HomeMy WebLinkAbout025 - P9.0 - PLUMBING DETAILS2
P9.0
11' - 6 1/2"7' - 6"WATER SERVICE
FIRE SERVICE
FDC
GAS SERVICE ELECTRIC SERVICE
Level 1
0' -0"
LEVEL 1
0' -0"
00 T.O. SLAB
100' -0"
SERVICE ANGLE STOP
METER/STRAINER ASSEMBLY
REDUCED PRESSURE ZONE
ASSEMBLY BACKFLOW PREVENTER
PRESSURE REDUCING VALVE
BUILDING ISOLATION VALVE
WATER HEATER2" COLD WATER SERVICE
ACE JOB 23BZ5752
12 N. BROADWAY
SECOND FLOOR
BELGRADE, MT 59714
406-388-3320
Client is responsible for notifying architect in writing for any
discovered errors or omissions in the plans and specifications
during construction of the project. Failure for Client to notify
Architect of any known errors or omissions in the plans or
specifications, and proceeding with constructing the portion of work
shown in the plans or specifications containing known errors or
omissions shall be a waiver by Client for any liability of Architect for
such known errors or omissions. Client releases Architect for any
liability for such portions of work, and Architect shall not be liable
for any delay damages, change orders, repair costs, removal or
demolition costs, or replacement of any such portions of work. COPYRIGHT 2022 KTGY GROUP INC. These plans and specifications are protected by United States copyright law and may not be used, reproduced, distributed, transmitted, displayed, or modified in any way without the prior written consent of KTGY Group, Inc. or the authorized copyright holder or licensee.Printed : File Path: 07/07/2023 10:05:19 AMAutodesk Docs://5752 - South Range Development Clubhouse/23BZ5752 - Mechanical_R22.rvtBOZEMAN, MTSouth Range CrossingP9.0
PLUMBING DETAILS
07/07/23PRELIMINARY - NOT FOR CONSTRUCTION
ktgy Project Number
Contact
Email
Principal
Designer
Architecture | Branding | Interiors | Planning
3660 Blake St.
Suite 500
Denver, CO 80205
ktgy.com
303.825.6400
Ken Hurt
khurt@ktgy.com
William Ramsey
Developer
PROVIDENCE
DEVELOPMENT CO.
529 E. MAIN STREET
BOZEMAN, MT 59772
PROVIDENCEDEVCO.COM
406-551-7939
No. DATE DESCRIPTION
1/4" = 1'-0"1 WATER RISER ROOM ENLARGED PLAN
1/4" = 1'-0"2 WATER RISER SECTION
80 128.5 2" 2" 2" RPZA 60 2" 75
PEAK
DEMAND
(GPM)
PEAK
DEMAND
(WSFU)
SERVICE
LINE SIZE METER SIZE
BACKFLOW
PREVENTER
SIZE
BACKFLOW
PREVENTER
TYPE
STATIC
PRESSURE AT
SERVICE
PRESSURE
REDUCING
VALVE SIZE
PRESSURE REDUCING
VALVE SETPOINT
CLUBHOUSE WATER SERVICE SCHEDULE
NOTES:
1. CONTRACTOR SHALL VERIFY SITE WATER SUPPLY STATIC PRESSURE AND SHALL NOTE DISCREPENCIES TO THE ENGINEER.
2. SITE CONTRACTOR SHALL PROVIDE WATER SERVICE PIPING AND ACCESSORIES UP TO AND INCLUDING THE SERVICE ANGLE STOP. SITE CONTRACTOR SHALL
PROVIDE DISINFECTION, FLUSHING, PRESSURE TESTING, AND BACTERIOLOGICAL TESTING OF THE SERVICE PIPING. PLUMBING CONTRACTOR SHALL PROVIDE PIPING
AND ACCESSORIES DOWNSTREAM OF THE SERVICE ANGLE STOP.
3. COORDINATE WITH THE CITY OF BOZEMAN FOR PROCUREMENT AND INSTALLATION OF THE SERVICE WATER METER.
4. SEE PLUMBING SECTIONS AND DETAILS FOR ADDITIONAL REQUIREMENTS.
TOTAL 1,150 MBH
EQ-### OUTDOOR BBQ 100 MBH
EQ-### RANGE 125 MBH
EQ-### INDOOR FIRE PLACE 125 MBH
POOL EQIUPMENT POOL EQUIPMENT 800 MBH
TAG DESCRIPTION
ITEM INPUT DEMAND DEMAND UNITS
CLUBHOUSE NATURAL GAS FUEL LOAD SUMMARY
NOTES:
1. EQUIPMENT INPUT DEMAND AT SITE ELEVATION IS BASED ON "ANSI Z21-13/CSA 4.9 INPUT RATING REQUIREMENTS AT SITE ELEVATION" OR THE PUBLISHED INPUT
DEMAND RATING AT SITE ELEVATION BY THE EQUIPMENT MANUFACTURER.
2. SYSTEM DELIVERY PRESSURE SHALL BE 2 PSIG AND SHALL BE REDUED TO 14" W.C. AT EACH PIECE OR GROUP OF EQUIPMENT. COORDINATE WITH THE LOCAL
UTILITY PROVIDER.
3. MOST REMOTE FIXTURE IS EQ-### ~#### FEET EQUIVALENT PIPE LENGTH FROM METER.
4. PLUMBING CONTRACTOR SHALL PRIME AND PAINT ALL NATURAL GAS PIPING ON THE BUILDING EXTERIOR TO MATCH THE BUILDING COLOR. COORDINATE WITH
GENERAL CONTRACTOR.
5. SEE BUILDING PLUMBING DRAWINGS FOR COORDIANTION AND ADDITIONAL REQUIREMENTS.
TOTAL FIXTURE LOAD 128.5 WSFU
WATER CLOSET, FLUSHOMETER VALVE UPC TABLE 610.10 4 90
URINAL, FLUSHOMETER VALVE UPC TABLE 610.10 1 20
SINK - LAUNDRY 1.5 0 0
SINK - KITCHEN, DOMESTIC 1.5 2 3
LAVATORY 1 2 2
SERVICE / MOP BASIN 3 1 3
DRINKING FOUNTAIN 0.5 2 1
HOSE BIBB, EACH ADDITIONAL 1 4 4
HOSE BIBB 2.5 1 2.5
DISHWASHER, DOMESTIC 1.5 2 3
CLOTHES WASHER 4 0 0
SHOWER (PER HEAD) 2 0 0
SOAKER TUB 10 0 0
BATHTUB OR COMBINATION BATH/SHOWER 4 0 0
FIXTURE TYPE WATER SUPPLY
FIXTURE UNITS / FIX.FIXTURE COUNT WSFU
CITY OF BOZEMAN WATER SERVICE CALCULATION - COMMERCIAL
NOTES:
1. FIXTURE LOADS IN ACCORDANCE WITH THE CITY OF BOZEMAN COMMERCIAL WATER SERVICE CALCULATION WORKSHEET AND CHAPTER 6 OF THE UNIFORM
PLUMBING CODE.
2. DISTRIBUTION PIPE SIZING PROVIDED IN ACCORDANCE WITH CHAPTER 6 OF THE UNIFORM PLUMBING CODE.