Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
056_A0.05 - Typical Details - Fire Rated
Plug all nused knockout holes with knockout caps (Typ) Cont. Bead of Resilient Caulk 1'-0" O.C. Min Outlet Box Pad Applied to Back of Boxes Closer than 24" O.C. 1/8" Clearance All Around Typ Flexible Conduit With 6" Slack Per 24" Run 2'-0" O.C. Min Outlet Box Pad Applied to Back of Boxes Closer than 24" O.C. Outlet Pad Applied to Back of Boxes in Rooms w/ Noise Criterion NC 25 or Less Flexible Conduit w/ 3" Slack Per 12" Run 1"1"1/2"1 1/4" Diam Polyethylene Foam Backing Rod or a 1 1/4" Diam Closed Cell Neoprene Sponge Rod with 2 Continuous Beads Non- Hardening Resilient Caulk, Continuous all 4 Sides of Duct Piping, See Mechanical 1" Thick Density Glass or Mineral Fiber 1" Wide x 1/2" Thick Neoprene Closed Cell, 2 Continuous Beads Non-Hardening Resilient Caulk 1/2"Note: Minimum 5" Separation Between Adjacent Penetrations 1-HR RATED REF ASSEMBLY 1-HR RATEDREF ASSEMBLYUNIT UNIT OR CORRIDOR UNIT SOLID BLOCKING, TYP 1-HR RATED REF ASSEMBLY 2-HR RATEDREF ASSEMBLYINTERIOR EXIT STAIR UNIT OR CORRIDOR UNIT 2-HR RATED REF ASSEMBLY SEE STRUCTURAL FOR PLYWOOD LOCATIONS, WHERE OCCUR 2-HR RATEDREF ASSEMBLYINTERIOR EXIT STAIR UNIT EXTERIOR 2-HR RATED REF ASSEMBLY WALL FURRING 1-HR RATED REF ASSEMBLY 1-HR RATED REF ASSEMBLY WALLNON-RATEDUNIT UNIT OR CORRIDOR SOLID BLOCKING 1-HR RATED REF ASSEMBLY UNIT UNIT OR CORRIDOR1-HR RATEDREF ASSEMBLYCONTINUOUS BLOCKING 1-HR RATED REF ASSEMBLY UNIT UNIT OR CORRIDOR1-HR RATEDREF ASSEMBLYCONTINUOUS BLOCKING 1-HR RATEDREF ASSEMBLYINTERIOR EXIT STAIR UNIT OR CORRIDOR 2-HR RATED REF ASSEMBLY UNIT OR CORRIDOR UNIT1-HR RATEDREF ASSEMBLYWALL NON-RATED 3/4" MIN. CONTROL MEASUREMENT Emergency Stop Door Close Alarm Bell Door Open 1 2 ELEVATOR CONTROL PANEL VIEW OF ELEV. CAB DOOR PLACE STAR ALONGSIDE MAIN EXIT FLOOR NOTES: - BUTTONS SHALL BE RAISED 1/8" (+/- 1/32") ABOVE SURROUNDING SURFACE. MIN. 3/8" CLR. SPACE BTWN BUTTONS TYP. - BUTTONS SHALL BE ILLUMINATED - BUTTONS SHALL BE ACTIVATED BY A MECHANICAL MOTION THAT IS DETECTABLE MAXIMUM HEIGHT FROM FLOOR TO HIGHEST BUTTON TOP OF HANDRAIL OF HIGHEST BUTTONS PHOTOELECTRIC TUBE BYPASS SWITCH HALL LANTERN EMERGENCY TELEPHONE W/ HANDSET CORD 2'-5" MIN. LENGTH REOPENING DEVICE SENSOR, 5" & 29" A.F.F.5"29"A B CALL BUTTON HALL LANTERN FLOOR LANDING SYMBOLS & NUMBERS ON BOTH SIDES OF DOOR JAMB W/ BRAILLE CHARACTERS PER ICC A117.1, 407.2.3. ENTRY LEVEL SHALL INCLUDE A RAISED STAR. SEE DETAIL MINIMUM HEIGHT FROM FLOOR TO LOWEST BUTTON ELEVATOR'S CAB VIEW 1 1/2" CLEAR BETWEEN RAIL AND WALL CAR CONTROL BUTTONS AS REQUIRED BY CODE, TYP. (ICC A117.1, 407.4.6 & 309) NOTES: -SOFFIT NOT SHOWN FOR CLARITY -AUDIBLE SIGNAL ALSO TO BE PROVIDED -The elevator shall comply with the emergency operation and signaling device requirements of ICC A117.1 Section 407. Standby power shall be provided in accordance with IBC Chapter 27 and Section 3003. NOTE: THE AUTOMATIC DOOR REOPENING DEVICE IS ACTIVATED IF AN OBJECT PASSES THROUGH EITHER LINE A OR B; LINES A & B REPRESENT THE VERTICAL LOCATION OF THE DOOR REOPENING DEVICE NOT REQUIRING CONTACT. DEVICE SHALL REMAIN EFFECTIVE FOR 20 SECONDS, MIN.60"72" MIN.42"4'-0" MAX.6'-0" MIN.4'-3" MIN.4'-6" MIN. FACE OF DOOR 35"4'-0" MAX.6'-0" TO 6'-6"4'-0" MAX.2'-11" MIN.2'-8"MINIMUM NUMERICAL SIZE 5/8" MIN. X 6'-8" MIN. 42" WIDE SIDE SLIDE DOOR BRAILLE CHARACTERS AS REQUIRED BY CODE, TYP. (ICC A117.1, 407.4.7.1) TO ACCOMODATE 24"x84" GURNEY PER IBC 3002.4.1a 51" MIN. PROJECT # SHEET NUMBERREVISION:DATE 618 N Wallace | Bozeman, MT 59715This drawing is not intended nor shall it be used for construction purposes unless the signed professional stamp of a regisered architect employed at MINARIK Architecture, Inc. is affixed above. Consultant:971−319−6249 | www.minarikarch.comProject Status:© 2022 MINARIK Architecture, Inc ALL RIGHTS RESERVED These Drawings are the Property of MINARIK Architecture, Inc and are not to be used or reproduced in any manner without prior written permission.11/10/2023 3:26:52 PM2303 A0.05The Lumberyard FlatsVirga Venture 1 LLCTschache Lane11/10/2023 Typical DetailsSchematic DesignAccoustic Detail - Receptacles in Stud Wall Acoustic Detail - Pipe / Conduit Wall Penetration PLAN DETAIL - 1 HOUR WALL TO 1 HOUR WALL PLAN DETAIL - 1 HOUR WALL TO 2 HOUR WALL PLAN DETAIL - 1 HOUR WALL TO 2 HOUR WALL PLAN DETAIL - NON-RATED WALL TO 1 HOUR WALL SECTION DETAIL - 1 HOUR WALL TO 1 HOUR FLOOR/CEILING SECTION DETAIL - 1 HOUR WALL TO 1 HOUR FLOOR/CEILING SECTION DETAIL - 2 HOUR WALL TO 1 HOUR FLOOR/CEILINGSECTION DETAIL - NON-RATED WALL TO 1 HOUR FLOOR/CEILING Elevator Cab Details REVISIONDATEREASON FOR ISSUE