HomeMy WebLinkAbout049_ES001_ElectricalDetails25' AFG
MAST ARM
4'
SINGLE
MEMBER
TYPE MASTARM
30" BASE
FINISHED
GRADE
BASE SIZE
SEE SCHED.2'-6"HEIGHT AFGSEE SCHED.DEPTH *** - SEE SCHED.
CONCRETE BASE SCHEDULE **
POLE HT.BASE
SIZE
VERT.
REINF.
TRANSVERSE
REINF.**
DEPTH
***
HEIGHT
AFG
14' TO 30'24" RND.(6) #6 *#3@8" O.C.7'-0" 2'-6"
ANCHOR BOLTS
FROM POLE MANF.
NOTE:
TRANSVERSE REINF.
SEE SCHEDULE
HANDHOLE - 4" X 6" (NOMINAL)
THWN CONDUCTOR AS SHOWN ON PLANS
PROVIDE 1' OF COILED SLACK ON
CONDUCTOR FEED THRU
PROJECT ANCHOR BOLTS 3" MIN. ABOVE TOP
OF BASE. PROVIDE DOUBLE NUTS FOR
LEVELING UNIT (ONE ABOVE AND ONE BELOW
BASE FLANGE). PROVIDE NON-SHRINK GROUT
IN VOID BETWEEN BASE FLANGE AND TOP OF
CONCRETE, LEAVING DRAIN HOLE. HAND FINISH.
CONNECT GROUND TO POLE
BASE W/ BOUNDARY #GB4C
PROVIDE FUSE(S) IN CKT. TO
BALLAST. FUSE(S) SHALL BE
BUSS TYP. BBS. FUSE
HOLDERS SHALL BE BUSS
"TRON" HEB WATERPROOF.
SIZE OF FUSE SHALL BE AS
REQUIRED BY LUMINAIRE
MANUFACTURER.
BASE COVER
BUSH CONDUITS
REINFORCED CONC.
PIER FOOTING BY
ELECTRICAL
CONTRACTOR
1" CHAMFER
SEE SITE PLAN
FOR CONDUIT
SIZE
FINISH GRADE. BACKFILL &
COMPACT AS RECOMMENDED BY
GEOTECHNICAL ENGINEER
VERT. REINF.
SEE SCHEDULE
NOTE:
• CONTRACTOR SHALL GRIND EXPOSED CONCRETE SMOOTH AS REQUIRED TO REMOVE
ANY FORMWORK MARKINGS.
* SPACE VERTICAL BARS EVENLY AROUND PERIMETER.
** PROVIDE REINF. CLEARANCE AND COVER PER ACI 318.
Date
Project Number
Sheet Name
ALL DRAWN AND WRITTEN INFORMATION
APPEARING SHALL NOT BE DUPLICATED,
DISCLOSED OR OTHERWISE USED
WITHOUT THE WRITTEN CONSENT OF
45 ARCHITECTURE
NOT FOR
CONSTRUCTION
REVISIONS
MARK DESCRIPTION DATE
ES001
ELECTRICAL DETAILSSIMKINS-HALLIN TRACT 3-B01.31.2024
6088.013WHEAT DRIVEBOZEMAN, MTSITE PLAN SUBMITTAL
LUMINAIRE SCHEDULE
TYPE LAMPS
LOAD
(W)
OUTPUT
(LM, NOMINAL)
CCT
(K)DESCRIPTION MFR CATALOG NO. OR SERIES MOUNTING VOLTAGE NOTES
E1 LED 24 W 2,900 4000K EXTERIOR WALL PACK WITH BATTERY PACK FOR EGRESS
DOORS
LITHONIA WPX1LEDP2-40K-MVOLT-E14WC-DDBXD WALL 120 V
E2 LED 47 W 6,000 4000K EXTERIOR WALL PACK WITH BATTERY PACK FOR GARAGE
DOORS/SITE LIGHTING
LITHONIA WPX2LED-40K-MVOLT-E14WC-DDBXD WALL 120 V
P1 LED 181 W 24,272 2700K SINGLE-HEAD POLE-MOUNT SITE LIGHT, TYPE 4 LITHONIA DSX2-P2-27K-80CRI-T4M-MVOLT-RPA-D
DBXD
25' ROUND
POLE
277 V 6
1. PRIOR SUBMITTAL NOT REQUIRED. ALL ALTERNATE FIXTURE SHOP DRAWINGS WILL BE REVIEWED AFTER THE
PROJECT IS AWARDED.
2. PRIOR SUBMITTAL IS REQUIRED.
3. ALTERNATE FIXTURE IS NOT ACCEPTED FOR SUBSTITUTIONS.
4. PROVIDE 0-10V DIMMING, DOWN TO 10% LUMEN OUTPUT, MINIMUM.
5. PROVIDE FUSING.
6. VERIFY FINISH WITH ARCHITECT.
7. PROVIDE WITH REMOTE 12V STEP-DOWN TRANSFORMER.
8. CIRCUIT VIA TYPE EM INVERTER.
9. LAMP DATA IS FOR 4' CROSS-SECTION OF FIXTURE.
10.MOUNT BOTTOM OF FIXTURE CENTERED AT 6” ABOVE TOP OF MIRROR. SEE ARCHITECT ELEVATIONS.
THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL CEILING TYPES AND PROVIDE ALL MOUNTING, FIRE-RATED, AND
IC-RATED ACCESSORIES AS REQUIRED. FOR FIRE-RATED CEILING ASSEMBLIES AND FOR CEILINGS WITH
INSULATION, VERIFY ALL RECESSED LUMINAIRE HOUSINGS ARE RATED APPROPRIATELY OR PROVIDE DROP-OVER
ENCLOSURES OR TENTS FOR LUMINAIRES. VERIFY THAT DROP-OVER ENCLOSURES OR TENTS ALLOW FOR AIR
SPACE AROUND LUMINAIRE PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:GENERAL NOTE:
N.T.S.2 POLE LIGHT HEIGHT DETAIL -EXTENDED MAST ARM
N.T.S.1 POLE LIGHT BASE DETAIL