PREPARED FOR :PROJECT NUMBER:PROJECT ARCHITECT :
ISSUE DATES:CITY VINEYARD T.I.
2825 WEST MAIN STREET, BOZEMAN, MT 59718
BECKY RENO JEFF KANNING 2327
REV0 PERMIT SET
10/4/2023 - REV0 PERMIT SET
-
-
-
-
2023 G011
FIRE & LIFE SAFETY
PLAN
- C O L L A B O R A T I V ED E S I G N A R C H I T E C T S2327 - CITY VINEYARD T.I.2280 GRANT ROAD, SUITE C BILLINGS, MT 59102 406.248.3443www.cd-mt.comA R C H I T E C T S
THESE DOCUMENTS, IN PART OR IN WHOLE, AND THEDESIGN THEY REPRESENT ARE THE SOLE PROPERTY OFCOLLABORATIVE DESIGN ARCHITECTS. THESEDOCUMENTS ARE INTENDED FOR THE PROJECT ON THESITE INDICATED. ANY USE, REPRODUCTION,MODIFICATION OR ADAPTATION WITHOUT THE EXPRESSWRITTEN CONSENT OF COLLABORATIVE DESIGNARCHITECTS IS STRICTLY PROHIBITED.
FIRE & LIFE SAFETY
GENERAL NOTES
1. BUILDING IS SPRINKLERED THROUGHOUT
2. PROVIDE INTERIOR WALL AND CEILING FINISHES PER THE FOLLOWING
REQUIREMENTS:
A. ROOMS/ENCLOSED SPACES: CLASS C FLAME SPREAD
B. INTERIOR EXIT STAIRWAYS/EXIT PASSAGEWAYS: CLASS B FLAME
SPREAD
C. CORRIDORS/ENCLOSURE FOR EXIT ACCESS STAIRWAYS: CLASS B
FLAME SPREAD
FIRE & LIFE SAFETY LEGEND
ROOM TAG
OCCUPANT LOAD NUMBER EXITING SPACE
BUILDING EXIT
Room Name
Room No.
-- SF3001
15
EXIT
ROOM NAME
ROOM NUMBER
ROOM AREA
OCCUPANT LOAD FACTOR
ROOM OCCUPANCY LOAD 4'-11/2"FEC
FEC
RETAIL
110
1,334 SF
60
23 EXISTING
MALL
102
3,170 SF
300
11
EXISTING
R.R.
103
65 SF
0
0
EXISTING
R.R.
104
65 SF
0
0
EXISTING
EXTERIOR
PATIO
485 SF
15
33
WORK
ROOM
111
842 SF
300
3
33
25
TOTAL TENANT
OCCUPANTS = 149
P.O.E. 95'-11"P.O.E. 80'-5"
32 x .2" = 7" REQ'D
34" PROVIDED
14'-0"
AREA NOT IN SCOPE
AREA NOT IN SCOPE
ES-1
ES-2
ES-1
ES-2
ES-1
HALL
105
67 SF
0
0
OFFICE
106
100 SF
150
1
WALK
IN
COOLER
107
76 SF
300
1
BAR
105
317 SF
200
2
EXISTING
VESTIBULE
100
276 SF
0
0
EXISTING
UTILITY
101
343 SF
300
2
LOUNGE
105
1,295 SF
15
87
VERIFY ROUGH OPENING24" A.F.F.SECTION PLAN
NOTE: OBJECTS PROJECTING FROM WALLS WITH THEIR
LEADING EDGES BETWEEN 21" AND 80" ABOVE THE FINISH
FLOOR SHALL PROTRUDE NO MORE THAN 4" INTO WALKS,
HALLS, CORRIDORS, PASSAGEWAYS OR AISLES.
SEMI-RECESSED MTL FIRE
EXTINGUISHER CABINET W/
RADIUSED CORNERS
FIRE EXTINGUISHER
WALL PER
PLAN/ASSEMBLY
TYPES FIRE EXTINGUISHER
SEMI-RECESSED FIRE
EXTINGUISHER CABINET
WALL PER PLAN/ASSEMBLY
TYPES
1
G011
FIRE & LIFE SAFETY PLAN
1/8" = 1'-0"
2
G011
RECESSED FIRE EXTINGUISHER CABINET
1" = 1'-0"
BUILDING CODE ANALYSIS
TI AREA: 4,039 SF
OCCUPANCY GROUP: MERCANTILE (M) & ASSEMBLY (A-2)
CONSTRUCTION TYPE: III-B
SPRINKLERED: YES
APPLICABLE CODES:
BUILDING CODE: 2021 IBC
MECHANICAL CODE: 2021 IMC
PLUMBING CODE: 2021 UPC
ELECTRICAL CODE: 2020 NEC
FIRE CODE: 2021 IFC
ENERGY CODE: 2021 IECC
ACCESSIBILITY CODE: 2017 ICC A117.1
BUILDING CODE SUMMARY:
CHAPTER 3 - OCCUPANCY:
MERCANTILE (M) & ASSEMBLY (A-2 )
CHAPTER 5 - GENERAL BUILDING HEIGHTS AND AREAS
TABLES 504.3, 504.4, 506.2:
M & A-2 OCCUPANCY, III-B, SPRINKLERED - NON-SEPARATED
CHAPTER 10 - MEANS OF EGRESS:
SECTION 1004 OCCUPANT LOAD
TABLE 1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
TOTAL TENANT OCCUPANTS = 149
SECTION 1005 MEANS OF EGRESS SIZING
1005.3.2 OTHER EGRESS COMPONENTS: THE CAPACITY, IN INCHES, OF MEANS OF EGRESS
COMPONENTS OTHER THAN STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE
OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF EGRESS CAPACTIY
FACTOR OF 0.2 INCH (5.1 MM) PER OCCUPANT.
APPLICATION: EXIT DOORS
MINIMUM PROVIDED: 32 INCHES MINIMUM PER 1008.1.1
SECTION 1006 NUMBER OF EXITS AND EXIT ACCESS DOORWAYS
1006.2 EGRESS FROM SPACES: ROOMS, AREAS OR SPACES, INCLUDING MEZZANINES, WITHIN
A STORY OR BASEMENT SHALL BE PROVIDED WITH THE NUMBER OF EXITS OR ACCESS
TO EXITS IN ACCORDANCE WITH THIS SECTION.
APPLICATION: M OCCUPANCY, WITH SPRINKLER - 75’ MAX ALLOWED
TWO EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE
THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL DISTANCE
EXCEEDS THE VALUES LISTED IN TABLE 1006.2.1
APPLICATION: M OCCUPANCY - MAXIMUM OCCUPANT LOAD OF 49 ALLOWED FOR ONE EXIT
FROM SPACE
SECTION 1008 MEANS OF EGRESS ILLUMINATION
1008.3 EMERGENCY POWER FOR ILLUMINATION: THE POWER SUPPLY FOR MEANS OF
EGRESS ILLUMINATION SHALL NORMALLY BE PROVIDED BY THE PREMISES’ ELECTRICAL
SUPPLY.
1008.3.2 BUILDINGS: IN THE EVENT OF POWER SUPPLY FAILURE IN BUILDINGS THAT REQUIRE
TWO OR MORE EXITS OR ACCESS TO EXITS, AN EMERGENCY ELECTRICAL SYSTEM
SHALL AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING AREAS:
1. INTERIOR EXIT ACCESS STAIRWAY AND RAMPS
2. INTERIOR AND EXTERIOR EXIT STAIRWAYS AND RAMPS
3. EXIT PASSAGEWAYS
4. VESTIBULES AND AREAS ON THE LEVEL OF DISCHARGE USED FOR EXIT DISCHARGE IN
ACCORDANCE WITH SECTION 1028.1.
5. EXTERIOR LANDINGS AS REQUIRED BY SECTION 1010.1.5 FOR EXIT DOORWAYS THAT LEAD
DIRECTLY TO THE EXIT DISCHARGE.
1010.2.4 LOCKS AND LATCHES:
LOCKS AND LATCHES SHALL BE PERMITTED TO PREVENT OPERATION OF DOORS WHERE
ANY OF THE FOLLOWING EXIST:
3. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT LOAD OF 300 OR LESS,
GROUPS B, F, M AND S, AND IN PLACES OF RELIGIOUS WORSHIP, THE MAIN DOOR OR
DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED LOCKING DEVICES
FROM THE EGRESS SIDE PROVIDED:
3.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS LOCKED
3.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE EGRESS SIDE ON OR ADJACENT
TO THE DOOR STATING: “THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS
OCCUPIED”. THE SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A CONTRASTING
BACKGROUND.
3.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS REVOCABLE BY THE BUILDING
OFFICIAL FOR DUE CAUSE.
SECTION 1017 EXIT ACCESS TRAVEL DISTANCE
1017.2 LIMITATIONS: EXIT ACCESS TRAVEL DISTANCE SHALL NOT EXCEED THE VALUES
GIVEN IN TABLE 1017.2
APPLICATION: M & A-2 OCCUPANCY
WITH SPRINKLER SYSTEM, 250' MAX ALLOWED
CHAPTER 11 - ACCESSIBILITY
1112 SIGNAGE
1112.1 SIGNS:
REQUIRED ACCESSIBLE ELEMENTS SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL
OF ACCESSIBILITY AT THE FOLLOWING LOCATIONS.
APPLICATION: EXIT DOORS, STAIRS, ELEVATORS, UTILITY ROOMS
1112.3 DIRECTIONAL SIGNAGE:
DIRECTIONAL SIGNAGE INDICATING THE ROUTE TO THE NEAREST LIKE ACCESSIBLE ELEMNT
SHALL BE PROVIDED AT THE FOLLOWING LOCATIONS. THESE DIRECTIONAL SIGNS
SHALL INCLUDE THE INTERNATIONAL SYMBOL OF ACCESSIBILITY AND SIGN
CHARACTERS SHALL MEET THE VISUAL CHARACTER REQUIREMENTS IN ACCORDANCE
WITH ICC A117.1.
APPLICATION: SEE CODE PLAN FOR SIGN LOCATIONS
CHAPTER 13 - ENERGY EFFICIENCY
1301.1.1 CRITERIA: BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
WITH THE INTERNATIONAL ENERGY CONSERVATION CODE.
CHAPTER 4 - COMMERCIAL ENERGY EFFICIENCY (IECC)
CLIMATE ZONE 6
BUILDING ENVELOPE REQUIREMENTS
SEE DRAWINGS FOR ENVELOPE ALTERATIONS AND REQUIREMENTS
CHAPTER 29 - PLUMBING SYSTEMS
2902.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES SHALL BE PROVIDED IN THE
MINIMUM NUMBER AS SHOWN IN TABLE 2902.1 BASED ON THE ACTUAL USE OF THE
BUILDING OR SPACE. USES NOT SHOWN IN TABLE 2902.1 SHALL BE CONSIDERED
INDIVIDUALLY BY THE CODE OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE
DETERMINED BY THIS CODE.
2902.1.1 FIXTURE CALCULATIONS. TO DETERMINE THE OCCUPANT LOAD OF EACH SEX,
THE TOTAL OCCUPANT LOAD SHALL BE DIVIDED IN HALF. TO DETERMINE THE
REQUIRED NUMBER OF FIXTURES, THE FIXTURE RATIO OR RATIOS FOR EACH
FIXTURE TYPE SHALL BE APPLIED TO THE OCCUPANT LOAD OF EACH SEX IN
ACCORDANCE WITH TABLE 2902.1. FRACTIONAL NUMBERS RESULTING FROM
APPLYING THE FIXTURE RATIOS OF TABLE 2902.1 SHALL BE ROUNDED UP TO THE
NEXT WHOLE NUMBER. FOR CALCULATIONS INVOLVING MULTIPLE OCCUPANCIES,
SUCH FRACTIONAL NUMBERS FOR EACH OCCUPANCY SHALL FIRST BE SUMMED AND
THEN ROUNDED UP TO THE NEXT WHOLE NUMBER.
USE TI OCCS MALES FEMALES
149 TOTAL OCCS
M - MERCANTILE 60 OCCS 30 30
REQUIRED FIXTURES: 1 WC / 500 .06 .06
REQUIRED FIXTURES: 1 LAVS / 750 .04 .04
A - RESTAURANT 89 OCCS 44 45
REQUIRED FIXTURES: 1 WC / 75 .6 .6
REQUIRED FIXTURES: 1 LAVS / 200 .2 .2
PROVIDED WATER CLOSETS: 1 1
PROVIDED LAVATORIES: 1 1
NOTES:
SIGNAGE LEGEND
SYMBOL
*TACTILE "EXIT" SIGN
DESCRIPTION
ILLUMINATED VISUAL "EXIT" SIGN
FEC FIRE EXTINGUISHER CABINET. T.O.EXTINGUISHER IS LESS THAN 60" A.F.F.
ROOM #LOCATION
FIRE EXTINGUISHER SCHEDULE SUMMARY
CABINET & MODEL
7023-A, 2A10BC
ES-1
ES-2
LOCATIONS TO BE VERIFIED BY INSPECTOR
BAR108
110 7023-A, 2A10BCRETAIL