVE
SITE OVERVIEW
N.T.S.
Appendix 3 — WaterCAD Fire Flow Report
NORTH LOT
Scenario: Automated Fire Flow Analysis
P41 J-47 P 2 J-17 P37
J-51 P52 PMP-1 P51 R 1
J--3 P12-NYD.LEAD -
J-37 77 J-24{HYD.)
J P4-FS J-8 v f`n
P19- S J-3 w J-18
w J-48
ao
?20-WS J-40 v
P5-FSJ-10
J-39 J-9
Color Coding Legend
Pipe:Diameter(in)
A
rn
<= 4.0
<= 6.0
J-20
<= 8.0
P22-.VJS J-4 J-50
J-19 P10-WS Other
P7 -FS J-14 79 P25-FS
J-43 J-13
R7
0.1
w J-5 P3-FS J fi
M J-35 18-W
J-36
a J-27
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Groves Water System.wtg Center [10.04.00.108]
10/23/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
NORTH LOT
Base Fire Flow Report
Base Fire Flow
Fire Flow(Needed) 1,500 gpm Velocity(Upper Limit) (N/A)ft/s
Fire Flow(Upper Limit) 3,500 gpm Pressure(System Lower (N/A) psi
Limit)
Pressure(Residual Lower 20 psi Pipe Velocity Greater Than 0.00 ft/s
Limit)
Pressure(Zone Lower Limit) 20 psi Node Pressure Less Than 0 psi
Use Minimum System False Pipe Set <All Pipes>
Pressure Constraint?
Use Velocity Constraint? False Nodes To Exclude <None>
Use Pipe Velocity Greater False Fire
Than? Fire Flow Nodes Supression
System
Use Node Pressure Less False Type
Adding Auxiliary Results None
Adding to Auxiliary Output Selection Set <No
Apply Fire Flows By Baseline Elements>
Demand
Fire Flow Auxiliary Results None
Type
13: Base Fire Flow,]unction and Hydrant Alternative Report
* ID Label Specify Local Velocity Fire Flow Fire Flow Pressure Pressure Pressure
Fire Flow (Upper (Needed) (Upper (Residual (Zone (System
Constraints? Limit) (gpm) Limit) Lower Lower Lower Limit)
(ft/s) (gpm) Limit) Limit) (psi)
(psi) (psi)
True 106 3-23 False (N/A) 1,500 3,500 20 20 (N/A)
True 107 24 False (N/A) 1,500 3,500 20 20 (N/A)
(HYD.)
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Groves Water System.wtg Center [10.04.00.108]
11/11/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
NORTH LOT
Fire Flow Node FlexTable: Fire Flow Results Table
Label Fire Flow Fire Flow Fire Flow Pressure Pressure Junction Is Fire Flow Run
Status (Needed) (Available) (Residual (Calculated w/ Balanced?
(gpm) (gpm) Lower Limit) Residual) Minimum
(psi) (psi) Pressure
(System)
3-23 Passed 1,500 1,736 20 23 PMP-1 True
J 24 Passed 1,500 1,736 20 21 PMP-1 True
(HYD.)
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Groves Water System.wtg Center [10.04.00.108]
11/11/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
SOUTH LOT
Scenario: Automated Fire Flow Analysis
J-26
v
TIJ
v J-3 P2 J-4
J-33 P8 J-34
A�
9
�O Cn n Cryfing Lxgend
J-3 Pipe:DiametPrfin)
Q -2
Q�
'= 4.0
J-31 J-1 t= 6.0
Other
P9 J-4 J-29
P3 J-
J-41J-11 J-2� P1922 P21 v P-2 PMP-1 p_1 R-1
J-45 J-15 J-30Qrti
0
J-16
J-46
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Broves Water System(South).wtg Center [10.04.00.108]
10/23/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
SOUTH LOT
Base Fire Flow Report
Base Fire Flow
Fire Flow(Needed) 1,500 gpm Velocity(Upper Limit) (N/A)ft/s
Fire Flow(Upper Limit) 3,500 gpm Pressure(System Lower (N/A) psi
Limit)
Pressure(Residual Lower 20 psi Pipe Velocity Greater Than 0.00 ft/s
Limit)
Pressure(Zone Lower Limit) 20 psi Node Pressure Less Than 0 psi
Use Minimum System False Pipe Set <All Pipes>
Pressure Constraint?
Use Velocity Constraint? False Nodes To Exclude <None>
Use Pipe Velocity Greater False Fire
Than? Fire Flow Nodes Suppression
System
Use Node Pressure Less True Type
Adding Auxiliary Results None
Than?
Adding to Auxiliary Output Selection Set <No
Apply Fire Flows By Baseline Elements>
Demand
Fire Flow Auxiliary Results None
Type
13: Base Fire Flow,]unction and Hydrant Alternative Report
* ID Label Specify Local Velocity Fire Flow Fire Flow Pressure Pressure Pressure
Fire Flow (Upper (Needed) (Upper (Residual (Zone (System
Constraints? Limit) (gpm) Limit) Lower Lower Lower Limit)
(ft/s) (gpm) Limit) Limit) (psi)
(psi) (psi)
True 61 3-21 False (N/A) 1,500 3,500 20 20 (N/A)
True 62 22 False (N/A) 1,500 3,500 20 20 (N/A)
(HYD.)
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Broves Water System(South).wtg Center [10.04.00.108]
11/11/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
SOUTH LOT
Fire Flow Node FlexTable: Fire Flow Results Table
Label Fire Flow Fire Flow Fire Flow Pressure Pressure Junction Is Fire Flow Run
Status (Needed) (Available) (Residual (Calculated w/ Balanced?
(gpm) (gpm) Lower Limit) Residual) Minimum
(psi) (psi) Pressure
(System)
J-21 Passed 1,500 1,779 20 22 3-41 True
] 22 Passed 1,500 1,733 20 20 3-41 True
(HYD.)
Bentley Systems,Inc. Haestad Methods Solution WaterCAD
Blackwood Broves Water System(South).wtg Center [10.04.00.108]
11/11/2024 76 Watertown Road,Suite 2D Thomaston,CT Page 1 of 1
06787 USA +1-203-755-1666
Appendix 4 — Water Main Capacity Analysis
Daily Water Usage Analysis
Blackwood Groves
Average Dail
Building Area
Commercial Spaces 0 sq. ft.
Annual Water Use/sq. ft. 0.273 gpd/sq. ft.
Average Daily Flow 0 gpd
No.Residential Units 216
Residents/unit 2.11
Gallons per Capita/day 170
Average Daily Flow 77,479 gpd
Total Annual Water Use 77,479 gpd
Peaking Factor Calculations
Commercial:
Max Occupancy
Commercial Spaces N/A
Residential:
Zoning Acres Units/Acre Density Total
(residents/unit) Population
REMU 7.84 27.55 2.11 456
Total Site Population: 456
Peaking Q(�) = 18 +p p Population/thousands 0.50 = =93/1000= 0.456
=
Factor Q(ave) 4 +p 0.50
Peaking Factor = 3.99
Peak Hour Water Usage
Average Daily Usage 77,479 gpd
Maximum Hour Usage 232,438 gpd
Maximum Hour Usage 9684.9 gph
Maximum Hour Usage 161.4 gpm
Total Max.Hour Usage 0.36 cfs
Appendix 5 - Ground Water Monitoring
M NOW A PART OF
MADISON �
ENGINEERING WWC
ENGINEERING
895 Technology Boulevard, Suite 203,Bozeman,MT 59718 1406.586.0262
August 22nd,2024
City of Bozeman Planning Department
20 East Olive
Bozeman,MT 59715
RE: Blackwood Groves Groundwater Monitoring
This document contains groundwater monitoring information for the Blackwood Groves subdivision
located on Block 1,Lot 1 and Block 13,Lot 1 of the Blackwood Grove Subdivision Phase 1 and 9,north of
Blackwood Road and Victoria Street, and east of S. 19t1i Ave in Bozeman,MT.
Included in this document is groundwater depth information taken from 13 test pits throughout the site.
Groundwater monitoring was completed by Allied Engineering from April to June 2024. Included is a map
showing the test pit locations where monitoring took place.
K:\Bozeman\Fourth Avenue Capital\2023531 Blackwood Grove Blk 1&13 Site Plan\04Data\Groundwater Monitoring\GW Monitoring.docx
895 Technology Blvd Suite 203 ♦ Bozeman,MT 59718 ♦ (406) 586-0262
_"PHy PARK•AREA
Hunt Map
Layers
�I COLIINS T
t' CITY OF BOZENIAN ROAD
IIC
bs S[ 1 n Cambridge Dr
fail
Y \ SOUTHBRIDGE SUB TP x `TP ? I~
LUDTKE \`� PH 3 PARK AREAS ►� BLAC KWOOD
LAND
CARY I FUND t I
WILLIAM
`AMY TF 3
SCHWEN�SEN
•.� I X x Scotch Grass l
*r I CITY OF BOZEMAN J
' P • I F, '( T a
J GRANITE GRANITE
OWNER OWNER
x TP- X LLC LLC r
d Is AwLYKKE
+ 1
Q CONDO CITY OF BOZEMAN
M MASTER' TP-7 TP-8
`N Victoria St
• x
� r
• Hf 4t Is i
O
=....F ` T P-9 1
BLACKWOOD
_ LAND
1322
SOUTH ( �': , ' CHIPSET - X FUND LLC
MONTANA I CONDO
I 'LLC_r VMF-' MASTER
b- �-_= TP-1 1 BLACKWOOD
LAND
r I FUND LLC
x x c
f T n <
3
— GAL-LAa" I TP 1? TP-13
• CON DO
DO D
LOVE MASTER I y
KELLY& l� Jl� I •
MICHAEL �
� r• i
Blackwood Rd Blackwood Rd
•
a
2024 Groundwater Monitoring Data: Summary of 13 Wells
Project Name: Blks 1 and 13, Blackwood Groves Sub.
Project Number: 23 150 32 Discovery Drive
Location: See Maps ALLIED Bozeman, MT 59718
Date Installed: 10/6/23 ENGINEERING Phone (406) 582-0221
Installed By: AESI SERVICES,INC. `S.o' Fax (406) 582-5770
Okerse Pr60-
NOTES:
1) Block 1 is located on NE side of S. 19th Avenue and Victoria Street.
2) Block 13 is located on SE side of S. 19th Avenue and Victoria Street.
3) MW-1 through MW-13 were installed during test pit explorations on 10/6/23.
4) MW-1 through MW-13 were installed in TP-1 through TP-13, respectively.
5) All test pits were dug to a depth of 10.0'below existing ground (EG)surface.
6) All monitoring wells consist of 10'long,4"diameter, perforated PVC pipes.
7) Depths to bottom of MWs range from 9.0'to 9.2'below existing site grades.
8) MW-1 through MW-8 were installed on Lot 1, Block 1.
9) MW-9 through MW-13 were installed on Lot 1, Block 13.
10) Groundwater depths were monitored by AESI from 3/22/24 to 6/17/24.
11) Groundwater depths are below existing ground (EG).
12) "Dry" MWs are noted as dry at bottom of the 9.0'to 9.2'MW depth.
13) Highest(shallowest)groundwater measurement to date in each well:
MW-1 MW-2 MW-3 MW-4 MW-5
Date Time Depth to GW Depth to GW Depth to GW Depth to GW Depth to GW
below EG below EG below EG below EG below EG
(feet) (feet) (feet) (feet) (feet)
10/06/23 N/A 6.3 4.5 6.5 6.5 4.3
03/22/24 4:00 PM 3.7 2.5 3.4 4.7 3.1
03/29/24 10:15 AM 3.7 2.5 3.4 4.7 3.1
04/05/24 10:15 AM 4.2 2.8 3.7 5.0 3.3
04/12/24 10:30 AM 4.7 3.2 4.1 5.4 3.6
04/26/24 10:00 AM 5.3 4.0 4.8 6.0 4.2
05/10/24 12:30 PM 3.7 2.1 3.4 5.0 2.9
05/17/24 10:00 AM 3.9 2.6 3.5 4.7 2.6
05/24/24 1:30 PM 3.9 2.4 3.6 5.0 3.1
06/03/24 10:00 AM 3.5 2.4 3.2 4.5 2.8
06/10/24 10:00 AM 4.5 3.0 4.0 5.3 3.4
06/17/24 12:00 PM 4.2 3.0 3.9 5.0 3.3
Groundwater Monitoring Data: Page 1 of 3
2024 Groundwater Monitoring Data: Summary of 13 Wells
Project Name: Blks 1 and 13, Blackwood Groves Sub.
Project Number: 23 150 32 Discovery Drive
Location: See Maps ALLIED Bozeman, MT 59718
Date Installed: 10/6/23 ENGINEERING Phone (406) 582-0221
Installed By: AESI SERVICES,INC. `S.o' Fax (406) 582-5770
Okerse Pr60-
NOTES:
1) Block 1 is located on NE side of S. 19th Avenue and Victoria Street.
2) Block 13 is located on SE side of S. 19th Avenue and Victoria Street.
3) MW-1 through MW-13 were installed during test pit explorations on 10/6/23.
4) MW-1 through MW-13 were installed in TP-1 through TP-13, respectively.
5) All test pits were dug to a depth of 10.0'below existing ground (EG)surface.
6) All monitoring wells consist of 10'long,4"diameter, perforated PVC pipes.
7) Depths to bottom of MWs range from 9.0'to 9.2'below existing site grades.
8) MW-1 through MW-8 were installed on Lot 1, Block 1.
9) MW-9 through MW-13 were installed on Lot 1, Block 13.
10) Groundwater depths were monitored by AESI from 3/22/24 to 6/17/24.
11) Groundwater depths are below existing ground (EG).
12) "Dry" MWs are noted as dry at bottom of the 9.0'to 9.2'MW depth.
13) Highest(shallowest)groundwater measurement to date in each well:
MW-6 MW-7 MW-8 MW-9 MW-10
Date Time Depth to GW Depth to GW Depth to GW Depth to GW Depth to GW
below EG below EG below EG below EG below EG
(feet) (feet) (feet) (feet) (feet)
10/06/23 N/A 5.5 7.5 6.5 8.5 7.5
03/22/24 4:00 PM 4.3 5.1 4.5 6.1 4.5
03/29/24 10:15 AM 4.3 5.2 4.5 6.1 4.4
04/05/24 10:15 AM 4.6 5.4 4.7 6.3 4.7
04/12/24 10:30 AM 4.9 5.8 5.0 6.6 5.1
04/26/24 10:00 AM 5.4 6.3 5.4 7.1 5.4
05/10/24 12:30 PM 4.5 5.5 4.6 6.2 4.4
05/17/24 10:00 AM 4.3 5.1 4.5 5.9 4.4
05/24/24 1:30 PM 4.5 5.3 4.5 6.1 4.4
06/03/24 10:00 AM 4.0 4.8 4.3 5.6 4.2
06/10/24 10:00 AM 4.7 5.5 4.7 6.2 4.6
06/17/24 12:00 PM 4.5 5.0 4.6 5.9 4.6
Groundwater Monitoring Data: Page 2 of 3
2024 Groundwater Monitoring Data: Summary of 13 Wells
Project Name: Blks 1 and 13, Blackwood Groves Sub.
Project Number: 23-150 32 Discovery Drive
Location: See Maps ALLIED Bozeman, MT 59718
Date Installed: 10/6/23 ENGINEERING Phone (406) 582-0221
Installed By: AESI SERVICES,INC. `S.o' Fax (406) 582-5770
Okerse Pr60-
NOTES:
1) Block 1 is located on NE side of S. 19th Avenue and Victoria Street.
2) Block 13 is located on SE side of S. 19th Avenue and Victoria Street.
3) MW-1 through MW-13 were installed during test pit explorations on 10/6/23.
4) MW-1 through MW-13 were installed in TP-1 through TP-13, respectively.
5) All test pits were dug to a depth of 10.0'below existing ground (EG)surface.
6) All monitoring wells consist of 10'long,4"diameter, perforated PVC pipes.
7) Depths to bottom of MWs range from 9.0'to 9.2'below existing site grades.
8) MW-1 through MW-8 were installed on Lot 1, Block 1.
9) MW-9 through MW-13 were installed on Lot 1, Block 13.
10) Groundwater depths were monitored by AESI from 3/22/24 to 6/17/24.
11) Groundwater depths are below existing ground (EG).
12) "Dry" MWs are noted as dry at bottom of the 9.0'to 9.2'MW depth.
13) Highest(shallowest)groundwater measurement to date in each well:
MW-11 MW-12 MW-13
Date Time Depth to GW Depth to GW Depth to GW
below EG below EG below EG
(feet) (feet) (feet)
10/06/23 N/A 7.0 6.5 6.5
03/22/24 4:00 PM 4.7 4.5 3.2
03/29/24 10:15 AM 4.9 4.7 3.5
04/05/24 10:15 AM 5.2 5.1 4.0
04/12/24 10:30 AM 5.7 5.6 4.5
04/26/24 10:00 AM 6.1 6.0 4.9
05/10/24 12:30 PM 4.9 4.7 3.6
05/17/24 10:00 AM 4.9 4.7 3.7
05/24/24 1:30 PM 5.0 4.7 3.7
06/03/24 10:00 AM 4.6 4.4 3.4
06/10/24 10:00 AM 5.2 4.7 3.9
06/17/24 12:00 PM 5.2 5.0 4.0
Groundwater Monitoring Data: Page 3 of 3
Appendix 6 — Master Subdivision Water
Design Report
WATER DESIGN REPORT
Blackwood Groves Subdivision
Prepared for:
Bridger Builders, Inc.
115 West Kagy Boulevard
Bozeman, MT 59715
Prepared by:
Ecia.
Engineering and Surveying Inc.
1091 SConeridge Drive • Bozeman, MT 5971 B
Phone (406)587-1115 • Fax(406) 587-9768
www.chengineers.com • info@chengineers.com
Project Number: 190390 ,
March, 2021
INTRODUCTION
The Blackwood Groves Subdivision is a proposed 120-acre development located in the
southeastern portion of the City of Bozeman in Gallatin County, Montana. The proposed project
is comprised of Residential Emphasis Mixed Use zoning and will feature a variety of commercial,
residential, and park/open space development. As part of the project, public improvements
including water, sanitary sewer, stormwater, and City road infrastructure are proposed as well.
This project is located in the City of Bozeman's South Pressure Zone (HGL 5125).
WATER SYSTEM LAYOUT
The proposed water system will utilize an existing 16" ductile iron main that runs east/west along
Blackwood Road, and then north through the property into the Alder Creek Subdivision. In
addition the project will extend existing stubs south and east for future development. The main
was looped through the subdivision to provided redundancy in the system. The stubs for future
development will be capped and have blowoffs installed. The proposed water system consists of
8" class 51 ductile iron water main, with one section of 12" class 51 ductile iron main located in
S. 11th Avenue.
WATER DISTRIBUTION SYSTEM SIZING
Residential Lots:
Values used for assessing the peak hour demand at residential lots were taken from the City
of Bozeman Design Standards and Specifications Policy (2017).
Average Daily Residential Usage = 170 gallons per capita per day
Average Population Density = 2.17 persons/dwelling unit
Maximum Day Demand (Peaking Factor=2.3)
Maximum Hour Demand (Peaking Factor= 3.0)
Commercial REMU Lots:
Values used for assessing the peak hour demand at commercial lots were taken from Table
3.8 in the City of Bozeman's Water Facility Plan Update (2017).
Average Daily Usage = 1,285 gallons per acre per day
Max Day Demand = 2,635 gallons per acre per day
Maximum Hour Demand = 3,855 gallons per acre per day
(Peaking Factor= 3.0)
Minimum Fire Hydrant Flow = 1,500 gpm
Residual Pressure Required = 20 psi for Fire Flow
The table shown below quantifies the demands placed at the junction nodes and calculates the
demands for Average Day, Maximum Day and Peak Hour within the subdivision. The peaking
factor for residential lots is 1, 2.3 and 3.0 respectively, and for Commercial REMU lots being 1,
2.0506 and 3.0 respectively based on the Average Day Demand of 1,285 gallons per acre per day.
A map depicting the contributing lots associated with each demand junction is included in
Appendix A.
Table 1: Demand Junction Summary
POPULATION AVERAGE DAY
DEMAND Acres of AVERAGE DAY DEMAND MAX DAY DEMAND DWELLING (RES.)2.17 GPM(170
JUNCTION Commercial GPM(1,285 GAL PER (2,635 GAL PER UNITS PEOPLE PER GALLONS PER RESIDENTIAL PEAK HOUR GPM(3.0
NODE* Lots ACRE PER DAY)** ACRE PER DAY)'- D.U.*** D.U. DAY PER PERSON MAX.DAY GPM AVERAGE DAY
DJ 1 7.7 6.9 14.1 20.7
DJ 2 12 26 3.1 7.1 9.2
DJ 3 12 26 3.1 7.1 9.2
DJ4 6 13 1.5 3.5 4.6
DJ 5 13 28 3.3 7.7 10.0
DJ 6 12 26 3.1 7.1 9.2
DJ 7 30 65 7.7 17.7 23.1
DJ 8 20 43 5.1 11.8 15.4
DJ 9 6 13 1.5 3.5 4.6
DJ 10 6 13 1.5 3.5 4.6
DJ 11 32 69 8.2 18.9 24.6
DJ 12 32 69 8.2 18.9 24.6
DJ 13 40 87 10.2 23.6 30.7
DJ 14 4.1 3.6 7.4 22.3
DJ 15 3.0 2.7 5.5 16.6
DJ 16 6 13 1.5 3.5 4.6
DJ 17 10 22 2.6 5.9 7.7
DJ 18 5 11 1.3 2.9 3.8
DJ 19 9 20 2.3 5.3 6.9
DJ 20 34 74 8.7 20.0 26.1
DJ 21 122 265 31.3 71.9 93.8
DJ 22 54 117 13.8 31.8 41.5
DJ 23 1.6 1.4 3.0 8.9
DJ 24 21 46 5.4 12.4 16.1
DJ 25 7 15 1.8 4.1 5.4
DJ 26 7 15 1.8 4.1 5.4
DJ 27 12 26 3.1 7.1 9.2
DJ 28 12 26 3.1 7.1 9.2
DJ 29 21 46 5.4 12.4 16.1
DJ 30 68 148 17.4 40.1 52.3
DJ 31 40 87 10.2 23.6 30.7
DJ 32 12 26 3.1 7.1 9.2
Total 16.4 14.7 30.1 661 1434 1 169.34 389.47 576.43
*See Demand Junction Map for more information on which lots contribute to each Demand Junction.
**Per COB Water Facility Plan Update Table 3.8
***COB Design Standards and Specifications
HYDRAULIC ANALYSIS
The water distribution model was created using WaterCAD Version 10.03.02.75 for demand
forecasting and describing domestic and fire protection requirements. The WaterCAD analysis is
enclosed at the end of the report analyzing the 8-inch and 12-inch water main extensions installed
with this project. The connection to the existing system was modeled as a pump using hydrant
curves obtained from the City of Bozeman Water Department. Curves were modeled for the
following hydrants: hydrant #2680 located at the intersection of Alder Creek Drive and S. 15th
Avenue and hydrant#2146 located at the southern terminus of S. 1 Ph Avenue. This data was used
to develop the pump curve used at the connection point to model the existing system.
In the model, the pump is connected to a reservoir which acts as a source of water. The elevation
of the reservoir is fixed at the elevation of the pump, which is also equivalent to the elevation of
the tie-in point. The reservoir does not create any head on the system;the head is generated entirely
by the pumps. The input data and the pump curves are included at the end of the report. The pump
curve table includes all calculations and equations used in determining flow characteristics at the
connection point. A C-factor of 130 was chosen for ductile iron class 51 pipe. The system was
modelled as a steady state hydraulic flow simulation.
CONCLUSION
The 8-inch class 51 ductile iron water main does provide adequate capacity with regards to the
Peak Hour Demands. The flows and pressures within the system for the Peak Hour Demands were
generated with the WaterCAD program and can be found at the end of the report.
The capacity of the system to meet fire flow requirements was tested by running a steady state fire
flow analysis for all junctions at fire hydrant locations. The model shows that the new hydrant
junctions satisfies fire flow constraints (residual pressure > 20 psi, flow rate > 1500 gpm), while
providing service to the proposed lots at peak hour. The results of the analysis at peak hourly flow
are included in Appendix B.
APPENDIX A
Demand Junction Map
� 11 • � � .� : . �"` IIII
•� �. �� i
Sheet I of I
ij�
BLOCK 11 �
•� - — _ - -
�
1�1 m MEMO r1 1 M a l�a-6-N�.■�I l l�Im IN •r r n •■MIN IN■����,■■n./= • '
■■ 0-► _ ■ IIYIN in Yi - ■ ■ ,TIC■R�■��' 7 c
DEMAND BLOCK 10
JUNCTION1JUNC
• ' •
• ■ • i
■
�n
a /
- - � -
I
BLOCK 13 BLOCK 14
I
•
DEMAND■ ■ ® DEMAND
BLOCKJum n..,ia 11- :8 Gy JUNCTION 14 ••
I
I ■ , d, ,
Q 7I■ ■ �IL,1 IIA •
■II• I IIII
BLOCKI / •
DEMAND
p_
! ■ JUNCTION III
- •
:aml1NJ1104—1` G.11\`■,I
lit
• I LOT8 •! (!!IIII- • •
men
1
■ DEMAND •
1 JI I .
_ `L �u • [—
SF
Mims 1\•I 1 M. ,10
7�--ice:.—■-
`li . li•
■ � L•L
} 1
ail
Ii 8
•
■■�■-_■-■_ ■�•d.i;\P\__#_ ■_�■-■ I I ������ _ _ SI�I ■�:r!�•�■■Ic�lII�r�I����■�yJ■16�fi�r - _ _ - _ •III�Y
ammmum
•
APPENDIX B
WaterCAD Output Results
Scenario: Base
'�..... ....
Hl-
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center 0.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 1
+1-203-755-1666
Scenario: Base
HY-
J-7,: W2,
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center 0.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 1
+1-203-755-1666
Scenario Summary Report
Scenario: Base
Scenario Summary
ID 1
Label Base
Notes
Active Topology Base Active Topology
Physical Base Physical
Demand Base Demand
Initial Settings Base Initial Settings
Operational Base Operational
Age Base Age
Constituent Base Constituent
Trace Base Trace
Fire Flow Base Fire Flow
Energy Cost Base Energy Cost
Transient Base Transient
Pressure Dependent Demand Base Pressure Dependent Demand
Failure History Base Failure History
SCADA Base SCADA
User Data Extensions Base User Data Extensions
Steady State/EPS Solver Calculation Base Calculation Options
Options
Transient Solver Calculation Options Base Calculation Options
Hydraulic Summary
Time Analysis Type Steady State Use simple controls during True
steady state?
Friction Method Hazen- Is EPS Snapshot? False
Williams
Accuracy 0.001 Start Time 12:00:00 AM
Trials 40 Calculation Type Fire Flow
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 1
+1-203-755-1666
Base Fire Flow Report
Base Fire Flow
Fire Flow(Needed) 1,500 gpm Fire Flow Auxiliary Results None
Type
Fire Flow(Upper Limit) 3,500 gpm Velocity(Upper Limit) (N/A)ft/s
Pressure(Residual Lower Pressure(System Lower
Limit) 20 psi Limit) (N/A) psi
Pressure(Zone Lower Limit) 20 psi Pipe Velocity Greater Than 0.00 ft/s
Use Minimum System False Node Pressure Less Than 0 psi
Pressure Constraint?
Use Velocity Constraint? False Pipe Set All Pipes
Use Pipe Velocity Greater False Fire Flow Nodes Hydrants
Than?
Use Node Pressure Less False Type
Adding Auxiliary Results None
Adding to Auxiliary Output Selection Set Hydrants
Apply Fire Flows By Baseline
Demand
13: Base Fire Flow, ]unction and Hydrant Alternative Report
* ID Label Specify Local Velocity(Upper Fire Flow Fire Flow Pressure Pressure Pressure
Fire Flow Limit) (Needed) (Upper (Residual (Zone Lower (System
Constraints? (ft/s) (gpm) Limit) Lower Limit) Lower Limit)
(gpm) Limit) (psi) (psi)
(psi)
True 190 HYD 1 False (N/A) 1,500 3,500 20 20 (N/A)
True 194 HYD 2 False (N/A) 1,500 3,500 20 20 (N/A)
True 198 HYD 3 False (N/A) 1,500 3,500 20 20 (N/A)
True 202 HYD 4 False (N/A) 1,500 3,500 20 20 (N/A)
True 206 HYD 5 False (N/A) 1,500 3,500 20 20 (N/A)
True 210 HYD 6 False (N/A) 1,500 3,500 20 20 (N/A)
True 211 HYD 7 False (N/A) 1,500 3,500 20 20 (N/A)
True 215 HYD 8 False (N/A) 1,500 3,500 20 20 (N/A)
True 219 HYD 9 False (N/A) 1,500 3,500 20 20 (N/A)
True 223 HYD 10 False (N/A) 1,500 3,500 20 20 (N/A)
True 227 HYD 11 False (N/A) 1,500 3,500 20 20 (N/A)
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 2
+1-203-755-1666
Base Fire Flow Report
13: Base Fire Flow, ]unction and Hydrant Alternative Report
* ID Label Specify Local Velocity(Upper Fire Flow Fire Flow Pressure Pressure Pressure
Fire Flow Limit) (Needed) (Upper (Residual (Zone Lower (System
Constraints? (ft/s) (gpm) Limit) Lower Limit) Lower Limit)
(gpm) Limit) (psi) (psi)
(psi)
True 232 HYD 12 False (N/A) 1,500 3,500 20 20 (N/A)
True 236 HYD 13 False (N/A) 1,500 3,500 20 20 (N/A)
True 240 HYD 14 False (N/A) 1,500 3,500 20 20 (N/A)
True 244 HYD 15 False (N/A) 1,500 3,500 20 20 (N/A)
True 245 HYD 16 False (N/A) 1,500 3,500 20 20 (N/A)
True 249 HYD 17 False (N/A) 1,500 3,500 20 20 (N/A)
True 253 HYD 18 False (N/A) 1,500 3,500 20 20 (N/A)
True 257 HYD 18 False (N/A) 1,500 3,500 20 20 (N/A)
True 261 HYD 19 False (N/A) 1,500 3,500 20 20 (N/A)
True 265 HYD 20 False (N/A) 1,500 3,500 20 20 (N/A)
True 269 HYD 21 False (N/A) 1,500 3,500 20 20 (N/A)
True 270 HYD 22 False (N/A) 1,500 3,500 20 20 (N/A)
True 277 HYD 23 False (N/A) 1,500 3,500 20 20 (N/A)
True 281 HYD 24 False (N/A) 1,500 3,500 20 20 (N/A)
True 285 HYD 25 False (N/A) 1,500 3,500 20 20 (N/A)
True 289 HYD 26 False (N/A) 1,500 3,500 20 20 (N/A)
True 293 HYD 27 False (N/A) 1,500 3,500 20 20 (N/A)
True 297 HYD 28 False (N/A) 1,500 3,500 20 20 (N/A)
True 304 HYD 29 False (N/A) 1,500 3,500 20 20 (N/A)
True 305 HYD 30 False (N/A) 1,500 3,500 20 20 (N/A)
True 309 HYD 31 False (N/A) 1,500 3,500 20 20 (N/A)
True 313 HYD 32 False (N/A) 1,500 3,500 20 20 (N/A)
True 322 HYD 33 False (N/A) 1,500 3,500 20 20 (N/A)
True 329 HYD 34 False (N/A) 1 1,500 1 3,500 1 201 20 (N/A)
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 2
+1-203-755-1666
FlexTable: Pump Table
ID Label Elevation Pump Definition Status(Initial) Hydraulic Grade Hydraulic Grade Flow(Total) Pump Head
(ft) (Suction) (Discharge) (gpm) (ft)
(ft) (ft)
512 HYDRANT 2680 4,999.36 HYD 2680 On 4,999.36 5,110.82 54 111.46
517 HYDRANT 2146 5,001.71 HYD 2146 On 5,001.71 5,110.95 523 109.24
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 1
+1-203-755-1666
Pump Definition Detailed Report: HYD 2146
Element Details
ID 528 Notes
Label HYD 2146
Pump Curve
Flow Head
(9Pm) (ft)
0 111.30
200 110.72
400 110.05
600 109.29
800 108.46
1,000 107.58
1,200 106.64
1,400 105.67
1,600 104.70
1,800 103.71
2,000 102.60
2,200 101.40
2,400 100.11
2,600 98.75
2,800 97.29
3,000 95.77
3,200 94.15
3,400 92.47
3,600 90.72
3,800 88.89
4,000 87.00
4,200 85.04
4,400 83.01
4,600 80.88
4,800 78.72
5,000 76.48
5,200 74.17
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 3
+1-203-755-1666
Pump Definition Detailed Report: HYD 2146
Pump Curve
Flow Head
(gpm) (ff)
5,400 71.79
5,600 69.37
5,800 66.85
6,000 64.27
6,200 61.64
6,400 58.94
6,600 56.17
6,800 53.33
7,000 50.45
7,200 47.47
7,400 44.45
7,600 41.33
7,800 38.17
8,000 34.96
8,200 31.66
8,400 28.29
8,600 24.88
8,800 21.39
9,000 17.84
9,200 14.24
9,400 10.57
9,600 6.83
9,8001 3.05
Pump Efficiency Type
Best Motor Efficiency 100.0%
Pump Efficiency Type Efficiency
Point
BEP Efficiency 100.0% Is Variable Speed Drive? False
BEP Flow 0 gpm
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 3
+1-203-755-1666
Pump Definition Detailed Report: HYD 2146
Transient(Physical)
Inertia (Pump and Motor) 0.000 Ib•ftz Specific Speed SI=25,
US=1280
Speed (Full) 0 rpm Reverse Spin Allowed? True
Graph
125.00 120.0
112.50
100.00 100.0
87.50
180.0
v
75.00 3
w M
62.50 60.0 ^.
rD
2 n
50.00
0
40.0
37.50
25.00
20.0
12.50
0.00 0.0
0 1,250 2,500 3,750 5,000 6,250 7,500 8,750
Flow (gpm)
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 3 of 3
+1-203-755-1666
Pump Definition Detailed Report: HYD 2680
Element Details
ID 513 Notes
Label HYD 2680
Pump Curve
Flow Head
(gpm) (ft)
0 112.04
200 111.28
400 110.03
600 108.35
800 106.22
1,000 103.71
1,200 100.80
1,400 97.55
1,600 93.92
1,800 89.93
2,000 85.62
2,200 81.00
2,400 76.04
2,600 70.73
2,800 65.08
3,000 59.08
3,200 52.71
3,400 46.04
3,600 39.02
3,800 31.66
4,000 24.00
4,200 16.02
4,4001 7.68
Pump Efficiency Type
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 3
+1-203-755-1666
Pump Definition Detailed Report: HYD 2680
Pump Efficiency Type
Best Motor Efficiency 100.0%
Pump Efficiency Type Efficiency
Point
BEP Efficiency 100.0% Is Variable Speed Drive? False
BEP Flow 0 gpm
Transient(Physical)
Inertia (Pump and Motor) 0.000 Ib•ftz Specific Speed SI=25,
US=1280
Speed (Full) 0 rpm Reverse Spin Allowed? True
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 3
+1-203-755-1666
Pump Definition Detailed Report: HYD 2680
Graph
125.00 120.0
112.50
100.0
100.00
87.50
80.0
v
c
75.00 3
w M
62.50 60.0 a
o m
2 n
50.00
0
40.0 .,
37.50
25.00
20.0
12.50
0.00 10.0
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000 4,500
Flow (gpm)
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 3 of 3
+1-203-755-1666
Fire Flow Node FlexTable: Fire Flow Report
Label Satisfies Fire Fire Flow Fire Flow Flow(Total Pressure Junction w/ Junction w/ Pressure
Flow (Needed) (Available) Available) (Residual Minimum Minimum (Calculated
Constraints? (gpm) (gpm) (gpm) Lower Limit) Pressure Pressure Residual @
(psi) (Zone) (System) Total Flow
Needed)
(psi)
HYD 1 True 1,500 3,500 3,500 20 3-54 HYDRANT 41
2146
HYD 2 True 1,500 3,500 3,500 20 3-54 HYDRANT 42
2146
HYD 3 True 1,500 3,500 3,500 20 3-54 HYDRANT 42
2146
HYD 4 True 1,500 3,500 3,500 20 3-54 HYDRANT 40
2146
HYD 5 True 1,500 3,500 3,500 20 3-54 HYDRANT 39
2146
HYD 6 True 1,500 3,500 3,500 20 3-54 HYDRANT 39
2146
HYD 7 True 1,500 3,500 3,500 20 3-54 HYDRANT 40
2146
HYD 8 True 1,500 3,500 3,500 20 3-54 HYDRANT 42
2146
HYD 9 True 1,500 3,500 3,500 20 3-54 HYDRANT 44
2146
HYD 10 True 1,500 3,500 3,500 20 3-54 HYDRANT 42
2146
HYD 11 True 1,500 3,500 3,500 20 3-54 HYDRANT 41
2146
HYD 12 True 1,500 3,500 3,500 20 3-54 HYDRANT 39
2146
HYD 13 True 1,500 3,500 3,500 20 3-98 HYDRANT 37
2146
HYD 14 True 1,500 3,500 3,500 20 3-54 HYDRANT 36
2146
HYD 15 True 1,500 3,500 3,500 20 3-54 HYDRANT 36
2146
HYD 16 True 1,500 3,500 3,500 20 3-103 HYDRANT 37
2146
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 3
+1-203-755-1666
Fire Flow Node FlexTable: Fire Flow Report
Label Satisfies Fire Fire Flow Fire Flow Flow(Total Pressure Junction w/ Junction w/ Pressure
Flow (Needed) (Available) Available) (Residual Minimum Minimum (Calculated
Constraints? (gpm) (gpm) (gpm) Lower Limit) Pressure Pressure Residual @
(psi) (Zone) (System) Total Flow
Needed)
(psi)
HYD 17 True 1,500 3,500 3,500 20 3-54 HYDRANT 35
2146
HYD 18 True 1,500 3,500 3,500 20 3-107 HYDRANT 36
2146
HYD 18 True 1,500 3,500 3,500 20 3-54 HYDRANT 35
2146
HYD 19 True 1,500 3,194 3,194 20 3-54 HYDRANT 33
2146
HYD 20 True 1,500 3,368 3,368 20 3-54 HYDRANT 33
2146
HYD 21 True 1,500 2,842 2,842 20 3-116 HYDRANT 30
2146
HYD 22 True 1,500 2,600 2,600 20 3-54 HYDRANT 30
2146
HYD 23 True 1,500 1,581 1,581 20 3-54 HYDRANT 21
2146
HYD 24 True 1,500 3,062 3,062 20 3-121 HYDRANT 31
2146
HYD 25 True 1,500 3,083 3,083 20 3-123 HYDRANT 31
2146
HYD 26 True 1,500 3,319 3,319 20 3-125 HYDRANT 32
2146
HYD 27 True 1,500 2,899 2,899 20 3-127 HYDRANT 31
2146
HYD 28 True 1,500 3,470 3,470 20 3-127 HYDRANT 34
2146
HYD 29 True 1,500 3,500 3,500 20 3-130 HYDRANT 34
2146
HYD 30 True 1,500 3,500 3,500 20 3-54 HYDRANT 37
2146
HYD 31 True 1,500 3,500 3,500 20 3-54 HYDRANT 37
2146
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 3
+1-203-755-1666
Fire Flow Node FlexTable: Fire Flow Report
Label Satisfies Fire Fire Flow Fire Flow Flow(Total Pressure Junction w/ Junction w/ Pressure
Flow (Needed) (Available) Available) (Residual Minimum Minimum (Calculated
Constraints? (gpm) (gpm) (gpm) Lower Limit) Pressure Pressure Residual @
(psi) (Zone) (System) Total Flow
Needed)
(psi)
HYD 32 True 1,500 3,500 3,500 20 3-54 HYDRANT 38
2146
HYD 33 True 1,500 3,500 3,500 20 DJ 7 HYDRANT 40
2146
HYD 34 True 1,500 3,079 3,079 20 3-144 HYDRANT 32
2146
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 3 of 3
+1-203-755-1666
FlexTable: Junction Table
ID Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (psi)
412 DJ 1 5,012.15 21 5,110.76 43
415 DJ 2 5,003.53 9 5,110.78 46
418 DJ 3 5,002.52 9 5,110.79 47
421 DJ 4 5,003.30 5 5,110.81 47
424 DJ 5 5,003.25 10 5,110.88 47
427 DJ 6 5,010.66 9 5,110.86 43
317 DJ 7 5,007.41 23 5,110.91 45
433 DJ 8 5,004.68 15 5,110.80 46
436 DJ 9 5,004.85 5 5,110.79 46
439 DJ 10 5,005.51 5 5,110.78 46
442 DJ 11 5,011.28 25 5,110.77 43
445 DJ 12 5,010.41 25 5,110.78 43
448 DJ 13 5,010.17 31 5,110.79 44
455 DJ 14 5,019.78 22 5,110.79 39
430 DJ 15 5,019.41 17 5,110.81 40
458 DJ 16 5,017.21 5 5,110.83 41
461 DJ 17 5,020.33 8 5,110.83 39
464 DJ 18 5,027.64 4 5,110.82 36
467 DJ 19 5,023.00 7 5,110.82 38
470 DJ 20 5,022.41 26 5,110.79 38
473 DJ 21 5,028.55 94 5,110.76 36
500 DJ 22 5,016.08 42 5,110.77 41
503 DJ 23 5,020.65 9 5,110.78 39
491 DJ 24 5,021.45 16 5,110.77 39
479 DJ 25 5,026.84 5 5,110.77 36
476 DJ 26 5,029.04 5 5,110.77 35
482 DJ 27 5,029.26 9 5,110.77 35
485 DJ 28 5,024.58 9 5,110.77 37
488 DJ 29 5,021.88 16 5,110.77 38
497 DJ 30 5,016.59 52 5,110.76 41
84 DJ 31 5,023.46 31 5,110.77 38
494 DJ 32 5,030.23 9 5,110.76 35
190 HYD 1 5,003.98 0 5,110.78 46
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 5
+1-203-755-1666
FlexTable: Junction Table
ID Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (psi)
194 HYD 2 5,003.24 0 5,110.78 47
198 HYD 3 5,005.44 0 5,110.78 46
202 HYD 4 5,006.53 0 5,110.77 45
206 HYD 5 5,010.70 0 5,110.77 43
210 HYD 6 5,010.14 0 5,110.77 44
211 HYD 7 5,008.93 0 5,110.79 44
215 HYD 8 5,004.48 0 5,110.79 46
219 HYD 9 5,002.11 0 5,110.80 47
223 HYD 10 5,005.59 0 5,110.82 46
227 HYD 11 5,007.00 0 5,110.81 45
232 HYD 12 5,011.80 0 5,110.81 43
236 HYD 13 5,015.48 0 5,110.80 41
240 HYD 14 5,020.18 0 5,110.80 39
244 HYD 15 5,018.61 0 5,110.79 40
245 HYD 16 5,014.61 0 5,110.79 42
249 HYD 17 5,022.05 0 5,110.78 38
253 HYD 18 5,017.67 0 5,110.77 40
257 HYD 18 5,019.97 0 5,110.78 39
261 HYD 19 5,023.31 0 5,110.77 38
265 HYD 20 5,025.44 0 5,110.77 37
269 HYD 21 5,030.40 0 5,110.77 35
270 HYD 22 5,028.47 0 5,110.77 36
277 HYD 23 5,031.88 0 5,110.76 34
281 HYD 24 5,028.15 0 5,110.77 36
285 HYD 25 5,029.12 0 5,110.79 35
289 HYD 26 5,027.10 0 5,110.82 36
293 HYD 27 5,027.16 0 5,110.82 36
297 HYD 28 5,021.38 0 5,110.82 39
304 HYD 29 5,023.40 0 5,110.82 38
305 HYD 30 5,016.46 0 5,110.84 41
309 HYD 31 5,017.60 0 5,110.82 40
313 HYD 32 5,013.34 0 5,110.83 42
322 HYD 33 5,007.42 0 5,110.92 45
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 5
+1-203-755-1666
FlexTable: Junction Table
ID Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (psi)
329 HYD 34 5,024.59 0 5,110.79 37
31 J-2 5,020.26 0 5,110.78 39
32 J-3 5,011.02 0 5,110.77 43
33 J-4 5,013.26 0 5,110.76 42
34 J-5 5,005.78 0 5,110.78 45
35 J-6 5,001.24 0 5,110.78 47
36 J-7 5,003.69 0 5,110.78 46
37 J-8 5,001.46 0 5,110.81 47
38 J-9 4,999.36 0 5,110.82 48
39 J-10 5,005.12 0 5,110.82 46
40 J-11 5,003.01 0 5,110.82 47
41 J-12 5,006.06 0 5,110.81 45
42 J-13 5,003.24 0 5,110.80 47
43 J-14 5,004.49 0 5,110.79 46
44 J-15 5,005.23 0 5,110.78 46
45 J-16 5,011.55 0 5,110.77 43
46 J-17 5,009.30 0 5,110.79 44
47 J-18 5,010.55 0 5,110.80 43
48 J-19 5,010.90 0 5,110.80 43
49 J-20 5,011.62 0 5,110.81 43
50 J-21 5,009.90 0 5,110.81 44
51 J-22 5,008.48 0 5,110.81 44
52 J-23 5,007.07 0 5,110.81 45
53 J-24 5,025.79 0 5,110.77 37
54 J-25 5,029.20 0 5,110.79 35
55 J-26 5,022.37 0 5,110.78 38
56 J-27 5,018.99 0 5,110.79 40
57 J-28 5,020.60 0 5,110.80 39
58 J-29 5,018.43 0 5,110.82 40
59 J-30 5,016.96 0 5,110.80 41
60 J-31 5,014.91 0 5,110.81 41
61 J-32 5,013.10 0 5,110.81 42
62 J-33 5,004.09 0 5,110.85 46
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 3 of 5
+1-203-755-1666
FlexTable: Junction Table
ID Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (psi)
64 J-35 5,002.46 0 5,110.92 47
65 J-36 5,001.71 0 5,110.94 47
66 J-37 5,007.72 0 5,110.90 45
67 J-38 5,007.97 0 5,110.89 45
68 J-39 5,008.92 0 5,110.88 44
69 J-40 5,009.87 0 5,110.87 44
70 J-41 5,012.64 0 5,110.83 42
71 J-42 5,013.04 0 5,110.83 42
72 J-43 5,015.03 0 5,110.83 41
73 J-44 5,017.62 0 5,110.82 40
74 J-45 5,016.33 0 5,110.84 41
75 J-46 5,016.44 0 5,110.84 41
76 J-47 5,021.74 0 5,110.82 39
77 J-48 5,023.82 0 5,110.82 38
78 J-49 5,027.30 0 5,110.82 36
79 J-50 5,027.89 0 5,110.82 36
80 J-51 5,027.89 0 5,110.77 36
81 J-52 5,030.41 0 5,110.77 35
82 J-53 5,028.25 0 5,110.77 36
83 J-54 5,032.26 0 5,110.76 34
85 J-56 5,027.68 0 5,110.77 36
86 J-57 5,025.96 0 5,110.77 37
87 J-58 5,021.04 0 5,110.77 39
88 J-59 5,022.71 0 5,110.77 38
89 J-60 5,020.43 0 5,110.78 39
91 J-62 5,003.37 0 5,110.78 46
92 J-63 5,003.61 0 5,110.87 46
137 J-69 5,004.57 0 5,110.83 46
150 J-70 5,012.29 0 5,110.83 43
187 J-72 5,003.81 0 5,110.78 46
191 J-74 5,003.97 0 5,110.78 46
195 J-76 5,005.99 0 5,110.78 45
199 J-78 5,006.41 0 5,110.77 45
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 4 of 5
+1-203-755-1666
FlexTable: Junction Table
ID Label Elevation Demand Hydraulic Grade Pressure
(ft) (gpm) (ft) (psi)
203 3-80 5,010.56 0 5,110.77 43
207 3-82 5,011.00 0 5,110.77 43
212 3-85 5,008.88 0 5,110.79 44
216 3-87 5,005.07 0 5,110.79 46
220 3-89 5,001.97 0 5,110.80 47
224 3-91 5,005.39 0 5,110.82 46
229 3-94 5,006.99 0 5,110.81 45
233 3-96 5,012.06 0 5,110.81 43
237 3-98 5,015.84 0 5,110.80 41
241 3-100 5,020.15 0 5,110.80 39
246 3-103 5,014.92 0 5,110.79 41
250 3-105 5,021.96 0 5,110.78 38
254 3-107 5,017.81 0 5,110.77 40
258 3-109 5,019.91 0 5,110.78 39
262 3-111 5,023.67 0 5,110.77 38
266 3-113 5,025.31 0 5,110.77 37
271 3-116 5,030.17 0 5,110.77 35
274 3-117 5,028.44 0 5,110.77 36
278 3-119 5,031.92 0 5,110.76 34
282 3-121 5,028.04 0 5,110.77 36
286 3-123 5,028.98 0 5,110.79 35
290 3-125 5,027.39 0 5,110.82 36
294 3-127 5,027.19 0 5,110.82 36
298 3-129 5,021.34 0 5,110.82 39
301 3-130 5,023.51 0 5,110.82 38
306 3-133 5,017.44 0 5,110.84 40
310 3-135 5,017.89 0 5,110.82 40
314 3-137 5,013.22 0 5,110.83 42
318 3-139 5,002.49 0 5,110.92 47
323 3-141 5,006.48 0 5,110.92 45
326 3-142 5,018.62 0 5,110.79 40
330 1 3-144 1 5,025.21 0 1 5,110.79 1 37
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 5 of 5
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
333 P-88 15 HYD 1 J-72 6.0 130.0 0 0.00 0.000
334 P-89 11 HYD 2 J-74 6.0 130.0 0 0.00 0.000
338 P-92 15 HYD 9 J-89 6.0 130.0 0 0.00 0.000
339 P-93 15 HYD 10 J-91 6.0 130.0 0 0.00 0.000
340 P-94 5 HYD 33 J-141 6.0 130.0 0 0.00 0.000
341 P-95 17 HYD 32 J-137 6.0 130.0 0 0.00 0.000
342 P-96 10 HYD 31 J-135 6.0 130.0 0 0.00 0.000
343 P-97 15 HYD 30 J-133 6.0 130.0 0 0.00 0.000
344 P-98 15 HYD 28 J-129 6.0 130.0 0 0.00 0.000
345 P-99 15 HYD 27 J-127 6.0 130.0 0 0.00 0.000
346 P-100 15 HYD 26 J-125 6.0 130.0 0 0.00 0.000
347 P-101 15 HYD 25 J-123 6.0 130.0 0 0.00 0.000
348 P-102 15 HYD 24 J-121 6.0 130.0 0 0.00 0.000
349 P-103 15 HYD 21 J-116 6.0 130.0 0 0.00 0.000
350 P-104 15 HYD 22 J-117 6.0 130.0 0 0.00 0.000
351 P-105 15 HYD 23 J-119 6.0 130.0 0 0.00 0.000
352 P-106 15 HYD 19 J-111 6.0 130.0 0 0.00 0.000
354 P-107 15 HYD 20 J-113 6.0 130.0 0 0.00 0.000
355 P-108 15 HYD 17 J-105 6.0 130.0 0 0.00 0.000
356 P-109 15 HYD 18 J-109 6.0 130.0 0 0.00 0.000
357 P-110 15 HYD 5 J-80 6.0 130.0 0 0.00 0.000
358 P-111 15 HYD 6 J-82 6.0 130.0 0 0.00 0.000
359 P-112 15 HYD 7 J-85 6.0 130.0 0 0.00 0.000
360 P-113 15 HYD 12 J-96 6.0 130.0 0 0.00 0.000
361 P-114 11 HYD 16 J-103 6.0 130.0 0 0.00 0.000
362 P-115 11 HYD 13 J-98 6.0 130.0 0 0.00 0.000
363 P-116 12 HYD 18 J-107 6.0 130.0 0 0.00 0.000
364 P-117 12 HYD 11 J-94 6.0 130.0 0 0.00 0.000
365 P-118 10 HYD 8 J-87 6.0 130.0 0 0.00 0.000
366 P-119 10 HYD 3 J-76 6.0 130.0 0 0.00 0.000
367 P-120 16 HYD 4 J-78 6.0 130.0 0 0.00 0.000
368 P-121 15 HYD 34 J-144 6.0 130.0 0 0.00 0.000
369 P-122 15 HYD 29 J-130 6.0 130.0 0 0.00 0.000
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 1 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
410 P-123 15 HYD 15 3-142 6.0 130.0 0 0.00 0.000
411 P-124 15 HYD 14 3-100 6.0 130.0 0 0.00 0.000
97 P-4 124 3-62 3-6 8.0 130.0 0 0.00 0.390
103 P-9 125 3-8 3-9 8.0 130.0 -54 0.34 0.390
105 P-11 80 3-13 3-14 8.0 130.0 53 0.34 0.740
114 P-19 138 3-26 3-59 8.0 130.0 38 0.24 0.000
116 P-21 136 3-58 3-2 8.0 130.0 -35 0.22 0.000
119 P-23 190 3-58 DJ 31 8.0 130.0 33 0.21 0.350
123 P-27 138 3-60 3-27 8.0 130.0 -51 0.33 0.000
128 P-31 69 3-18 3-19 8.0 130.0 -48 0.31 0.000
129 P-32 91 3-19 3-20 8.0 130.0 -48 0.31 0.390
130 P-33 124 3-20 3-21 8.0 130.0 -18 0.11 0.000
131 P-34 111 3-21 3-22 8.0 130.0 -18 0.11 0.000
132 P-35 111 3-22 3-23 8.0 130.0 -18 0.11 0.000
136 P-39 124 3-10 3-11 8.0 130.0 0 0.00 0.000
138 P-40 60 3-10 3-69 8.0 130.0 -85 0.54 0.000
139 P-41 88 3-69 3-33 8.0 130.0 -85 0.54 0.000
140 P-42 88 3-33 3-63 8.0 130.0 -85 0.54 0.000
142 P-44 58 3-35 3-36 8.0 130.0 -118 0.75 0.400
145 P-47 28 3-37 3-38 8.0 130.0 82 0.52 0.000
146 P-48 69 3-38 3-39 8.0 130.0 82 0.52 0.200
147 P-49 69 3-39 3-40 8.0 130.0 82 0.52 0.000
149 P-51 33 3-41 3-42 8.0 130.0 27 0.17 0.000
151 P-52 35 3-41 3-70 8.0 130.0 46 0.29 0.740
152 P-53 367 3-70 3-20 8.0 130.0 46 0.29 0.050
154 P-55 114 3-32 3-31 8.0 130.0 16 0.10 0.000
159 P-60 168 3-44 3-43 8.0 130.0 -27 0.17 0.000
167 P-68 65 3-46 3-45 8.0 130.0 -40 0.25 0.350
171 P-72 146 3-51 3-57 8.0 130.0 -22 0.14 0.000
172 P-73 372 3-57 3-60 8.0 130.0 -29 0.19 0.000
175 P-76 330 3-53 DJ 31 8.0 130.0 -9 0.06 0.700
179 P-79 148 3-52 3-56 8.0 130.0 -16 0.10 0.000
180 P-80 180 3-56 3-24 8.0 130.0 -14 0.09 0.000
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 2 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
188 P-3(1) 180 3-5 3-72 8.0 130.0 -13 0.09 0.740
189 P-3(2) 40 3-72 3-62 8.0 130.0 -13 0.09 0.350
192 P-6(1) 180 3-15 3-74 8.0 130.0 -16 0.10 0.740
193 P-6(2) 40 3-74 3-7 8.0 130.0 -16 0.10 0.350
196 P-13(1) 41 3-15 3-76 8.0 130.0 25 0.16 0.890
201 P-2(2) 41 3-78 3-5 8.0 130.0 -28 0.18 0.740
204 P12(1) 29 3-3 3-80 8.0 130.0 -28 0.18 0.740
205 P22(1) 267 3-80 3-78 8.0 130.0 -28 0.18 0.350
208 P1)3(2) 267 3-76 3-82 8.0 130.0 25 0.16 0.350
209 P2)3(2) 29 3-82 3-16 8.0 130.0 25 0.16 0.740
213 P-16(1) 29 3-17 3-85 8.0 130.0 -20 0.13 0.740
217 P1)6(2) 267 3-85 3-87 8.0 130.0 -20 0.13 0.350
218 P2)6(2) 40 3-87 3-14 8.0 130.0 -20 0.13 0.740
221 P-10(1) 40 3-8 3-89 8.0 130.0 35 0.22 0.500
222 P-10(2) 100 3-89 3-13 8.0 130.0 35 0.22 0.350
225 P-86(1) 99 3-12 3-91 8.0 130.0 -51 0.33 0.350
226 P-86(2) 40 3-91 3-10 8.0 130.0 -51 0.33 0.000
230 P-36(1) 11 3-23 3-94 8.0 130.0 -18 0.11 0.350
231 P-36(2) 134 3-94 3-12 8.0 130.0 -18 0.11 0.350
234 P-54(1) 48 3-20 3-96 8.0 130.0 16 0.10 0.000
235 P-54(2) 115 3-96 3-32 8.0 130.0 16 0.10 0.000
238 P-56(1) 52 3-31 3-98 8.0 130.0 16 0.10 0.000
239 P-56(2) 62 3-98 3-30 8.0 130.0 16 0.10 0.350
242 P-57(1) 169 3-30 3-100 8.0 130.0 16 0.10 0.000
243 P-57(2) 24 3-100 3-28 8.0 130.0 16 0.10 0.740
248 P-29(2) 358 3-103 3-17 8.0 130.0 5 0.03 0.390
251 P-18(1) 24 3-26 3-105 8.0 130.0 28 0.18 0.740
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 3 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
255 P1)8(2) 237 3-105 3-107 8.0 130.0 28 0.18 0.350
259 P-22(1) 23 3-2 3-109 8.0 130.0 40 0.26 0.740
263 P-24(1) 40 DJ 31 3-111 8.0 130.0 -6 0.04 0.740
267 P-25(1) 30 3-24 3-113 8.0 130.0 -30 0.19 0.740
268 P-25(2) 160 3-113 3-59 8.0 130.0 -30 0.19 0.000
272 P-78(1) 41 3-52 3-116 8.0 130.0 7 0.04 0.740
275 P-77(1) 41 3-53 3-117 8.0 130.0 0 0.00 0.740
279 P-75(1) 37 3-54 3-119 8.0 130.0 0 0.00 0.000
284 P-71(2) 41 3-121 3-51 8.0 130.0 -23 0.15 0.740
287 P-64(1) 41 3-25 3-123 8.0 130.0 -53 0.34 0.740
288 P-64(2) 310 3-123 3-49 8.0 130.0 -53 0.34 0.500
291 P-81(1) 61 3-49 3-125 8.0 130.0 -12 0.07 0.000
295 P-82(1) 29 3-50 3-127 8.0 130.0 -15 0.10 0.740
296 P-82(2) 231 3-127 3-47 8.0 130.0 -15 0.10 0.000
299 P-67(1) 30 3-47 3-129 8.0 130.0 -32 0.20 0.000
302 P-66(1) 61 3-48 3-130 8.0 130.0 -10 0.06 0.740
308 P2)7(2) 74 3-133 3-46 8.0 130.0 -40 0.25 0.390
311 P-59(1) 25 3-29 3-135 8.0 130.0 -27 0.17 0.740
312 P-59(2) 12 3-135 3-44 8.0 130.0 -27 0.17 0.000
315 P-61(1) 153 3-43 3-137 8.0 130.0 -27 0.17 0.350
316 P-61(2) 15 3-137 3-42 8.0 130.0 -27 0.17 0.390
320 P-43(2) 5 3-139 3-35 8.0 130.0 -118 0.75 0.000
324 P-87(1) 31 DJ 7 3-141 8.0 130.0 -23 0.15 0.000
325 P-87(2) 134 3-141 3-139 8.0 130.0 -23 0.15 0.350
327 (1)9(1) 24 3-27 3-142 8.0 130.0 5 0.03 0.740
328 (2)9(1) 235 3-142 3-103 8.0 130.0 5 0.03 0.350
332 P-63(2) 305 3-144 3-25 8.0 130.0 18 0.11 0.700
413 P-1(1) 211 3-4 DJ 1 8.0 130.0 0 0.00 0.000
414 P-1(2) 213 DJ 1 3-3 8.0 130.0 -21 0.13 0.500
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 4 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
416 P-7(1) 220 3-7 DJ 2 8.0 130.0 23 0.14 0.390
417 P-7(2) 230 DJ 2 3-62 8.0 130.0 13 0.09 0.000
419 P-8(1) 219 3-7 DJ 3 8.0 130.0 -39 0.25 0.000
420 P-8(2) 199 DJ 3 3-8 8.0 130.0 -48 0.31 0.000
422 P-38(1) 294 3-8 DJ 4 8.0 130.0 -29 0.19 0.000
423 P-38(2) 290 DJ 4 3-10 8.0 130.0 -34 0.22 0.500
425 (Pi)3(1) 67 3-63 DJ 5 8.0 130.0 -85 0.54 0.000
426 P2)3(1) 144 DJ 5 3-139 8.0 130.0 -95 0.61 0.350
428 P-50(1) 62 3-40 DJ 6 8.0 130.0 82 0.52 0.000
429 P-50(2) 156 DJ 6 3-41 8.0 130.0 72 0.46 0.390
434 P-37(1) 286 3-12 DJ 8 8.0 130.0 33 0.21 0.000
435 P-37(2) 298 DJ 8 3-13 8.0 130.0 18 0.11 0.000
437 P-12(1) 206 3-14 DJ 9 8.0 130.0 33 0.21 0.000
438 P-12(2) 212 DJ 9 3-15 8.0 130.0 28 0.18 0.000
440 P-5(1) 220 3-5 DJ 10 8.0 130.0 -15 0.09 0.000
441 P-5(2) 230 DJ 10 3-15 8.0 130.0 -19 0.12 0.000
443 P-14(1) 228 3-16 DJ 11 8.0 130.0 29 0.19 0.500
444 P-14(2) 222 DJ 11 3-3 8.0 130.0 4 0.03 0.740
446 P-15(1) 211 3-16 DJ 12 8.0 130.0 -18 0.12 0.000
447 P-15(2) 207 DJ 12 3-17 8.0 130.0 -43 0.27 0.890
449 P-30(1) 230 3-17 DJ 13 8.0 130.0 -17 0.11 0.390
450 P-30(2) 102 DJ 13 3-18 8.0 130.0 -48 0.31 0.000
462 P 67(2) 75 3-129 DJ 17 8.0 130.0 -32 0.20 0.350
(1)(1)
463 P 67(2) 215 DJ 17 3-133 8.0 130.0 -40 0.25 0.000
(1)(2)
465 P1)1(2) 174 3-125 DJ 18 8.0 130.0 -12 0.07 0.000
466 (P2)1(2) 179 DJ 18 3-50 8.0 130.0 -15 0.10 0.350
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 5 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
468 P1)6(2) 102 3-130 DJ 19 8.0 130.0 -10 0.06 0.000
469 P2)6(2) 250 DJ 19 3-47 8.0 130.0 -16 0.10 0.350
471 (Pi)3(1) 138 3-28 DJ 20 8.0 130.0 44 0.28 0.000
472 P2)3(1) 213 DJ 20 3-144 8.0 130.0 18 0.11 0.350
474 (Pi)1(1) 179 3-25 DJ 21 8.0 130.0 71 0.45 0.700
475 (P2)1(1) 141 DJ 21 3-121 8.0 130.0 -23 0.15 0.000
477 P1)8(2) 186 3-116 DJ 26 8.0 130.0 7 0.04 0.000
478 P2)8(2) 192 DJ 26 3-51 8.0 130.0 1 0.01 0.350
480 P-74(1) 205 3-56 DJ 25 8.0 130.0 -2 0.01 0.000
481 P-74(2) 213 DJ 25 3-57 8.0 130.0 -7 0.05 0.000
483 P1)7(2) 170 3-117 DJ 27 8.0 130.0 0 0.00 0.000
484 P2)7(2) 240 DJ 27 3-52 8.0 130.0 -10 0.06 0.350
486 P1)4(2) 175 3-111 DJ 28 8.0 130.0 -6 0.04 0.700
487 P2)4(2) 234 DJ 28 3-24 8.0 130.0 -16 0.10 0.700
489 P-20(1) 222 3-59 DJ 29 8.0 130.0 14 0.09 0.350
490 P-20(2) 228 DJ 29 3-58 8.0 130.0 -2 0.01 0.000
492 P-26(1) 232 3-59 DJ 24 8.0 130.0 -6 0.04 0.000
493 P-26(2) 186 DJ 24 3-60 8.0 130.0 -22 0.14 0.700
495 P1)5(2) 182 3-119 DJ 32 8.0 130.0 0 0.00 0.000
496 P2)5(2) 212 DJ 32 3-53 8.0 130.0 -9 0.06 0.350
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 6 of 7
+1-203-755-1666
FlexTable: Pipe Table
ID Label Length Start Stop Diameter Hazen-Williams Flow Velocity Minor Loss
(Scaled) Node Node (in) C (gpm) (ft/s) Coefficient
(ft) (Derived)
498 P1)2(2) 223 3-109 DJ 30 8.0 130.0 40 0.26 0.700
499 P2)2(2) 375 DJ 30 3-3 8.0 130.0 -12 0.08 0.000
501 P 18(2) 99 3-107 DJ 22 8.0 130.0 28 0.18 0.000
(2)(1)
502 P 18(2) 259 DJ 22 3-16 8.0 130.0 -14 0.09 0.000
(2)(2)
514 P-127 16 HYDRANT 3-9 8.0 130.0 54 0.34 0.000
2680
164 P-65 262 3-49 3-48 12.0 130.0 -41 0.12 0.350
169 P-70 393 3-29 3-48 12.0 130.0 32 0.09 0.000
144 P-46 396 3-36 3-37 16.0 130.0 404 0.65 0.000
184 P-84 450 3-2 3-26 16.0 130.0 -75 0.12 0.350
185 P-85 665 3-37 3-45 16.0 130.0 323 0.51 0.350
431 P-58(1) 193 3-28 DJ 15 16.0 130.0 -257 0.41 0.000
432 P-58(2) 158 DJ 15 3-29 16.0 130.0 -274 0.44 0.500
456 P-62(1) 183 3-28 DJ 14 16.0 130.0 229 0.36 0.500
457 P-62(2) 177 DJ 14 3-27 16.0 130.0 206 0.33 0.000
459 P-69(1) 146 3-45 DJ 16 16.0 130.0 283 0.45 0.350
460 P-69(2) 202 DJ 16 3-29 16.0 130.0 279 0.44 0.000
504 P-28(1) 205 3-27 DJ 23 16.0 130.0 150 0.24 0.500
505 P-28(2) 213 DJ 23 3-26 16.0 130.0 141 0.22 0.000
520 P-129 16 HYDRANT 3-36 16.0 130.0 523 0.83 0.000
2146
HYDRA
516 P-128 30 R-2 NT 9,999.0 130.0 54 0.00 0.000
2680
HYDRA
524 P-131 16 R-3 NT 9,999.0 130.0 523 0.00 0.000
2146
WaterCAD
WaterModel.wtg Bentley Systems,Inc. Haestad Methods Solution Center [10.03.02.75]
3/12/2021 27 Siemon Company Drive Suite 200 W Watertown,CT 06795 USA Page 7 of 7
+1-203-755-1666
Appendix 7 — City of Bozeman Correspondence
Josh Wolfram
From: Lance Lehigh <Ilehigh@BOZEMAN.NET>
Sent: Thursday, November 14, 2024 2:42 PM
To: Josh Wolfram
Cc: Joselyn Hartwig; Christopher Budeski;jBurtell@SummitFireSecurity.com; Scott Mueller;
Shawn Kohtz
Subject: RE: [EXTERNAL][SENDER UNVERIFIED]Blackwood Groves Fire Flows
Attachments: ATT00001.txt;ATT00002.htm
Follow Up Flag: Follow up
Flag Status: Flagged
WARNING: This email originated from an external sender. Please use caution when clicking links or opening
attachments.
Josh and team,
The City requires a minimum fire flow of 1,500 gpm on the City's distribution system at a residual pressure at 20 psi at
the hydrant/main, noting some hydrants may not meet these requirements at dead ends.The City owns the distribution
system, and this is where the City's Fire Department will connect in an event to fight a fire. Providing some additional
context,the City's water facility plan recommends fire flows of at least 1,500 gpm or higher on the mains, depending on
the anticipated land use, and provides recommended long-term infrastructure requirements, such as backbone
transmission mains to be constructed as development occurs to achieve these recommendations as the City builds out.
This helps the City maintain a good ISO rating for insurance.
When new buildings are constructed,the Fire Code requires a water supply to meet the fire flow for that particular
building type.The fire flow value is a building-specific value. Without going into exhaustive detail,the value is calculated
on the area of the building,type of construction, occupancy of the building, presence or lack of fire sprinklers, etc. If the
building is not suppressed,then the needed fire flow increases to meet the needed fire flow requirements for that
particular building type. In general, almost all new construction of any scale requires a fire suppression system.
The fire suppression design engineer will evaluate these parameters, including the available flow that can be provided by
the City's distribution system, and design a system to meet IBC/IFC codes for that particular structure.
I think the confusion may be around what is required at the distribution system node (hydrant) and what is required for
the fire line to supply the fire suppression system, which are two different values. Ensure you can provide the proper fire
fighting flow to the hydrants (minimum 1,500 gpm)within the development and the needed fire flow to the suppression
system fire line to meet IBC/IFC codes.
Even with a reduced flow due to an automatic sprinkler system in a building, the City wants to achieve 1,500 gpm at the
hydrant/distribution main for fire flow purposes.
I hope this clears up any confusion and lays a path forward for all parties. Please let us know if you have additional
questions.
Lance
City of Bozeman
i
Lance Lehigh, PE, CFM I Engineer III
From:Josh Wolfram <jwolfram@wwcengineering.com>
Sent: Monday, November 11, 2024 11:07 AM
To: Lance Lehigh <Ilehigh@BOZEMAN.NET>
Cc:Joselyn Hartwig<jhartwig@wwcengineering.com>; Christopher Budeski <cbudeski@wwcengineering.com>;
jBurtell@SummitFireSecurity.com
Subject: [EXTERNAL][SENDER UNVERIFIED]Blackwood Groves Fire Flows
CAUTION:This email originated from outside of the organization. Do not click links or open attachments unless you recognize the
sender and know the content is safe.
Lance,
We are working on modeling the flows for the proposed water main and services at Blackwood Groves for our
infrastructure submittal. We have had projects in the past where the City has required 1500 gpm to each fire
service, however we failed to find anywhere in the International Fire Code or City code that states this. Joe with
Summit Fire Security relayed that you had a conversation on Friday about this and that the City would not
require 1500 gpm to each fire service to approve the infrastructure. Can you confirm this is the case?
Let me know if you have any questions.
Thanks,
r NOW A YAKY Or'
MADISON ^
ENGINEERING �r WWC
—J ENGINEERING
JOSH WOLFRAM I Associate Engineer
895 Technology Blvd,Ste 203 1 Bozeman,MT 59718
0:406.586.0262 1 D:406.898.3445
www.wwcengineering.com
2