MIN 6.5' COVER
(TYP.)STA 0+10.0216" X 8" TEEINV= 4586.85FG-EG-4595.720+00 FG-4596.70EG-4596.43FG-4597.00EG-4595.970+81
STA 0+12.14
8" GATE VALVE
INV= 4586.86
STA 0+71.89
90° VERT. BEND W/
THRUST BLOCK
INV= 4589.31
F
F
TV
TV
TV
TV
EEDYH
DYH DYH
I
I
D D
D
D S
D
S
D
D
D
S
P
P
P
WV
WVWV
WVWV WV
WVWV WV
BP BP BP BP BP
NG NG NG NG
S S SDSDSDSDSD SD
BP BP BP BP BP BPBPBPBPBPBTBTBTBTBTBTBTSD S
W W W W
XX
SD
SD
SD SD SD SDSD
12
S
D
15SDF
F
TV
TV
TV
TV
EE DY H
DYH DYH
I
I
D D
D
D S
D
S
D
D
D
S
P
P
P
WV
WV WV
WV WVWV
WVWV WV
BP BP BP BP
BP
NG NG NG NG
S S SD SDSD SD SD SD
BP BP BP BP BP BP BP BPBPBPBT BT BT BT BTBT BTSD S
W W W W
XX
1' MIN TO 2' MAX
ABOVE FINISHED FLOOR
FLANGE TO BE THREADED ON STANDPIPE,
MJ TO FLANGE ADAPTERS NOT ACCEPTABLE
(TYPICAL FOR ALL RISER CONFIGURATIONS)
3/4" MIN. REDI ROD, INSTALLED IN EVERY OTHER
AVAILABLE MJ BOLT HOLES (TYP) -
5/8" RODS ACCEPTABLE FOR 4" LINES
FLOOR
4" OR LARGER CLASS 51
DUCTILE IRON PIPE (TYP)
MECHANICAL
JOINTMAIN
TAPPING TEE & VALVE, OR
INSTALL VALVE AT PROPERTY
LINE (TYPICAL FOR ALL
RISER CONFIGURATIONS)
THRUST
BLOCK
90° BEND WITH THRUST BLOCK
FLANGED
OS&Y
VALVE
1' MIN TO 2' MAX
ABOVE FINISHED FLOOR
FLANGED
OS&Y
VALVE
PROVIDE FLEXIBLE,
WATER-TIGHT CONNECTION
FOR ALL WALL OR FLOOR
PIPE PENETRATIONS.
MECHANICAL JOINT
90° BEND WITH
THRUST BLOCK
FLOOR
FLANGED
OS&Y VALVE
1' MIN TO 2' MAX
2' MIN TO 3' MAX
CLEARANCE ABOVE
FINISHED FLOOR
COATED STEEL
WALL PLATE,
5/16" MINIMUM
THICKNESS
CITY OF BOZEMAN REQUIREMENTS
FOR INSTALLATION OF
DOUBLE CHECK VALVE ASSEMBLY
1. THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL LISTED FLANGED
KENNEDY OR MUELLER OS&Y VALVE THE SAME SIZE AS THE FIRE SERVICE
LINE.
2. ALL DOUBLE CHECK VALVE ASSEMBLIES SHALL BE:
A. UL OR FM LISTED.
B. APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION
FOR CROSS CONNECTION CONTROL AND HYDRAULIC RESEARCH
(USCFCCCHR) FOR OPERATION IN THE PROPOSED POSITION (VERTICAL
OR HORIZONTAL) AS SHOWN ON APPROVED PLANS.
C. INSTALLED AS SHOWN ON THE APPROVED PLANS.
3. A FLOW DETECTION DEVICE SHALL BE INSTALLED IMMEDIATELY FOLLOWING
THE DOUBLE CHECK VALVE ASSEMBLY (ALARM CHECK VALVE, FLOW
SENSOR/ALARM, METER, ETC.) AS SHOWN ON THE APPROVED PLANS.
PADDLE-TYPE FLOW ALARMS NOT PERMITTED ON DRY SYSTEMS.
4. A DOUBLE DETECTOR CHECK VALVE ASSEMBLY MAY BE USED WITH A
STANDARD CITY OF BOZEMAN METER. THE METER LOOP OF THE DOUBLE
DETECTOR ASSEMBLY SHALL HAVE A DOUBLE CHECK VALVE ASSEMBLY
INSTALLED WHICH MEETS THE SAME INSTALLATION CRITERIA SPECIFIED
ABOVE IN REQUIREMENT NUMBER TWO.
5. HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF TWO FEET (2') ABOVE
THE FINISHED FLOOR.
6. THE FIRE SERVICE RISER MUST BE A MINIMUM OF TWO FEET (2') FROM ANY
OUTSIDE WALL.
7. THE INCOMING FIRE SERVICE LINE SHALL BE A MINIMUM OF 6.5' AND A
MAXIMUM OF 7.5' BELOW THE FINISHED GRADE.
8. ALL FIRE SERVICE LINE APPURTENANCES SHALL HAVE A MINIMUM PRESSURE
RATING OF 175 PSI.
9. ALL FIRE SERVICE LINES FOUR INCHES (4") AND LARGER SHALL BE CLASS 51
DUCTILE IRON PIPE.
10. LINE SIZING: THE DOUBLE CHECK VALVE ASSEMBLY SHALL BE EQUAL IN SIZE
TO BOTH THE INCOMING PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE
DIAMETER (DOWNSTREAM).
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
NO PRESSURE GAUGES OR PRESSURE GAUGE
FITTINGS WILL BE ALLOWED ON THE TEST PORTS
OF ANY BACKFLOW PREVENTION ASSEMBLY.
ONLY FITTINGS ALLOWED BETWEEN
FIRST OS&Y VALVE AND BACKFLOW
ASSEMBLY TO BE 90° BEND
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
DOUBLE CHECK VALVE
(MIN. REQUIREMENT)
AS INDICATED ON
APPROVED PLAN(S)
10'-0" MAX*
MECHANICAL
JOINTOUTSIDE WALL*PER NFPA-24
FIG A.10.6.3.1
WALL213.19'FTVTVEEDYH
IIDPPWVWVWVWVBPBPBPBPBPBPBPBPNGNGNGNGNGSDBPBPBPBPBPBPBP
BPBP BP BP BP BP BP BP
BT BT BT BT BT BT BT BT BT BTWWWW
W8W 8WWS WSF TVTVEE DYH
IID PPWVWV WVWVBPBP BPBP BPBPBPBP NGNG NGNGNGSDBP BPBP BPBPBPBP
BPBP
BP BP
BP BP BP
BP
BT BT BT BT BT BT BT BT BT BTW WW W W0+000+811
1
NOT TO SCALE
STANDARD FIRE SERVICE LINE INSTALLATION
FOR CLASS I, II, & III SYSTEMS 02660-13
GENERAL NOTES:
SCALE: 1" = 100'
OVERALL SITE PLAN VIEW
BRONKEN WAREHOUSE
FIRE SERVICE LINE
3345 PRINCE LN, LOT 5A, BLOCK 3 OF
NELSON MEADOWS SUBDIVISION
CITY OF BOZEMAN, GALLATIN COUNTY, MONTANA
ZONED: M-1
CLASS I SYSTEM
SYSTEM CLASSIFICATION:
ACCORDING TO THE NFPA 24, A FLOW RATE OF 1560 GALLONS PER MINUTE IS REQUIRED
FOR FLUSHING OF A 8-INCH FIRE SERVICE LINE. THEREFORE, THE INSTALLING CONTRACTOR
MUST PROVIDE AN ORIFICE SIZE OF AT LEAST 2 INCHES TO MEET THIS REQUIREMENT BASED
ON THE CURRENT PARAMETERS OF THE SYSTEM.
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING FLOW TEST DATA AND PREPARING
HYDRAULIC CALCULATIONS.
FLUSHING REQUIREMENTS:
X
X 8" FIRE SERVICE
2" DOMESTIC WATER SERVICE
STATIONING FOLLOWS CENTERLINE OF PROPOSED FIRE SERVICE LINE.
CENTERLINE OF 2" DOMESTIC WATER IS OFFSET 2.0' (CENTER TO
CENTER) TO THE EAST OF THE FIRE SERVICE LINE. INSTALL BOTH
UTILITIES IN THE SAME TRENCH.
ALL ESTIMATED QUANTITIES ARE
APPROXIMATE AND ARE TO BE USED ONLY
AS A BASIS FOR ESTIMATING THE
PROBABLE COST OF THE WORK AND FOR
THE PURPOSE OF COMPARING BIDS
SUBMITTED FOR THE WORK. THE ACTUAL
AMOUNT OF WORK DONE AND MATERIALS
FURNISHED UNDER UNIT PRICE ITEMS MAY
DIFFER FROM THE ESTIMATED QUANTITIES.
PROPOSED BUILDING
FFE: 4597.00
Know what's below.
before you dig.Call
R FIRE SERVICE LINE
TYPE A TRENCH BACKFILL
TYPE 1 PIPE BEDDING
STATION 0+10 TO 0+81
INSTALL ± 59 LF OF
8" CLASS 51 DIP AWWA C151
STA 0+10.02 - 0.0' LT
INSTALL NEW 16" X 8" TEE
NOTES BY SYMBOL: 8" FIRE SERVICE
1
2
1
NOTES BY SYMBOL: 2" DOMESTIC SERVICE
2
STA 0+10.02 - 2.00' RT
INSTALL NEW 2" SERVICE SADDLE
STA 0+68.89 - 0.0' LT
EXTERIOR BUILDING WALL
SEE DETAIL 02660-13, THIS SHEET, FOR
CONNECTION TO BUILDING
STA 0+68.89 - 2.0' RT
EXTERIOR BUILDING WALL
1
1
2 2
1. ALL IMPROVEMENTS ON THIS PROJECT SHALL BE COMPLETED IN ACCORDANCE WITH THE
MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS, 6TH EDITION DATED APRIL 2010 (MPWSS);
THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS; AND THE PROJECT SPECIFICATIONS.
2. A PRECONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION.
NO MATERIAL CHANGES MAY BE MADE TO THIS PLAN WITHOUT THE APPROVAL OF THE CITY OF
BOZEMAN WATER/SEWER SUPERINTENDENT.
3. ALL TEXT AND FEATURES SHOWN SHADED WERE EXISTING.
4. THE LOCATION, DEPTH, AND SIZE OF THE EXISTING UTILITIES SHOWN ON THESE PLANS IS
APPROXIMATE. THE CONTRACTOR SHALL VERIFY THE EXISTENCE, LOCATION, DEPTH, AND SIZE
OF THE UTILITIES PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE
FOR ANY DAMAGE TO THE EXISTING FACILITIES DUE TO FAILURE TO LOCATE OR PROPERLY
PROVIDE PROTECTION WHEN LOCATION IS KNOWN.
5. DIMENSIONS SHOWN FOR PIPE LENGTHS ARE MEASURED FROM CENTER-OF-JUNCTION TO
CENTER-OF-JUNCTION FOR PAYMENT PURPOSES.
6. ALL WATER VALVES OWNED AND OPERATED BY THE CITY OF BOZEMAN SHALL BE OPERATED BY
AUTHORIZED CITY OF BOZEMAN PERSONNEL ONLY. CONTRACTOR SHALL COORDINATE WITH THE
CITY ENGINEER PRIOR TO CONNECTING TO EXISTING WATER LINES OWNED AND MAINTAINED BE
THE CITY OF BOZEMAN.
7. WATER CONNECTIONS SHALL BE PERFORMED BY A LICENSED PLUMBER.
8. ALL VALVES SHALL BE INSTALLED WITH THRUST BLOCKING AND VALVE BOXES IN ACCORDANCE
WITH THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS AND CITY OF BOZEMAN STANDARD
DRAWING NO. 02660-3.
9. ALL FITTINGS REQUIRING THRUST BLOCKING, INCLUDING BENDS GREATER THAN ELEVEN AND
ONE-QUARTER DEGREES (11.25°), TEES, AND PLUGS, SHALL BE INSTALLED IN CONFORMANCE
WITH THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS AND CITY OF BOZEMAN STANDARD
DRAWING NO. 02660-1.
10. IN LIEU OF CONCRETE THRUST BLOCKS, THRUST RESTRAINT MAY BE PROVIDED UTILIZING
MEGALUG; UNI-FLANGE; MJ FIELD LOK SERIES DI; FIELD LOK 350 GASKETS FOR PUSH-ON JOINTS,
MANUFACTURED BY US PIPE; SIGMA ONE LOK SERIES SLD, MANUFACTURED BY SIGMA
CORPORATION; OR APPROVED EQUAL FOR ALL FITTINGS THAT REQUIRE THRUST RESTRAINT,
EXCEPT FOR CUT-IN OR TAPPING TEES (FOR MAINS OR SERVICES) AND BENDS ON SERVICE LINES
INSIDE BUILDING FOUNDATIONS, UNLESS SPECIFICALLY PROHIBITED BY THE CITY OF BOZEMAN.
THE MECHANICAL RESTRAINTS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS AND AT ALL JOINTS AS SPECIFIED BY THE ENGINEER.
11. DETECTABLE WARNING TAPE SHALL BE INSTALLED, CENTERED OVER ALL WATER MAINS, SERVICE
LINES, AND HYDRANT LEADS. TAPE SHALL BE INSTALLED A MINIMUM OF EIGHTEEN INCHES (18")
AND MAXIMUM OF TWENTY-FOUR INCHES (24") BELOW FINISH GRADE.
12. THE SIX INCH (6") FIRE SERVICE LINE SHALL BE INSTALLED IN ACCORDANCE WITH THE CITY OF
BOZEMAN FIRE SERVICE LINE STANDARDS. THIS PLAN IS FOR CONSTRUCTION OF THE SIX INCH
(6") FIRE SERVICE LINE FROM THE EXISTING WATER MAIN TO THE OS&Y VALVE IN THE BUILDING.
13. THE FIRE SERVICE LINE SHALL BE INSTALLED, CHLORINATED, AND TESTED TO A MINIMUM OF 200
PSI BY A SINGLE CONTRACTOR. OWNER OR OWNER'S AUTHORIZED REPRESENTATIVE SHALL
PROVIDE CONSTRUCTION OBSERVATION AND PREPARE THE RECORD DRAWINGS. CONTRACTOR
SHALL FILL OUT AND SUBMIT "CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR
UNDERGROUND PIPING".
14. CONTRACTOR SHALL ADJUST ALL VALVE BOXES, CURB BOXES, AND MANHOLES TO FINAL GRADE
UPON COMPLETION OF ALL CONSTRUCTION. ANY BOXES OR MANHOLES DAMAGED OR
OTHERWISE DISTURBED BY THE CONTRACTOR OR SUBCONTRACTOR SHALL BE REPAIRED AT THE
EXPENSE OF THE CONTRACTOR. THIS WORK WAS INCIDENTAL TO THE PROJECT.
15. IF CORROSIVE SOILS ARE FOUND ON SITE, CONTRACTOR TO USE V-BIO POLYETHYLENE
ENCASEMENT AROUND PIPE.
16. THE FIRE LINE CONNECTION TO THE CITY WATER MAIN WITHOUT THE USE OF A TAPPING TEE WILL
BE MADE BY THE CONTRACTOR INSTALLING THE APPROPRIATE SIZED TEE IN THE WATER MAIN.
THE WATER DEPARTMENT WILL OPERATE ALL VALVES FOR THE SHUTDOWN OF THE LINE TO
INSTALL THE TEE AND MUST BE PROVIDED WITH A MINIMUM OF 24 HOURS' NOTICE BEFORE THE
WORK BEGINS. TEMPORARY WATER SERVICE SHALL BE PROVIDED TO ALL AFFECTED WATER
CUSTOMERS IF THE SHUTDOWN PERIOD IS ANTICIPATED TO EXCEED FOUR HOURS. THE CITY OF
BOZEMAN RESERVES THE RIGHT TO DETERMINE THE LIKELY EXTENT OF THE MAIN SHUT DOWN
BASED ON THE PROPOSED WORK AND CONTRACTOR EXPERIENCE, AND REQUIRE THE
INSTALLATION OF TEMPORARY WATER SERVICES BY THE CONTRACTOR.
C4.0
SITE PLAN REVIEW
12/03/21
2200.048STELLA FRIABRONKEN WAREHOUSE 3345 PRINCE LANE, BOZEMAN, MT FIRE SERVICE AND DOMESTIC WATER SERVICE9/24/2021 9:45:22 AMPRELIMINARYDRAWINGS----No. 49499
CELINE M
PROF
ESSIONAL E N G IN EERM O N TAN
A
LICENSE D
SAUCIER
COPYRIGHT 2019
ISSUE DATE DESCRIP.
ITEM NO.DESCRIPTION
ESTIMATED
QUANTITY UNIT
FIRE SERVICE QUANTITY SCHEDULE
103
8" CLASS 51 DIP AWWA C151 FIRE SERVICE 59 LF101
16" X 8" TEE
1 EA
1 EA102
0
VERT. SCALE IN FEET
0
HORIZ. SCALE IN FEET
1.5 3 3 6
15 30 30 60
104 1 EA8" OS&Y FL x FL VALVE & ASSEMBLY
8" GATE VALVEPRINCE LANEPRINCE LANE NELSON ROAD02660-13
-
PROPOSED FINISHED
GROUND AT CENTERLINE
OF FIRE SERVICE (TYP)
EXISTING GROUND
SURFACE (TYP)
FINISHED FLOOR
ELEVATION = 4597.00
FOR OS&Y VALVE
INSTALLATION
SEE DETAIL
BOTTOM OF FLANGE
ELEVATION = 4598.50
EXISTING GAS AND
BURIED POWER
APPROX. LOCATION
1 12/3/21 SP REV 1
CITY OF BOZEMAN
APPROVED FOR ONE YEAR FROM THIS DATE
These plans an specifications have been reviewed by the City
of Bozeman and are hereby approved. This approval does not
imply any specific warranty of the project design by the City of
Bozeman. All engineering design details and construction
operations performance are the responsibility of the design
engineer and the owner.
_____________________________________________________
Date City Review Engineer
12/10/2021 mschultz
06/27/23
21389-CO
4580
4585
4590
4595
4600
4605
4580
4585
4590
4595
4600
4605
0+00 1+00 2+00 3+00 4+00 5+00 6+00 7+00MH-(1)STATION: 0+46.59RIM ELEV = 4596.4615" IE IN S: 4590.1315" IE OUT W: 4589.93 MH-(2)STATION: 1+45.12RIM ELEV = 4596.14 15" IE IN E: 4589.29 15" IE OUT N: 4589.09 MH-(3) STATION: 4+92.09RIM ELEV = 4593.03 15" IE IN S: 4586.82 15" IE OUT W: 4586.62 94.54 LF 15" PVC @ 0.68%
342.98 LF 15" PVC @ 0.66%
181.26 LF 15" PVC @ 0.79%
EXISTING GROUND
SURFACE
PROPOSED FINISHED
GROUND AT PIPE
CENTERLINE
15" FLARED END
TREATMENT SECTION
W/ RIP RAP AT OUTLET
INV OUT: 4585.18'
CUT EXISTING 15" STORM PIPE
APPROXIMATELY 46' FROM EXISTING
MANHOLE IN PRINCE LANE
CONTRACTOR TO VERIFY LOCATION,
CONDITION, AND DEPTH OF EXISTING
STORM MAIN PRIOR TO ORDERING
NEW SD MANHOLES
STA: 0+57.31
6" SANITARY
SERVICE CROSSING
INV: 92.65
STA: 4+18.62
12" STORM DRAIN
CROSSING
INV: 90.42'
STA: 5+52.17
12" STORM DRAIN
CROSSING
INV: 88.37'
STA: 2+59.71
12" STORM DRAIN
CROSSING
INV: 91.88
12SD
SS12SD 12SD12SD12SD 12SD12SD 12SD15S D
15 SD
15SD
15SD
SD
SD12SD 12SD 12SD
SD SDFTVDYH DDDDSSPWVWVWVWVBPBPBPBPBPBPBPBPBPBPNGNGNGNGNGNGNGNGSSSSSSSSSSSSSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDSDBPBPBPBPBPBPBPBPBPWWWWWWWXXXXXXXXXXXXXXXF TV
DY HD D DDSS PWVWV WVWVBPBP BP BP BP BPBPBP BPBPNGNGNGNGNG NG NG NGSSSSS S S S S S S SSD SD SD SDSD SD SDSDSD SD SDSD SD SD SD SD SD SD SDSD SD SD SDSDBP BPBPBPBP BP BP BPBPW W W W W W WXX XX X X X X X X X X X X X N0°01'20"E 497.68'N89°52'46"W155.00'
342.68'222.49'222.63'S89°52'46"E 453.37'108.74'77.67'
S0°01'20"W 505.04'15SD 15SD 15SD15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SD 15SDSDMH-(1)
STA 0+46.59
N=50924.86
E=49836.41
MH-(3)
STA 4+92.09
N=51274.95
E=49750.10
OUTLET
STA 6+75.86
N=51342.33
E=49579.13
94.54 LF 15" PVC @ 0.68%342.98 LF 15" PVC @ 0.66%181.26 LF 15" PVC @ 0.79%MH-(2)
STA 1+45.12
N=50928.20
E=49737.93
0+00 1+002+00 3+00 4+00 5+00 6+00 7+004
5
9
5
4596
4
5
9
4
45924592
4591
4588458945904589 45904596
4595
4594
4595.00
4592.75
-1.
4
4
%-7.12%-2.76%-5.42%-3.10%-1
.
3
3
%C6.0
SITE PLAN REVIEW
1/13/2022
2008STELLA FRIABRONKEN WAREHOUSE3345 PRINCE LANE, BOZEMAN, MTSTORM DRAIN PLAN & PROFILE9/24/2021 9:45:22 AMNo. 49499
CELINE M
PROFESSIONAL E N G IN EERM O N T AN
A
LICENS ED
SAUCIER
COPYRIGHT 2019
ISSUE DATE DESCRIP.
PROPOSED BUILDING
0
VERT. SCALE IN FEET
0
HORIZ. SCALE IN FEET
2.5 5 5 10
15 30 30 60
STORM SEWER
STA 0+00.00 - 7+00.00
INSTALL 619 LF 15" PVC A-2000
TYPE A TRENCH BACKFILL,
TYPE 2 PIPE BEDDING
1. ALL IMPROVEMENTS ON THIS PROJECT SHALL BE COMPLETED IN ACCORDANCE
WITH THE MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS, 6TH EDITION
DATED APRIL 2010 (MPWSS); THE CITY OF BOZEMAN MODIFICATIONS TO THE
MPWSS; AND THE PROJECT SPECIFICATIONS.
2. ALL STORM DRAIN INLETS AND MANHOLES SHALL BE THE SIZE INDICATED, AND
CONSTRUCTED PER CITY OF BOZEMAN STANDARD DETAILS:
CURB INLET (2' X 3'): DETAIL # 02720-1A
CURB INLET (3' DIA.): DETAIL # 02720-1
CURB INLET (4' DIA.): DETAIL # 02720-1B
DROP INLET (2' DIA.) : DETAIL # 02720-2
MANHOLE: DETAIL # 02720-3 PREFERRED; #02720-4 AS NEEDED
MANHOLES INDICATING “RIM=” SHALL HAVE SOLID COVERS, THOSE INDICATING
“GRATE=” SHALL HAVE SLOTTED (GRATED) COVERS, AND THOSE INDICATING
“TBC=” SHALL HAVE CURB INLET TYPE SLOTTED COVERS.
3. .ALL PIPES LABELED "SD" (STORM DRAIN) ARE 12" DIA. OR LARGER. STORM DRAIN
PIPE SHALL BE DUAL WALLED, SMOOTH INTERIOR POLYETHYLENE PIPE. USE HP
STORM, AS MANUFACTURED BY ADS.
4. THE LOCATION, DEPTH, AND SIZE OF THE EXISTING UTILITIES SHOWN ON THESE
PLANS IS APPROXIMATE. THE CONTRACTOR SHALL VERIFY THE EXISTENCE,
LOCATION, DEPTH, AND SIZE OF THE UTILITIES PRIOR TO CONSTRUCTION. THE
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY DAMAGE TO THE
EXISTING FACILITIES DUE TO FAILURE TO LOCATE OR PROPERLY PROVIDE
PROTECTION WHEN LOCATION IS KNOWN.
5. DIMENSIONS SHOWN ARE TO CENTERLINE OF PIPE OR FITTING.
6. THE PIPE GRADES SHOWN ARE CALCULATED FROM ACTUAL DISTANCES,
EDGE-OF-MANHOLE TO EDGE-OF-MANHOLE AS APPLICABLE. THE DISPLAYED PIPE
LINEAL FEET REFLECTS THE DISTANCE FROM CENTER-OF-MANHOLE TO
CENTER-OF-MANHOLE ON ALL GRAVITY PIPING.
7. LAY PIPE TO UNIFORM GRADE BETWEEN INDICATED ELEVATION POINTS.
CONSTRUCTION NOTES:
1. ALL IMPROVEMENTS ON THIS PROJECT SHALL BE COMPLETED IN ACCORDANCE WITH THE MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS, SIXTH EDITION
DATED APRIL 2010 (MPWSS); THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS; AND THE PROJECT SPECIFICATIONS.
2. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE DIVISION OF INDUSTRIAL REGULATIONS (OSHA) SAFETY STANDARDS. IF REQUESTED BY THE INSPECTOR,
THE CONTRACTOR SHALL PROVIDE PROOF OF A PERMIT FROM SAID DIVISION.
3. THE CONTRACTOR'S OPERATIONS SHALL BE CONFINED WITHIN THE PROJECT LIMITS. MATERIALS AND EQUIPMENT SHALL BE STORED ON THE PROJECT SITE
WHERE APPROVED BY THE OWNER. IT SHALL BE UNDERSTOOD THAT THE RESPONSIBILITY FOR PROTECTION AND SAFEKEEPING OF EQUIPMENT AND MATERIALS
ON OR NEAR THE SITE WILL BE ENTIRELY THAT OF THE CONTRACTOR AND THAT NO CLAIM SHALL BE MADE AGAINST THE OWNER BY REASON OF ANY ACT OF AN
EMPLOYEE OR TRESPASSER.
4. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. ANY DISCREPANCIES FOUND ARE TO BE BROUGHT TO THE ENGINEER'S
ATTENTION PRIOR TO COMMENCEMENT OR CONTINUATION OF CONSTRUCTION ACTIVITIES.
5. REFERENCE ALL SURVEY MONUMENTS, SECTION CORNERS, 1/4 CORNERS, AND PROPERTY CORNERS PRIOR TO BEING DISTURBED BY CONSTRUCTION. ANY
MONUMENTS AND CORNERS DISTURBED DURING CONSTRUCTION SHALL BE REPLACED BY A PROFESSIONAL LAND SURVEYOR (PLS) REGISTERED IN THE STATE
OF MONTANA.
6. A PRE-CONSTRUCTION MEETING (AS REQUIRED) SHALL BE HELD WITH THE GENERAL CONTRACTOR, SITE SUBCONTRACTOR,CITY OF BOZEMAN, OWNER, AND
MORRISON-MAIERLE, INC. PRIOR TO THE START OF CONSTRUCTION.
7. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND THE CITY, COUNTY, AND/OR STATE INSPECTOR 48 HOURS PRIOR TO COMMENCING CONSTRUCTION AND 24
HOURS IN ADVANCE OF SPECIFIC INSPECTION NEEDS DURING THE COURSE OF THE WORK. ALL WORK SHALL BE PERFORMED DURING NORMAL WORKING HOURS
AND SUBJECT TO THE AVAILABILITY OF AN INSPECTOR AND APPROVED BY THE ENGINEER. THE CONTRACTOR WILL BE BILLED FOR SAID INSPECTION SERVICES
AS PROVIDED IN THE MOST RECENTLY ADOPTED FEES FOR SUCH SERVICES.
8. THE CONTRACTOR SHALL PERFORM ALL CONSTRUCTION ACTIVITIES IN A MANNER TO MINIMIZE INCONVENIENCE TO THE ADJACENT BUSINESSES.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL PUBLIC AND PRIVATE PROPERTY INSOFAR AS IT MAY BE AFFECTED BY THESE OPERATIONS,
ALL COSTS FOR PROTECTING, REMOVING, AND RESTORING EXISTING IMPROVEMENTS SHALL BE BORNE SOLELY BY THE CONTRACTOR.
10. THE CONTRACTOR SHALL AT ALL TIMES TAKE WHATEVER MEASURES ARE NECESSARY TO ASSURE THE PROPER CONTAINMENT AND DISPOSAL OF POLLUTANTS
ON THE SITE IN ACCORDANCE WITH ANY AND ALL APPLICABLE LOCAL, STATE, AND FEDERAL REGULATIONS.
11. THE CONTRACTOR SHALL IMMEDIATELY CLEAN UP ANY CONSTRUCTION MATERIALS INADVERTENTLY DEPOSITED ON EXISTING STREETS, SIDEWALKS, OR OTHER
PUBLIC RIGHTS-OF-WAY AND MAKE SURE STREETS AND WALKWAYS ARE CLEANED AT THE END OF EACH WORKING DAY.
12. CONSTRUCTION WORK ZONE TRAFFIC SIGNS SHALL BE FURNISHED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH APPLICABLE REQUIREMENTS OF THE
REGULATORY AGENCIES HAVING JURISDICTION. A TRAFFIC CONTROL PLAN, PREPARED BY THE CONTRACTOR, MAY BE REQUIRED BY THE CITY OR STATE.
"CONSTRUCTION AHEAD" WARNING SIGNS ARE TO TO BE INSTALLED ALONG ADJACENT ROADS OR DRIVEWAYS. FLASHERS WITH CAUTION TAPE ARE TO BE
INSTALLED WHERE ANY CONSTRUCTION ACTIVITY CROSSES A SIDEWALK OR PEDESTRIAN PATH IN ACCORDANCE WITH THE SPECIFICATIONS AND ANY OR ALL
LOCAL REGULATIONS.
13. AREAS ON THE SITE TO BE GRADED SHALL BE CLEARED AND GRUBBED OF ALL VEGETATION AND DEBRIS. THESE MATERIALS SHALL BE REMOVED FROM THE SITE
BY THE CONTRACTOR.
14. SURFACE SOILS WITHIN THE PROJECT LIMITS CONTAINING ROOTS AND ORGANIC MATTER SHALL BE STRIPPED DOWN AND STOCKPILED OR DISCARDED AS
DIRECTED BY THE OWNER OR ENGINEER.
15. NO STOPPING, PARKING, OR STORING OF CONSTRUCTION MATERIALS IN THE PUBLIC STREETS /ROADS, RIGHTS-OF-WAY, OR ANY DRIVEWAY IS ALLOWED.
16. THE CONTRACTOR SHALL RESTORE ALL ROADWAY SURFACES TO EQUAL OR BETTER CONDITION THAN EXISTED PRIOR TO EXCAVATION AS DETERMINED BY
AGENCY, OWNER, AND/OR ENGINEER.
17. ASPHALT AND CONCRETE SHALL BE SAW CUT OR NEAT CUT AS APPROVED BY THE ENGINEER.
18. THE CONTRACTOR SHALL UTILIZE COMPACTION EQUIPMENT SUITABLE FOR THE SOIL TYPES AND SURFACE MATERIALS ENCOUNTERED ON THE PROJECT.
19. SIDE SLOPES FROM DRIVE AND PARKING AREAS SHALL BE 4:1 MAX UNLESS OTHERWISE SPECIFIED.
20. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT THERE IS A CONSTRUCTION PERMIT APPROVED BY THE MONTANA DEPARTMENT OF ENVIRONMENTAL
QUALITY (MDEQ) OR LOCAL GOVERNING AGENCY AS APPROPRIATE FOR THE CONTROL OF STORM WATER RUNOFF. IF THERE IS NOT AN APPROVED PERMIT, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THE NECESSARY APPROVALS FROM MDEQ OR THE LOCAL GOVERNING AGENCY.
21. CONTRACTOR IS RESPONSIBLE FOR PROJECT DUST CONTROL.
22. ACCESSIBLE ROUTES SHALL HAVE A MAXIMUM. RUNNING SLOPE OF 5%.
EXISTING 15" STORM
DRAIN PIPE
EXISTING STORM
MANHOLE
1 12/3/21 SP REV 1
22.5" MIN DEPTH OF 2" TO 3" WASHED STONE SPLASH
PAD UNDERLAIN WITH PROPEX GEOTEX 601 NONWOVEN
GEOTEXTILE FABRIC OR APPROVED EQUAL,
REFER TO DETAIL "TEMPORARY OUTLET VELOCITY
DISSIPATION DEVICES RC-2" FROM MDT'S EROSION AND
SEDIMENT CONTROL BEST MANAGEMENT PRACTICES,
PAGE 59
EXISTING 15" STORM DRAIN
TO BE REMOVED
EXISTING 15" STORM DRAIN
TO BE REMOVED
EXISTING STORM DRAIN
MANHOLE TO BE REMOVED
PROPOSED SWALE
@ 1.0% SLOPE
2 1/13/22 SP REV 2
3 1/14/22 ENG REV 1
3
3
CITY OF BOZEMAN
APPROVED FOR ONE YEAR FROM THIS DATE
These plans an specifications have been reviewed by the City
of Bozeman and are hereby approved. This approval does not
imply any specific warranty of the project design by the City of
Bozeman. All engineering design details and construction
operations performance are the responsibility of the design
engineer and the owner.
_____________________________________________________
Date City Review Engineer
01/24/2022 mschultz
06/27/23
21389-CO
SS SSS S S SDSBP BP BPBP BP BP BP BPBP BP BP BPBP BPNGNG NG NG NG NG NGNGNG NG NGSS SS SSS S S S S S S SSSD SD SD SD SD SD SD SD SD SD SD SDSD SD SDBP BP BP BP BP BP BP BPBP BPBP BP BPBPW W WW W W W W W W W 435.82'15SD15SD 15SD 15SD15SD 15SD 15SDSD SD SD SDMH-(1)
STA 0+51.59
N=50929.87
E=49836.58
0+00 1+004" TOP SOIL
6" (MIN) 3" MINUS
COMPACTED SUBGRADE (95%)
FINE GEO FABRIC
STRUCTURAL GEO-GRID
COPYRIGHT 2019
PROPOSED BUILDING
CONSTRUCTION NOTES:
1. ALL IMPROVEMENTS ON THIS PROJECT SHALL BE COMPLETED IN ACCORDANCE WITH THE MONTANA PUBLIC WORKS STANDARD SPECIFICATIONS, SIXTH EDITION
DATED APRIL 2010 (MPWSS); THE CITY OF BOZEMAN MODIFICATIONS TO THE MPWSS; AND THE PROJECT SPECIFICATIONS.
2. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE DIVISION OF INDUSTRIAL REGULATIONS (OSHA) SAFETY STANDARDS. IF REQUESTED BY THE INSPECTOR,
THE CONTRACTOR SHALL PROVIDE PROOF OF A PERMIT FROM SAID DIVISION.
3. THE CONTRACTOR'S OPERATIONS SHALL BE CONFINED WITHIN THE PROJECT LIMITS. MATERIALS AND EQUIPMENT SHALL BE STORED ON THE PROJECT SITE
WHERE APPROVED BY THE OWNER. IT SHALL BE UNDERSTOOD THAT THE RESPONSIBILITY FOR PROTECTION AND SAFEKEEPING OF EQUIPMENT AND MATERIALS
ON OR NEAR THE SITE WILL BE ENTIRELY THAT OF THE CONTRACTOR AND THAT NO CLAIM SHALL BE MADE AGAINST THE OWNER BY REASON OF ANY ACT OF AN
EMPLOYEE OR TRESPASSER.
4. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. ANY DISCREPANCIES FOUND ARE TO BE BROUGHT TO THE ENGINEER'S
ATTENTION PRIOR TO COMMENCEMENT OR CONTINUATION OF CONSTRUCTION ACTIVITIES.
5. REFERENCE ALL SURVEY MONUMENTS, SECTION CORNERS, 1/4 CORNERS, AND PROPERTY CORNERS PRIOR TO BEING DISTURBED BY CONSTRUCTION. ANY
MONUMENTS AND CORNERS DISTURBED DURING CONSTRUCTION SHALL BE REPLACED BY A PROFESSIONAL LAND SURVEYOR (PLS) REGISTERED IN THE STATE
OF MONTANA.
6. A PRE-CONSTRUCTION MEETING (AS REQUIRED) SHALL BE HELD WITH THE GENERAL CONTRACTOR, SITE SUBCONTRACTOR,CITY OF BOZEMAN, OWNER, AND
MORRISON-MAIERLE, INC. PRIOR TO THE START OF CONSTRUCTION.
7. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND THE CITY, COUNTY, AND/OR STATE INSPECTOR 48 HOURS PRIOR TO COMMENCING CONSTRUCTION AND 24
HOURS IN ADVANCE OF SPECIFIC INSPECTION NEEDS DURING THE COURSE OF THE WORK. ALL WORK SHALL BE PERFORMED DURING NORMAL WORKING HOURS
AND SUBJECT TO THE AVAILABILITY OF AN INSPECTOR AND APPROVED BY THE ENGINEER. THE CONTRACTOR WILL BE BILLED FOR SAID INSPECTION SERVICES
AS PROVIDED IN THE MOST RECENTLY ADOPTED FEES FOR SUCH SERVICES.
8. THE CONTRACTOR SHALL PERFORM ALL CONSTRUCTION ACTIVITIES IN A MANNER TO MINIMIZE INCONVENIENCE TO THE ADJACENT BUSINESSES.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL PUBLIC AND PRIVATE PROPERTY INSOFAR AS IT MAY BE AFFECTED BY THESE OPERATIONS,
ALL COSTS FOR PROTECTING, REMOVING, AND RESTORING EXISTING IMPROVEMENTS SHALL BE BORNE SOLELY BY THE CONTRACTOR.
10. THE CONTRACTOR SHALL AT ALL TIMES TAKE WHATEVER MEASURES ARE NECESSARY TO ASSURE THE PROPER CONTAINMENT AND DISPOSAL OF POLLUTANTS
ON THE SITE IN ACCORDANCE WITH ANY AND ALL APPLICABLE LOCAL, STATE, AND FEDERAL REGULATIONS.
11. THE CONTRACTOR SHALL IMMEDIATELY CLEAN UP ANY CONSTRUCTION MATERIALS INADVERTENTLY DEPOSITED ON EXISTING STREETS, SIDEWALKS, OR OTHER
PUBLIC RIGHTS-OF-WAY AND MAKE SURE STREETS AND WALKWAYS ARE CLEANED AT THE END OF EACH WORKING DAY.
12. CONSTRUCTION WORK ZONE TRAFFIC SIGNS SHALL BE FURNISHED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH APPLICABLE REQUIREMENTS OF THE
REGULATORY AGENCIES HAVING JURISDICTION. A TRAFFIC CONTROL PLAN, PREPARED BY THE CONTRACTOR, MAY BE REQUIRED BY THE CITY OR STATE.
"CONSTRUCTION AHEAD" WARNING SIGNS ARE TO TO BE INSTALLED ALONG ADJACENT ROADS OR DRIVEWAYS. FLASHERS WITH CAUTION TAPE ARE TO BE
INSTALLED WHERE ANY CONSTRUCTION ACTIVITY CROSSES A SIDEWALK OR PEDESTRIAN PATH IN ACCORDANCE WITH THE SPECIFICATIONS AND ANY OR ALL
LOCAL REGULATIONS.
13. AREAS ON THE SITE TO BE GRADED SHALL BE CLEARED AND GRUBBED OF ALL VEGETATION AND DEBRIS. THESE MATERIALS SHALL BE REMOVED FROM THE SITE
BY THE CONTRACTOR.
14. SURFACE SOILS WITHIN THE PROJECT LIMITS CONTAINING ROOTS AND ORGANIC MATTER SHALL BE STRIPPED DOWN AND STOCKPILED OR DISCARDED AS
DIRECTED BY THE OWNER OR ENGINEER.
15. NO STOPPING, PARKING, OR STORING OF CONSTRUCTION MATERIALS IN THE PUBLIC STREETS /ROADS, RIGHTS-OF-WAY, OR ANY DRIVEWAY IS ALLOWED.
16. THE CONTRACTOR SHALL RESTORE ALL ROADWAY SURFACES TO EQUAL OR BETTER CONDITION THAN EXISTED PRIOR TO EXCAVATION AS DETERMINED BY
AGENCY, OWNER, AND/OR ENGINEER.
17. ASPHALT AND CONCRETE SHALL BE SAW CUT OR NEAT CUT AS APPROVED BY THE ENGINEER.
18. THE CONTRACTOR SHALL UTILIZE COMPACTION EQUIPMENT SUITABLE FOR THE SOIL TYPES AND SURFACE MATERIALS ENCOUNTERED ON THE PROJECT.
19. SIDE SLOPES FROM DRIVE AND PARKING AREAS SHALL BE 4:1 MAX UNLESS OTHERWISE SPECIFIED.
20. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT THERE IS A CONSTRUCTION PERMIT APPROVED BY THE MONTANA DEPARTMENT OF ENVIRONMENTAL
QUALITY (MDEQ) OR LOCAL GOVERNING AGENCY AS APPROPRIATE FOR THE CONTROL OF STORM WATER RUNOFF. IF THERE IS NOT AN APPROVED PERMIT, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THE NECESSARY APPROVALS FROM MDEQ OR THE LOCAL GOVERNING AGENCY.
21. CONTRACTOR IS RESPONSIBLE FOR PROJECT DUST CONTROL.
22. ACCESSIBLE ROUTES SHALL HAVE A MAXIMUM. RUNNING SLOPE OF 5%.
EXISTING 15" STORM
DRAIN PIPE
EX 1
PR #4
10/6/2022
2008STELLA FRIABRONKEN WAREHOUSE3345 PRINCE LANE, BOZEMAN, MTSTORM MANHOLE ACCESS DRIVE9/24/2021 9:45:22 AMNo. 49499
CELINE M
PROFESSIONAL E N G IN EERM O N T AN
A
LICENS ED
SAUCIER
EXISTING STORM
MANHOLE
EXISTING 15" STORM DRAIN
TO BE REMOVED
ISSUE DATE DESCRIP.
1 12/3/21 SP REV 1
3 2/3/22 ADD 2
SCALE: 1/2" = 1'-0"
PROPOSED ACCESS DRIVE TO MANHOLE
PROPOSED ACCESS
DRIVE, SEE DETAIL
1/EX1
10 205 10 0
SCALE IN FEET
PROPOSED ACCESS
DRIVE, SEE DETAIL
1/EX1
06/27/23
21389-CO