HomeMy WebLinkAbout029 Reclamation System - Engineer memo •• pTA%j N q••., KELLY L. W O O L P E P T TED AN ARCHITECTURE I ENGINEERING I GEOSPATIAL �0.41300 PE �•�.' •�oFSs�CENSG� • Memo • 'ONA� � • • 7-29-22 To: City of Bozeman From: Kelly Stedman, PE Date: 7-29-22 Proposed Tidal Wave Auto Spa Subject: 2102 W. Babcock St Bozeman, MT The proposed reclamation system for the Tidal Wave car wash consists of four underground tanks;three 1,500 gal reclamation tanks and a 1,500 gallon oil water separator. Discharge water from the car wash enters into Tank#1 where it is then interconnected with Tank#2 and Tank#3.There is a separate discharge from the carwash that bypasses the reclamation system and enters directly into Tank#4(oil water separator)from the tire shine component.The pump for the reclamation tank system is located in tank#3.The tanks are interconnected with a 6" pipe between Tank#3 and Tank#4(oil/water separator).The discharge in the reclamation tanks is pumped back to the car wash and recycled in the next wash cycle. It is designed by the manufacturer of the car was equipment so that 67.6%of the water is recycled through the reclamation system and the remaining water is discharged to the sewer system. If the pump in Tank#3 were to fail and water discharging to the reclamation system was not able to recirculate back to the car wash, it would overflow into the oil water separator through a 6" pipe(15 on the detail). It should be noted that the pumps have typical highwater alarms. Based on the water usage information provided by the manufacturer during normal operation,the freshwater usage per car is 23.33 gallons per car while using 48.80 gallons per car of reclaimed water. If the reclaim pump failed and the car wash tunnel continued to operate,the 48.80 gallons would be drawn from the freshwater line instead of the reclaimed water system.Therefore,a total of 72.13(23.33+48.80)gallons per car would discharge to the sanitary sewer system during a reclaim pump failure.The car wash typically operates at 1 car minute. If the pump did not recycle the water in the reclamation tank,the car wash discharge of 72.13 gpm would all go to the 6"sanitary lateral.The proposed 6" lateral is to be constructed at a 1%minimum slope to the sanitary main.A 6" pipe at 1%slope flowing half full has the capacity to handle approximately 100 gpm.The proposed 6"sanitary lateral has the capacity for the carwash discharge,a SSO would not occur,and the water would be discharged to the sanitary sewer system. Page 2 TYPICAL LAYOUT Discharge Pipe to 6" gravity sanitary lateral. TANK#1 TANK#2 TAN #3 TANK t0or• TANKS TYPICAL 1,500 GAL.PRECAST CONCRETE 5 TANK 11-to UNDERFLOW-IS PRIMARY SETTLEMENT 6 TANK#2-SECONDARY SETTLEMENT W,A BAFFLE TANK#3-PROCESSTANK 12 TANK#4-OIL AND WATER SEPARATOR PER MUNICIPAL 1A 2B SPECIFICATIONS 1S 2A 13 a 2 NICn_ 6 T UNDERGROUND PLUMBING 3M 4 I 1-2"SCH 80 PVC PIPE-UNDERFLOW DISCHARGE-TO 43 2-6"SCH 40 PVC PIPE-EXTERNAL CROSSOVER-FROM TANK 1 B TO TANK 2A 3-TWO 6"SCH 40 PVC PIPES-CENTER TRENCH-TO 16 TANKIB 4-4"OR 6'5CH 40 PVC PIPE-OVERFLOW FROM TANK 2B TO TANK 3 5-SS CH 40 PVC PIPE-EXTERNAL CROSSOVER-FROM 15 WALL TANK 2B TO TANK 3 6-W SCH 80 PVC PIPE-FILTER PUMP SUCTION LINE- T FROM WASH FROM TANK 3"SHOULD HAVE SLIGHT FALL TO RISER ENTRANCE,16- INSTALL 90'AS HIGH AS POSSIBLE ON RISER TO BELOW ANGLE ALLOW FOR EASY MAINTENANCE.' IRON 7-3"SCH 80 PVC PIPE-SPARE SUCTION LINE-FROM EXIT_ TANK 3'COMPLETE PLUMBING ON SPARE SUCTION g LINE.UNION 8 FOOT VALVE SAME AS PRIMARY(6). SHOULD HAVE SLIGHT FALL TO RISER.INSTALL 90' CENTER TRENCH AS HIGH AS POSSIBLE ON RISER TO ALLOW FOR EASY MAINTENANCE' S-4'OR 6"SCH 40 PVC PIPE-AQUAPREP DISCHARGE- SPLIT TO TANK 3 ISLA 9-4'OR 6"SCH 40 PVC PIPE-AQUAPREP DISCHARGE- )TES: ABOVE GROUND PLUMBING SPLIT TO CENTER TRENCH 1CTUAL TANK DIMENSIONS MAY VARY. 10-2'PIPE-RECLAIM WATER OUTLET-FROM ERS TO CAR WASH EQUIPMENT 12-6"SCH 40 PVC PIPE-INTERNAL CROSSOVER-FROM 'LUMBING SHOULD BE PLACED AS SHOWN 11-2'PIPE-FRESH WATER INLET-FROM CITY WATER SOURCE TO ERS TANK 1A TO TANK I 2EGARDLESS OF WHAT TANKS ARE USED. 14-2"SCH 80 PVC PIPE-AQUAPREP DISCHARGE TEED W.I BALL VALVES 13-6"SCH 40 PVC PIPE-INTERNAL CROSSOVER-FROM ILL PIPES MUST BE SET BELOW FROST LINE. TANK 2A TO TANK 2B iUCTION LINES MUST BE SCH 80 PVC. UNDERGROUND ELECTRICAL 15-6"SCH 40 PVC PIPE-TIRE SHINE DRAIN TO TANK 4 )O NOT INSTALL SCREENS ON FOOT VALVE. A-1'PVC CONDUIT-LOW WATER PROTECTION FLOAT SWITCH(FS-2)-TANK 3 16-6"SCH 40 PVC PIPE-EXTERNAL CROSSOVER FROM 'ONSULT ENGINEER FOR ELEVATIONS. TO MECHANICAL ROOM TANK 3 TO TANK 4 PIECE TANK IS REQUIRED B-i'PVC CONDUIT-FOR FUTURE USE-TANK 26 TO MECHANICAL ROOM 17-PIPE TO SANITARY SEWER HATCH TANK ELEVATION AS SHOWN. ABOVE GROUND ELECTRICAL r._a eueec ornmra iu i._i o.i a o�.,�ro.r�nuc Detail for reference only