HomeMy WebLinkAbout10 C5.10 Lighting DetailsSCALE: N.T.S.22TYPICAL PULL BOXSCALE: N.T.S.21TYPICAL POLE BASESCALE: N.T.S.20TYPICAL STREET LIGHTSCALE: N.T.S.23TYPICAL PULL BOX DIMENSIONSSCALE: N.T.S.24TYPICAL CONDUIT BURIALSCALE: N.T.S.26NOT USEDSCALE: N.T.S.25POLE BASE DETAILPOLEHEIGHTSIZELONG STLHORIZONTAL STL*DEPTH**HEIGHTAFG(T.O.C.)40'24"Ø(8) # 6***#4 AT 12"O.C.4'-6"2"LIGHT FIXTURE BASE SCHEDULE *****PROVIDE TYPE (E1) LIGHT AND FIXTURE FOR ALL NEW POLES**DEPTH BELOW FINISHED GRADE.***SPACE LONG. STEEL EVENLY AROUND PERIMETER. 2.5" END CLEARANCE.****PROVIDE REINF. CLEARANCE PER ANCI 318.24" DIA.4' - 6"2' - 6"PROVIDE FUSE(S) IN CKT. TO BALLAST.FUSE(S) SHALL BE BUS TYPE BBS. FUSEHOLDERS SHALL BE BUSS "TRON" HEBWATERPROOF. SIZE OF FUSE SHALL BE ASREQUIRED BY LUMINAIRE MANUFACTURER.CONNECT GROUND TO POLE BASEW/BURNDY #GB4CBASE COVERFINISH GRADE2" CHAMFERPROJECT ANCHOR BOLT 3"MIN ABOVE TOP OF BASE.PROVIDE DOUBLE NUTS FORLEVELING UNIT (ONE ABOVEAND ONE BELOW BASEFLANGE). GROUT VOIDBETWEEN BASE FLANGE ANDTOP OF CONCRETE, LEAVINGDRAIN HOLE.HAND FINISH.BUSH CONDUITSCONTRACTOR MAY FORMFOUNDATION WITHSONOTUBE.HANDHOLE - 4" X6" (NOMINAL)M-4000 CONCRETE FILLLONG REINF. SEESCHEDULEANCHORBOLTS FROMPOLE MANF.HORIZ. TIES SEE SCHEDULETHWN CONDUCTOR PROVIDE 1' OFCOILED SLACK ON CONDUCTORFEED THRUC5.10AS NOTEDELECTRICAL DETAILSBVHEC Sep 26, 2022 - 5:38pmCAD FILE: M:\193190\Drawings\Exhibits\ELECTRICAL PLAN.dwg
REVISIONSDATEPROJECT NUMBERHYALITE Engineers, PLLC2304 N 7th Ave. Ste. LBozeman, MT 59715Tel: (406) 587.2781w w w . hyaliteeng. comFax: (406) 522.92252018E. FRONTAGE ROADBOZEMAN, MT 59715FRONTAGE ROAD LLC8/29/202219319022x34 originals SCALESHEET TITLEDESIGN BYPO BOX 1070BOZEMAN, MT 59771COMMERCIAL DEVELOPMENT