HomeMy WebLinkAbout009 - Informal Review CommentsREF #CYCLE REVIEWED BY TYPE FILENAME
1 CD Technician
Luz Chase
10/2/23 2:25 PM
Checklist Item
Reference Sect. 38.420 to verify if parkland is required. If so please explain how the
requirements will be satisfied.
2 CD Technician
Luz Chase
10/2/23 2:25 PM
Checklist Item
If you have questions for city staff, include them in the narrative for city staff to
review.3 1 Solid Waste
Russell Ward
10/6/23 2:52 PM
Changemark
SLD Waste
1. is this an enclosure or a trash room? if it is a trash room it will need to be written
into covenants that it is managements responsibility to move trash dumpster out to
tip pad for collection. tip pad will need to be heated. must also have 50 foot
straight approach to tip pad. 2. if this is an enclosure then we will also need 50 foot
straight approach to front of enclosure, no parking allowed within the 50 foot
approach. we will also need to have detailed plans for the covered enclosure.
002 - A101 - First and Second Floor
Plans.PDF
4 1 Building Division
Ben Abbey
10/18/23 10:15 AM
Changemark
BLDG - EV-Parking
EV parking is a concern for fire hazard. The building codes do not directly address
the life safety. Additional Separations or provision could be proposed thru [A]
104.11 Alternative methods. Recommend doing this before submitting for building
application for approval.
002 - A101 - First and Second Floor
Plans.PDF
5 1 Building Division
Ben Abbey
10/18/23 10:15 AM
Changemark
BLDG - Design Criteria
https://www.bozeman.net/departments/community-
development/building/bozeman-design-criteria
002 - A101 - First and Second Floor
Plans.PDF
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
REVIEW COMMENTS
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
6 1 Building Division
Ben Abbey
10/18/23 10:15 AM
Changemark
BLDG - Adopted Codes
https://www.bozeman.net/departments/community-
development/building/adopted-codes
002 - A101 - First and Second Floor
Plans.PDF
7 1 Building Division
Ben Abbey
10/18/23 10:15 AM
Changemark
BLDG - Elevator two-way communication
Two-way Communication is required in the application. Please include details in
your building application construction documents.
002 - A101 - First and Second Floor
Plans.PDF
8 1 Forestry Division
Alex Nordquest
10/18/23 10:42 AM
Changemark
Forestry Changemark note #01
Blvd trees shall be spaced at least 10' clear of signage, especially for a bus stop.
Please adjust tree spacing or consider omitting a tree from the proposed
Landscape Plan. Blvd trees can be spaced as close as 25-30' from each other
(depending on species) to accommodate utilities & signage
011 - Landscape Plan.pdf
9 1 Forestry Division
Alex Nordquest
10/18/23 10:44 AM
Changemark
Forestry Changemark note #02
Proposed tree is unnecessarily close to hydrant (minimum of 10' required). Blvd
trees can be spaced as close together as 25-30' depending on species.
011 - Landscape Plan.pdf
10 1 Forestry Division
Alex Nordquest
10/18/23 10:45 AM
Changemark
Forestry Changemark note #03
Please omit proposed tree from the Landscape Plan. Too many spacing conflicts
with Stop sign, Street Vision Triangle, and No Parking sign.
011 - Landscape Plan.pdf
11 1 Stormwater Division
Russ Smith
10/18/23 11:24 AM
Changemark
R.Smith - Stormwater
There is an infiltration chamber at this location, not a drywell. Please describe in
detail how the stormwater from the public right of way will be retrofitted or
modified to handle stormflows on and off-site. Please provide appropriate
easements and maintenance plans for all stormwater treatment facilities.
010 - C1.0 Civil Concept Plan.pdf
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
12 1 Water and Sewer
Division
Nick Pericich
10/20/23 11:44 AM
Changemark
W/S Water Services
There are two pairs of 2" domestic water and 4" fire stubs into the lot in this area.
The posts are likely delineating these stubs. You will have to terminate water
services that aren't used at the water main in the street. You can only have one
domestic water service and meter for each building or property. Which in this case
010 - C1.0 Civil Concept Plan.pdf
13 1 Water and Sewer
Division
Nick Pericich
10/20/23 11:44 AM
Changemark
W/S Stormtech Chamber
This is illustrated on our record drawing that this is not a drywell. It is a stormtech
chamber.
010 - C1.0 Civil Concept Plan.pdf
14 1 Water and Sewer
Division
Nick Pericich
10/20/23 11:44 AM
Changemark
W/S Water Service
This is actually a 2" domestic water and 4" fire setup at this point. It is unlikely that
112 units will be served by a 2" domestic water service and I'm not sure what size
fire service will be needed, but that is what is existing.
010 - C1.0 Civil Concept Plan.pdf
15 1 Water and Sewer
Division
Nick Pericich
10/20/23 11:44 AM
Changemark
W/S Sewer Stub
There is an existing sewer stub in this vicinity that isn't shown on your drawing.
010 - C1.0 Civil Concept Plan.pdf
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
16 1 Engineering
Suzanne Ryan
10/24/23 11:51 AM
Library Comment
BMC 38.410.130. Water Adequacy: The development will need to satisfy the water
adequacy code requirement prior to a future site plan approval. If sufficient water
rights cant be provided to offsets the development's annual demand then a cash-in-
lieu of water rights (CILWR) payment will be required. The City assesses the CILWR
fee at a rate of $6,000 per acre-foot. The fee determination will take place during
the site plan review, however if there are any questions or if a preliminary review is
desired please contact Griffin Nielsen with the Engineering/Utilities Department
directly at gnielsen@bozeman.net or (406) 582-2279. The City encourages the use
of groundwater wells to supply irrigation demands, which in turn will reduce the
CILWR fee. Applicant must obtain a pre-determination from the DNRC
demonstrating that a well groundwater well may be permitted under Montanas
exempt appropriation or that provide the water right documentation if existing
prior to finalization of the CILWR fee determination. Finally, the City would like to
make the owner aware of an available CILWR rebate of approximately 20% for
residential units if high-efficiency fixtures (toilets, washers, and shower heads)
meeting the City Water Conservation Division standards are installed. The rebate
would be released at occupancy and requires an agreement defining the terms and
amount rebate be finalized and executed prior to final plan approval. If the owner is 17 1 Engineering
Suzanne Ryan
10/24/23 11:51 AM
Library Comment
BMC 38.410.060 - Easements: Show all easements on plans.
18 1 Engineering
Suzanne Ryan
10/24/23 11:51 AM
Library Comment
DSSP Plans and Specifications Review Policy A. -Plans, specifications, and submittals
for public infrastructure improvements must be submitted to the City Engineering
Department through the engineering Project Dox Portal
(https://www.bozeman.net/services/development-center) for infrastructure review.
(fireline).
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
19 1 Engineering
Suzanne Ryan
10/24/23 11:52 AM
Library Comment
DSSP II.B.1 A Storm Drainage Plan shall include a map or plat showing building
site(s), open areas, drainage ways, ditches, culverts, bridges, storm sewers, inlets,
storage ponds, roads, streets, and any other drainage improvements. The map shall
also include identification and square foot coverage of the various ground surfaces
(i.e. vegetation, gravel, pavement, structures).
20 1 Engineering
Suzanne Ryan
10/24/23 11:52 AM
Library Comment
DSSP Section II A. 4. - The applicant must include a storm drainage plan with post-
construction storm water management controls that are designed to infiltrate,
evapotranspire, and/or capture for reuse the post-construction runoff generated
from the first 0.5 inches of rainfall from a 24-hour storm preceded by 48 hours of
no measurable precipitation.21 1 Engineering
Suzanne Ryan
10/24/23 11:52 AM
Library Comment
Montana Post Construction Storm Water BMP Design Manual - The proposed
project is located in an area that is known to have seasonally high groundwater.
The applicant must demonstrate that seasonal high groundwater will not impact
the function or maintenance of the proposed facilities. Industry guidance
recommends a three-foot minimum separation from the bottom of the proposed
facility to the underlying groundwater table. The applicant must provide local
seasonal high groundwater elevations to support the proposed design.22 1 Engineering
Suzanne Ryan
10/24/23 11:52 AM
Library Comment
DSSP Section II C. - The applicant must provide on-site detention with release rates
limited to predevelopment runoff rates. Retention ponds must be sized based on a
10-year, 2-hour storm intensity.23 1 Engineering
Suzanne Ryan
10/24/23 11:53 AM
Library Comment
BMC 38.220.080 A. 2.i. - A traffic impact study will be required for the proposed
development which will need to discuss how much daily traffic will be generated on
existing local and neighborhood streets, roads and alleys, when the subdivision is
fully developed.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
24 1 Engineering
Suzanne Ryan
10/24/23 11:53 AM
Library Comment
BMC 38.270.020 - Construction Routes: A construction route map must be provided
showing how materials and heavy equipment will travel to and from the site.
25 1 Engineering
Suzanne Ryan
10/24/23 11:53 AM
Library Comment
DSSP Section V. B. - Sanitary Sewer System Design Criteria: The applicant must
provide an estimate of the peak-hour sanitary sewer demand certified by a
professional engineer for the proposed project prior to site plan approval.
26 1 Engineering
Suzanne Ryan
10/24/23 11:54 AM
Library Comment
DSSP Section V.A. Water -The applicant must provide an estimate of the maximum
day demand plus fire flow and the peak hour demand.27 1 Engineering
Suzanne Ryan
10/24/23 12:01 PM
Comment
The proposed project is within a half a mile of 27th and Baxter Lane. 27th and
Baxter Lane is on the Capital Improvement plan within the next 5 years. The
applicant will be required to pay CIL of infrastructure for their respective impacts.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
28 1 Water Conservation
Division
Eric Neustrup
10/25/23 10:13 AM
Comment
Outdoor Watering: Best Practices for Water Efficiency Recommendations:
1.Hydrozoning: Landscaped areas should be on separate irrigation zones (valves)
based on the vegetations water demand. Grouping plants with similar watering
needs in the same irrigation zone will reduce over or under watering of the
vegetation. 2.Drought Tolerant Landscaping: Drought tolerant and water-wise
landscaping requires approximately 75% less water than turfgrass. Maximizing the
installation of drought tolerant landscaping, especially within areas surrounded by
pavement is recommended to improve aesthetics and maximize water efficiency.
3.Topsoil: A topsoil depth of 4- 6 (after grading) should be installed in seeded and
sodded areas. This will support proper root depth growth and assist with plant and
turfgrass resiliency. 4.Drip Irrigation: Perennials, shrubs, and trees should be
irrigated using low flow drip irrigation technology that will directly target the roots.
5.MSMT (Rotary) Nozzles: Multi-stream, multi-trajectory (MSMT) rotary nozzles can
reduce water loss from evaporation and wind drift by up to 50%, and allow more
time for water to infiltrate into the soil, reducing runoff. MSMT rotary nozzles
should be installed where overhead irrigation is to be used. 6.Weather-based
Irrigation Controllers: When programmed properly, weather-based irrigation
controllers can reduce outdoor water use by 25%. A weather-based irrigation
controller that can automatically adjust the watering schedule according to local
weather events should be installed. 7.Narrow Landscaped Area Irrigation: Utilizing
overhead spray irrigation in narrow landscaped areas (< 8) can result in large
amounts of overspray onto pavement and other surrounding areas. Low volume
drip or subsurface drip irrigation should be installed in these areas to eliminate
overspray. Alternatively, consider plantings that will not require irrigation beyond
the establishment period to avoid wasting water in these narrow landscaped areas.
8.Pressure Regulation: To ensure uniform coverage of turf areas, the use of pressure
regulating sprinkler bodies is encouraged. These sprinkler bodies can help avoid
inconsistent spray patterns within one zone, in which certain heads may result in
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
29 1 Fire Department
Scott Mueller
10/25/23 1:14 PM
Comment
The proposed building is required to have a ground level exterior accessed fire
control room. Room shall contain fire alarm control panel and fire riser. FDC shall
be located on building/parking lot front and be within 100 feet of a fire hydrant.
Site circulation for fire apparatus is acceptable.30 1 Parks Department
Ross Knapper
10/27/23 10:10 AM
Changemark
Parks
38.220.080.A.2.o - Site Plan Requirements Please add a parkland tracking table to
001-A010-Site Plan showing the park and recreation requirements for this project.
If proposing CILP to meet parkland requirements, please use the parkland tracking
table provided in the City Documents folder.
001 - A010 - Site Plan.PDF
31 1 Parks Department
Ross Knapper
10/27/23 10:12 AM
Changemark
Parks
38.420.020.A.1. - Park and Recreation Requirements Please add a section to the
narrative document that describes how the project satisfies the park and recreation
requirements listed in Sec. 38.420.
003 Project Narrative.pdf
32 1 Parks Department
Ross Knapper
10/27/23 10:13 AM
Changemark
Parks
38.420.030.A. - Cash donation in-lieu of land dedication If project proposes CILP,
please include a narrative statement that addresses how the projects meets the
criteria for cash-in-lieu as established in City Commission Resolution No. 4784, A
Resolution of the City Commission of the City of Bozeman, Montana, Establishing
the Criteria for Evaluation of Requests for Use of Cash-In-Lieu of Parkland
003 Project Narrative.pdf
33 1 Planning
Nakeisha Lyon
11/7/23 3:33 PM
Changemark
Dwelling Units Count
The drawings denote 112 units. Please ensure this information is consistent within
the submittal.
001 Bozeman Planning Application
Signed.pdf
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
34 1 Planning
Nakeisha Lyon
11/7/23 3:33 PM
Comment
Proposed UDC: The adoption of the new UDC has been put on hold by our City
Commission, and Staff is not aware of when this will be back on schedule to be
adopted. Please provide some consideration to this as you work through
formalizing your site plan submittal and the timeline that works best for you and
your client. 35 1 Planning
Nakeisha Lyon
11/7/23 3:35 PM
Library Comment
BMC 38.220.080 - Site Plan Submittal Requirements. The application must meet the
SP form requirements. Please ensure conformance with this section of the BMC and
the Site Plan Checklist (SP) during the formal submittal process.
36 1 Planning
Nakeisha Lyon
11/7/23 3:37 PM
Library Comment
BMC 38.320.030.C. Form and intensity standards elements. Density. Please provide
the minimum density calculations to demonstrate conformance with the R-5 zoning
district. Per Footnote 1 of this table, the minimum density in the R-5 zone is eight
dwelling units per "gross" acre.37 1 Planning
Nakeisha Lyon
11/7/23 3:37 PM
Library Comment
BMC 38.320.030.E. Form and intensity standards elements. Roof Pitch and Height.
Please provide the roof pitch in feet to ensure conformance with the maximum 60
feet. 38 1 Planning
Nakeisha Lyon
11/7/23 3:38 PM
Library Comment
BMC 38.350.050. Setback and height encroachments, limitations, and exceptions.
No balcony, deck, or terrace that extends above the height of the ground floor level
may encroach into required setbacks. Please ensure this provision and any other
encroachments are demonstrated/met in the formal submittal.
39 1 Planning
Nakeisha Lyon
11/7/23 3:38 PM
Library Comment
BMC 38.350.060. Fences, walls, hedges. Please demonstrate conformance with this
provision if applicable for any on-site landscaping or screening mechanisms utilized
in this proposal.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
40 1 Planning
Nakeisha Lyon
11/7/23 3:39 PM
Comment
Division 38.380. Affordable Housing. Please consider the affordable housing
provisions within this section of the code for additional development incentives if
affordable housing may be created within this development project.
41 1 Planning
Nakeisha Lyon
11/7/23 3:41 PM
Library Comment
Sec. 38.400.100. Street vision triangle in related to parallel parking spaces. The
street vision triangle for the access into the parking lot along North 25th Avenue
appears to encroach into the rear of the last parallel parking space. This cannot
occur and this last space must be eliminated. Please demonstrate this in the formal
submittal. 42 1 Planning
Nakeisha Lyon
11/7/23 3:41 PM
Library Comment
Sec. 38.400.100.C. Street vision triangle. The street vision triangle appears to be
taken from different points at these intersections on different plans (i.e. landscape
and civil plan). Please ensure this provision is demonstrated consistently in the
formal submittal. 43 1 Planning
Nakeisha Lyon
11/7/23 3:46 PM
Library Comment
BMC 38.410.080.F. Stormwater facilities generally must not occupy more than one-
third of a required front setback. Departures will be considered (per section
38.250.060) for stormwater facilities with Low Impact Development (LID)
components, underground components, or exceptional design. Please ensure
conformance with this provision for the proposed facility along North 25th Avenue.
44 1 Planning
Nakeisha Lyon
11/7/23 3:46 PM
Library Comment
BMC 38.410.080.G. All finish grades in landscaped areas must comply with the
provisions set forth in section 38.550.050.L. Please demonstrate conformance with
this provision in the formal submittal. 45 1 Planning
Nakeisha Lyon
11/7/23 3:46 PM
Library Comment
BMC 38.410.080.H. Please demonstrate this standards regarding landscaping of
stormwater retention/detention facilities in landscaped areas as landscape
amenities if applicable. Please demonstrate conformance with this provision in the
formal submittal.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
46 1 Planning
Nakeisha Lyon
11/7/23 3:59 PM
Library Comment
BMC 38.510.030.I - Trail/park frontages. This frontage is applicable along Tschache
Lane. The following are the applicable comments Staff noticed are not
demonstrated within this informal submittal and must be during the formal
submittal. 1) Facade Transparency: Please demonstrate at least 15% of the entire
facade is transparent. 2) Weather Protection: If any primary residential entries are
along the north elevation, at least 3' in depth is required. 3) Parking Location:
Please provide a 10' minimum buffer of landscaping between the street and off
street parking areas meeting the performance standards of division 38.550. 4)
Landscaping: For setbacks adjacent to buildings with windows, provide low level
landscaping that maintains views between the building and the street. Also provide
plant materials that screen any blank walls and add visual interest at both the
pedestrian scale and motorist scale. For extended wall areas, provide for a diversity
of plant materials and textures to maintain visual interest from a pedestrian scale.47 1 Planning
Nakeisha Lyon
11/7/23 4:11 PM
Library Comment
BMC 38.510.030.D - Mixed block frontages. This block frontage is applicable to
North 27th Avenue, North 25th Avenue, and Breeze Lane. The following are the
applicable comments Staff noticed are not demonstrated within this informal
submittal and must be during the formal submittal. 1) Facade Transparency: Please
demonstrate at least 15% of the entire facade is transparent. 2) Weather Protection:
At least 3' in depth weather protection is required for any primary residential
entries. 3) Parking Location: Please provide a 10' minimum buffer of landscaping
between the street and off street parking areas meeting the performance standards
of division 38.550 along North 27th and North 25 Avenues. 4) Landscaping: For
setbacks adjacent to buildings with windows, provide low level landscaping that
maintains views between the building and the street. Also provide plant materials
that screen any blank walls and add visual interest at both the pedestrian scale and
motorist scale. For extended wall areas, provide for a diversity of plant materials
and textures to maintain visual interest from a pedestrian scale.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
48 1 Planning
Nakeisha Lyon
11/7/23 4:27 PM
Comment
A window sample either photographic evidence or physical to demonstrate
transparency is required prior to final building permit approval.49 1 Planning
Nakeisha Lyon
11/7/23 4:29 PM
Library Comment
BMC 38.510.030.J - Special residential block frontage standards along sidewalks
and internal pathways. Please demonstrate conformance with Sec. 38.510.030.J. for
special residential block frontage standards along sidewalks and internal pathways
for the ground floor living spaces along Breeze Lane and North 27th Avenue.
50 1 Planning
Nakeisha Lyon
11/7/23 4:30 PM
Library Comment
Sec. 38.520.040.C.3. Pedestrian paths through parking lots. Developments must
provide specially marked or paved sidewalks through parking areas. At least one
walkway must be provided every four rows of parking or at a maximum spacing of
200 feet. The pathways must provide a safe connection to the building entrance
and meet the pathway design standards set forth in subsection D. Please provide a
pedestrian pathway through the parking lot that breaks up this area in accordance
with this provision.51 1 Planning
Nakeisha Lyon
11/7/23 4:36 PM
Library Comment
BMC 38.520.070. - Location and design of service areas and mechanical equipment.
Please demonstrate conformance with this provision during the formal submittal, if
applicable.52 1 Planning
Nakeisha Lyon
11/7/23 4:36 PM
Library Comment
BMC 38.520.070. B.1.b. Ground level private outdoor space. Please ensure these
open spaces are enclosed by a fence and/or hedge at least 32 inches in height to
qualify as required open space. Please demonstrate conformance with this
provision during the formal submittal. 53 1 Planning
Nakeisha Lyon
11/7/23 4:36 PM
Library Comment
BMC 38.520.070. B.2. Please ensure that shared open space areas are separated
from ground level windows, streets, service areas and parking lots via landscaping,
fencing, and/or other acceptable treatments that enhance safety and privacy for
both the shared open space and dwelling units. Please demonstrate conformance
with this provision during the formal submittal.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
54 1 Planning
Nakeisha Lyon
11/7/23 4:36 PM
Library Comment
BMC 38.520.070. B.5. Shared rooftop decks. Please ensure this space integrates
landscaping elements that enhance the character of the space and encourage its
use, and incorporate features that provide for the safety of residents, such as
enclosures, railings, and appropriate lighting levels. Please demonstrate
conformance with this provision during the formal submittal.
55 1 Planning
Nakeisha Lyon
11/7/23 4:41 PM
Library Comment
BMC 38.530.040.E. - Building massing and articulation. Facade with. Please
demonstrate conformance with this section for the south faade design along
Breeze Lane during the formal submittal. 56 1 Planning
Nakeisha Lyon
11/7/23 4:41 PM
Library Comment
BMC 38.530.070 - Blank wall treatments. Please demonstrate conformance with this
provision during the formal submittal.
57 1 Planning
Nakeisha Lyon
11/7/23 4:46 PM
Library Comment
BMC 38.540.050.A.4&5. Bicycle parking standards. Please provide bicycle parking,
design, dimensions, etc, in conformance with these standards during the formal
submittal. 58 1 Planning
Nakeisha Lyon
11/7/23 4:47 PM
Library Comment
BMC 38.540.020.E. - Stall, aisle and driveway design. Parallel parking spaces. Parallel
parking spaces must be a minimum of 24 feet in length and seven feet in width
measured from the inside edge of a curb or the inside edge of the asphalt if
curbing is not present. Please demonstrate conformance with this provision during
the formal submittal. 59 1 Planning
Nakeisha Lyon
11/7/23 4:50 PM
Library Comment
BMC 38.550. - Landscaping. Please ensure all applicable components of this
Division are met in the formal submittal. This includes drought tolerant thresholds,
planting species, materials, symbols, names, locations, quantities, container or
caliper sizes, heights, spread and spaces, parking lot and street frontage tree
calculations, irrigation plans, etc.
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
60 1 Planning
Nakeisha Lyon
11/7/23 4:57 PM
Library Comment
BMC 38.560. Signs. Signage must be in conformance with Sec. 38.560.060.B. for the
R-5 zoning district. Signs are not approved as a component of the formal site plan
application. A separate sign and building permit is required. The monument sign
appears to be proposed within an easement. Please be advised that any signage
approved within any easement is at risk for damage if work must be done in said
easement and this is at the cost of the property owner. 61 1 Planning
Nakeisha Lyon
11/7/23 4:57 PM
Library Comment
BMC 38.570. Lighting. Please provide a photometric plan, lighting specifications,
and other details and specifications in conformance with this Division if any on-site
lighting is proposed.
DISCUSSION STATUS
The developer is requesting a CILP for park dedication as the
site cannot readily provide land for park use and there is a
city park within 300 feet of the subject property.
Info Only
N/A Info Only
Management will bring dumpsters to the refuse pad from the
internal refuse room. There is no enclosure over the refuse
pad. We will heat it, and no parking allowed in front of it.
There is 57' clear in front of the pad to allow such approach.
Info Only
There will be no internal EV charging stations Info Only
N/A Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
REVIEW COMMENTS
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
N/A Info Only
Okay, we will include details in our building permit
submission.
Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Jamison spoke with Griffin about the possibility of Compass
putting the $83,328 CILWR fee in escrow with the city while
the project awaits a response from the DNRC. Compass
would request that this item could remain open during
construction in hopes that a well could be approved before
certificate of occupancy. Griffin suggested this may have to
be resolved prior to permit.
Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
Comment to be addressed in next stage.Info Only
This has been provided in the Site Plan submittal process.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Attachment C - Construction Route Map 24.04.18 Info Only
This will be addressed with the infrastructure submittal.Info Only
The will be addressed with infrastructure submittal.Info Only
Acknowledged Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Fire control room was added to the plans in the Site Plan
submittal. This is shown on Sheet A010 or A101.
Info Only
This will be included in the Site Plan Re-Submittal Package Info Only
38.420.020 A 1d.Land dedication or its equivalent must not
be required for any dwelling units or group quarters
occupancy in excess of the following:(2)For development
within the R-3, R-4, R-5, R-O, and REMU zoning districts, the
maximum net residential density must be 12 dwelling units
or 27 persons in group quarters per acre. Compass exceeds
12 units/acre therefore CILP is required.
Info Only
The developer is requesting a CILP for park dedication as the
site cannot readily provide land for park use and there is a
city park within 300 feet of the subject property.
Info Only
This is accurate.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Acknowledged.Info Only
Acknowledged.Info Only
This will be provided in the site plan submittal.Info Only
Roof pitch is provided for a section on A103, and on the
exterior elevations.
Info Only
There are no balconies, decks or terraces above ground level
that extend beyond the building setback.
Info Only
Fences are no more than 42" high. Landscape to comment
on hedges.
Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Owner to comment.Info Only
Street vision triangles updated in the site plan submittal.Info Only
Street vision triangles updated and coordinated in the site
plan submittal.
Info Only
Acknowleged.Info Only
Acknowledged.Info Only
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
1) Plans were updated in the site plan submittal to show
compliance with the 15% transparency requirements. See
calculations provided on A501. 2)All primary entrances have a
min. 3' overhang with canopies above. 3) N/A 4) N/A
Info Only
1) Plans were updated in the site plan submittal to show
compliance with the 15% transparency requirements. See
calculations provided on A501. 2)All primary entrances have a
min. 3' overhang with canopies above. 3) N/A 4) N/A
Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Attachment A - Window Transparency Example Info Only
Comment to be addressed in next stage.Info Only
There are only three rows of parking, and the maximum
travel distance from any stall to the nearest sidewalk is 85';
therefore a sidewalk through the parking lot is not requried.
Info Only
See A101 and A50X for exterior mechanical louvers, and
switch gear location. A010 for transformer location, and
landscape plan for screening locations.
Info Only
A 42" high fence will be provided at private ground level
outdoor spaces.
Info Only
Shared open spaces are separated from gound level windows
with fencing and landscaping. See A010 and L1.0.
Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
See A011 for an enlarged plan of the rooftop patio which
shows landscape planters integrated on the space. The
exterior railing will be code minimum 42" high for safety of
the residents, and the electrical plans will provide code
minimum exit lighting. That exit lighting plan will be provided
in the Building Permit Submittal.
Info Only
See Attachement B - South Elevation Facade Articulation to
demonstrate compliance with building mass articulation.
Info Only
There are no blank walls that are over 15' long and 10' high.
The use of windows on all floors have been utilized to meet
this requirement. The longest span we have is 14'-5" on the
north side on ground level. See Elevation "B".
Info Only
Civil to comment.Info Only
See Sheet A010 for dimensions on parallel parking spaces to
confirm compliance.
Info Only
Comment to be addressed in next stage.Info Only
Plan Review - Review Comments Report
Project Name: 23303 Palisades Multi Family INF
Workflow Started: 9/27/2023 9:11:51 AM
Report Generated: 06/21/2024 09:38 AM
Monument sign has been relocated on Sheet A010 to be off
the utility easement. See generic sign design on A010, but
the General Contractor will pull a separate permit at a later
date.
Info Only
See E1.1 Lighting Plan provided in the Site Plan submittal.Info Only