PERMIT SETSPANISH PEAKSCONNECTIONS HEALTH SOLUTIONSN.T.S.19 LEVEL 1 LIGHTING SYSTEMS DEMOLITION PLAN
TRUE
NORTH
0'4'2'4'8'
SCALE : 1/4" = 1'-0"
ELECTRICAL GENERAL DEMOLITION NOTES
I ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH NEC, STATE AND LOCAL
BUILDING CODE.
J PRESENT ANY USABLE/ SALVAGEABLE ELECTRICAL DEVICES TO OWNER INCLUDING BUT
NOT LIMITED TO: LIGHT FIXTURES, ELECTRICAL HEATERS, PANELS, CIRCUIT BREAKERS
ETC. REMOVE ALL UNCLAIMED ITEMS AND DISPOSE IN ACCORDANCE WITH ALL
REGULATIONS AND STANDARDS.
K ALL DASHED ITEMS ON DEMOLITION PLANS ARE TO BE REMOVED UNLESS NOTED
OTHERWISE. SOLID ITEMS ARE TO REMAIN OR TO BE RELOCATED AS NOTED.
L ANY WORK THAT REQUIRES POWER DISRUPTIONS SHALL BE SCHEDULED AND APPROVED
BY THE OWNER. ALL WORK SHALL BE PERFORMED WITH NO DISRUPTION OF THE
OWNER'S BUSINESS.
ELECTRICAL GENERAL DEMOLITION NOTES
A INTENT OF DEMOLITION WORK IS TO REMOVE ALL ELECTRICAL SYSTEMS WITHIN THE
PROJECT AREA IN PREPARATION FOR RENOVATION WORK. THIS INCLUDES ALL DEVICES,
WIRING, FIXTURES, AND ABANDONED SYSTEMS CABLING. FIRE ALARM CABLING COMING
FROM THE ADJOINING SPACE SHOULD BE REMOVED BACK TO PROJECT BOUNDARY.
B ALL DEVICE AND EQUIPMENT SHOWN ARE BASED ON LIMITED FIELD OBSERVATIONS.
CONTRACTOR SHALL VERIFY EXISTING CONDITIONS AND MAKE ALLOWANCE IN THEIR
BID TO ACCOUNT FOR ALL EXISTING CONDITIONS THAT AFFECT THEIR WORK.
C EXISTING WIRING METHODS OBSERVED IN THE PROJECT AREA DO NOT COMPLY WITH
REQUIREMENTS FOR THE PLANNED FUTURE USE AS A HEALTHCARE FACILITY IN
ACCORDANCE WITH 2017 NEC 517.13(A). ALL WIRING THAT DOES NOT COMPLY WITH
THIS REQUIREMENT SHALL BE REMOVED.
D ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES IN AREAS OF THIS
FACILITY AFFECTED BY REMODEL WORK INCLUDING BUT NOT LIMITED TO: JUNCTION
BOXES, OUTLETS, LIGHTS, CABLE, CONDUIT AND WIRE. ALL DEVICES MAY NOT BE
SHOWN ON THIS SHEET AND SITE INVESTIGATION IS REQUIRED FOR EXACT QUANTITIES.
CONFIRM DEMOLITION SCOPE WITH GENERAL CONTRACTOR AT PRE-BID WALK AND
RECYCLE WHERE FEASIBLE. DISPOSE OF ALL FLUORESCENT LAMPS AND BALLASTS IN A
LEGAL AND ENVIRONMENTALLY FRIENDLY MANNER. PROVIDE PROPER DISPOSAL
DOCUMENTATION STATING ITEMS DISPOSED OF AND QUANTITY TO OWNER FOR
RETENTION.
E EXISTING CONDUITS STUBBED THROUGH THE FLOOR THAT ARE NOT REUSED OR ARE
ABANDONED SHALL BE REMOVED.
F RETAIN ALL FIRE ALARM DEVICES FOR REUSE. RETURN ALL UNUSED FIRE ALARM DEVICES
TO THE OWNER.
G PROVIDE NEW CONDUCTORS IN EXISTING RACEWAYS THAT ARE FEASIBLE TO RE-USE.
USE EXISTING BACKBOXES WITH NEW DEVICES IN APPROPRIATE AREAS.
H REMOVE ALL WIRING FROM DESTINATION POINT BACK TO SOURCE AS NO EXISTING
WIRING MAY BE REUSED IN THE NEW ELECTRICAL WORK. EXISTING CONDUITS AND
PATHWAYS MAY BE REUSED IF THEY MEET THE PROJECT REQUIREMENTS.
ELECTRICAL KEYNOTES
1 REMOVE EXIT SIGN FOR REPLACEMENT.
2 REMOVE ILLUMINATED EXTERIOR SIGN AND ASSOCIATED CIRCUITS.