Loading...
HomeMy WebLinkAbout009 Sewer Peak Hourly Demand LetterPage | 1 SE Engineers PO Box 10776 Bozeman, MT 59718 01/11/24 Dairy Queen Sewer Peak Hourly & Hourly Domestic Water Demands The Peak Hourly Demand (PHD) is calculated as follows: • Building Average Daily Demand (Qave) o Restaurant, Full Service = 40 Gallon / Seat (ref: 15A NCAC 02T.0114 Wastewater Design Flow Rates - see attached) ▪ Total Seats = 44 ▪ Qave = 44 seats. x (40 gal / seat) ▪ Qave = = 1,760 gallon per day • Peaking Factor (Qmax/Qave) = (18 + P1/2) / (4 + P½) (ref: Design Standards and Specifications Policy; City of Bozeman March 2004) o P = Population in thousands o P = 44 occupants = 0.044 Thousand of People o Qmax = ((18 + 0.209) / (4 + 0.209)) x 1,760 o Qmax = 4.33 x 1,760 o Qmax = 7,614 gal/ day Hourly domestic water demand is based off attached spreadsheet: Hourly domestic water demand = 13.0 GPM (from spreadsheet) x 60 min/ hour Hourly domestic water demand = 780 GPH SE Engineers Bill Edden, PE Owner, Mechanical Engineer Project Name:Dairy Date 1/11/2024 SE Engineers PO Box 1491 Three Forks, MT 59752 406-600-8796 Flush Valve = 0, Flush Tank = X X Static Pressure in Main (PSI)80 Elevation Rise (FT)26 Meter Loss (PSI)7 Backflow Preventor Loss (PSI) 8 Minimum Available Water Pressure (PSI) 53.82 Minimum Required Fixture Pressure (PSI) 15 Maximum Length 250 Developed Length Factor 1.5 Total Developed Length 375 Fixture Qty FU Total FU Sink 2 2 4 Clothes Washer 0 4 0 Dishwasher (Domestic)0 1.5 0 Drinking Fountain 0 0.5 0 Drinking Fountain Assembly 0 0.75 0 One Hose Bibb 1 2.5 2.5 Each Additional Hose Bibb 1 1 1 Kitchen Sink (domestic)0 1.5 0 Hair wash sink 0 3 0 Lavatory 4 1 4 Mop Basin 1 3 3 Bath/ Shower 0 4 0 Tire Wash 0 5 0 Urinal Public (1.0 GPF)0 4 0 Urinal Assembly (1.0 GPF) 0 5 0 Water Closet Public (1.6 GPF gravity) 2 2.5 5 Water Closet Public (1.6 GPF Flushometer tank) 0 2.5 0 Water Closet Public (1.6 GPF Flushometer valve) 0 5 0 Water Closet Assembly (1.6 GPF gravity) 0 3.5 0 Water Closet Assembly (1.6 GPF Flushometer tank) 0 3.5 0 Water Closet Assembly (1.6 GPF Flushometer valve)0 6 0 19.5 13 2.9813333 1 5.05 4.15 Water Flow Velocity (FPS) Calculated Main Friction Loss (PSI/100ft) Project Information Total Water Demand Total FU Total GPM Allowable Friction Loss Per 100 Feet (PSI) Water Main Sizing (Input By User)