HomeMy WebLinkAbout009 C600 UTILITY DETAILSNEW PVC PIPE AS NOTED ON PLANS NEW FOUR INCH (4") SCH. 40 PVC ROOF DRAIN LEADER @ 1/4" PER FOOT SLOPE (MIN) OR AS INDICATED PER PLAN NEW TEE-WYE FITTING (AS REQUIRED) FOR CONNECTION TO ROOF DRAIN LATERAL LINE NOTE: VERIFY PLAN BURY DEPTH IN THE FIELD, INSURING EIGHTEEN INCHES (18") OF MINIMUM COVER 1/4" BELOW TOP OF NEW PAVEMENT SURFACE 3'-0" (MIN) HEAVY DUTY MONUMENT BOX, SIMILAR TO CAIRD ENG. NO. 50608-1 PAVING & GRAVEL AS REQUIRED SEAL JOINT WITH RAM-NEK 8" x 3' ROUND CONCRETE SLAB SLIP HUB TO THREADED ADAPTER THREADED PLUGFROST EXPANSION SLEEVE CLEANOUT PIPE - 4" Ø PVC 45° BEND NON-SHRINK BACKFILL END OF TRENCH VERIFY PIPE SIZE PER PLAN DIMENSIONS END OF LINE CLEANOUT (IF REQUIRED) USE PLUG 1' MIN TO 2' MAX ABOVE FINISHED FLOOR FLANGE TO BE THREADED ON STANDPIPE, MJ TO FLANGE ADAPTERS NOT ACCEPTABLE (TYPICAL FOR ALL RISER CONFIGURATIONS) 3/4" MIN. REDI ROD, INSTALLED IN EVERY OTHER AVAILABLE MJ BOLT HOLES (TYP) - 5/8" RODS ACCEPTABLE FOR 4" LINES FLOOR BACKFLOW PREVENTION ASSEMBLY REQUIRED BACKFLOW PREVENTION DEVICE TO BE DETERMINED BY WATER SUPERINTENDENT METER SIZED SAME AS INCOMING LINE, NO EXCEPTIONS 4" OR LARGER CLASS 51 DUCTILE IRON PIPE (TYP) MECHANICAL JOINTMAIN TAPPING TEE & VALVE, OR INSTALL VALVE AT PROPERTY LINE (TYPICAL FOR ALL RISER CONFIGURATIONS) THRUST BLOCK NO PRESSURE GAUGES OR PRESSURE GAUGE FITTINGS WILL BE ALLOWED ON THE TEST PORTS OF ANY BACKFLOW PREVENTION ASSEMBLY. ***A MINIMUM OF FOUR (4) PIPE DIAMETERS OF STRAIGHT RUN PIPE IS REQUIRED UPSTREAM AND DOWNSTREAM OF THE METER / STRAINER ASSEMBLY 90° BEND WITH THRUST BLOCK FLANGED OS&Y VALVE 1' MIN TO 2' MAX ABOVE FINISHED FLOOR FLANGED OS&Y VALVE PROVIDE FLEXIBLE, WATER-TIGHT CONNECTION FOR ALL WALL OR FLOOR PIPE PENETRATIONS. MECHANICAL JOINT 90° BEND WITH THRUST BLOCK FLOOR FLANGED OS&Y VALVE 1' MIN TO 2' MAX 2' MIN TO 3' MAX CLEARANCE ABOVE FINISHED FLOOR COATED STEEL WALL PLATE, 5/16" MINIMUM THICKNESS CITY OF BOZEMAN REQUIREMENTS FOR INSTALLATION OF BACKFLOW PREVENTION ASSEMBLY 1.THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL LISTED FLANGED KENNEDY OR MUELLER OS&Y VALVE THE SAME SIZE AS THE SERVICE LINE. COMBINATION STRAINER / METER IMMEDIATELY FOLLOWING OS&Y VALVE - METER MUST SET HORIZONTAL. 2.ALL BACKFLOW PREVENTION ASSEMBLIES SHALL BE: A.UL OR FM LISTED. B.APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC RESEARCH (USCFCCCHR) FOR OPERATION IN THE PROPOSED POSITION (VERTICAL OR HORIZONTAL) AS SHOWN ON APPROVED PLANS. C.INSTALLED AS SHOWN ON THE APPROVED PLANS. 3.HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF TWO FEET (2') AND MAXIMUM OF THREE FEET (3') ABOVE THE FINISHED FLOOR. 4.THE SERVICE RISER MUST BE A MINIMUM OF TWO FEET (2') FROM ANY OUTSIDE WALL. 5.THE INCOMING SERVICE LINE SHALL BE A MINIMUM OF 6.5' AND A MAXIMUM OF 7.5' BELOW THE FINISHED GRADE. 6.ALL SERVICE LINE APPURTENANCES SHALL HAVE A MINIMUM PRESSURE RATING OF 175 PSI. 7.ALL SERVICE LINES FOUR INCHES (4") AND LARGER SHALL BE CLASS 51 DUCTILE IRON PIPE. 8.LINE SIZING: THE BACKFLOW PREVENTION ASSEMBLY AND METER SHALL BE EQUAL IN SIZE TO BOTH THE INCOMING PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE DIAMETER (DOWNSTREAM). FOR EXAMPLE, A FOUR INCH (4") SERVICE LINE SHALL HAVE A FOUR INCH (4") METER AND BACKFLOW PREVENTION ASSEMBLY. 9.A MINIMUM OF FOUR (4) PIPE DIAMETERS OF STRAIGHT RUN PIPE IS REQUIRED UPSTREAM AND DOWNSTREAM OF THE METER / STRAINER ASSEMBLY. VERIFY SCALE! THESE PRINTS MAY BE REDUCED. LINE BELOW MEASURES ONE INCH ON ORIGINAL DRAWING. MODIFY SCALE ACCORDINGLY! 2024COPYRIGHT © MORRISON-MAIERLE, INC., SHEET NUMBER PROJECT NUMBER DRAWING NUMBER DATEDESCRIPTIONNO.BY N:\5659\022 - NWX LOT 11 SITE PLAN\ACAD\SHEETS\C600 SITE DETAILS.DWGREVISIONS DRAWN BY: DSGN. BY: APPR. BY: DATE: Q.C. REVIEW DATE: BY: 2880 Technology Blvd West Bozeman, MT 59718 406.587.0721 www.m-m.net engineers surveyors planners scientists MorrisonMaierle PLOTTED BY:CELINE SAUCIER ON Jul/10/2024 NWX CHIPOTLE 1438 DAYSPRING AVENUE, BOZEMAN MT 59718 BOZEMAN MONTANA UTILITY DETAILS 5659.022 9 C600 CGD CMS MEE 5/31/2024   1 SANITARY SEWER & STORM DRAIN CLEANOUT DETAIL NOT TO SCALE 2 ROOF DRAIN DOWNSPOUT CONNECTION NOT TO SCALE 3 WATER SERVICE DETAIL FOR SERVICE 4" AND LARGER NOT TO SCALE No. 49499 CELINE M PR O FESSIONAL E N G INEERM O N TANA LICENSE D SAUCIER