HomeMy WebLinkAboutFire Sprinkler_MaterialsAddison Condos Bozeman, MT #22049 FIRE SPRINKLER PRODUCT DATA SHEET INDEX (Import material is acceptable) Description Size/Rating Manufacturer Model Number SPRINKLERS (SR – Standard Response / QR – Quick Response / SC – Standard Coverage / EC – Extended Coverage) Standard Spray Sprinkler Upright and Pendent, SC/QR ½” K=5.6 Tyco RFII Standard Spray Sprinkler Sidewall, SC/QR ½” K=5.6 Tyco TY-FRB Extended Spray Sprinkler Sidewall, SC/QR ½” K=5.6 Tyco EC5 Residential Coverage Sprinkler Pendent, QR ½” K = 4.9 Tyco LFII Residential Coverage Sprinkler Sidewall, QR ½” K = 4.2 Tyco LFII Dry Sprinkler, SC Sidewall, SR 1” K = 5.6 Victaulic VS1 OVERHEAD PIPING Black Steel - Standard Wall ASTM A-135/795 Type E, Grade A 1” – 2” Bullmoose Schedule 40 CPVC - Plastic Pipe ASTM F442, SDR 13.5 1” – 2” Tyco-Fire Blazemaster Schedule 40 FITTINGS CPVC - Plastic Pipe Sch 40 or Sch 80 1” – 2” Tyco-fire Blazemaster Screwed Fitting Galvanized Malleable Iron, 150 lb 1" - 2" Anvil International Class 150 Screwed Fitting Ductile Iron, 300 lb 1" – 2" Smith Cooper Class 300 Welded Outlet 1" - 2" Anvil International Weld-Miser Tee-Let Rigid Grooved Coupling 2” Victaulic 009N (EZ Style) Flexible Grooved Coupling 2” Victaulic 075 Grooved Fittings - Short Take-out 2” Victaulic Firelock HANGERS AND BRACING Offset Hanger 1” – 2” Afcon Fig 514 Sway Brace Fitting Model 4 1” – 2” Eaton Fig 4L Addison Condos Bozeman, MT #22049 Description Size/Rating Manufacturer Model Number Attachment Fitting Locking 1” Eaton Fig 980 VALVES Double Check Valve Assemblies 2” Deringer Model 20 Globe Valve ½” - 2" United Brass Model 125SUL Gauge Test Valve (3 - Way Globe Valve) ¼” United Brass Model 76 FireLock Check Valve-Grooved 2” Victaulic Model 717 Riser Manifold with pressure relief - Grooved 2” Tyco RM1 Ball Drip Valve 1/2” United Brass Fig 235 ELECTRIC DEVICES Horn/Strobe 24 VDC Potter SASH-24 Series FIRE DEPARTMENT CONNECTION FDC – Flush Mounted Brass 2½” x 2½” FPPI Item No. 09-650-00 FDC Wall Plate “Auto-Spkr” wording 2” IPS FPPI Item No. 09-508-00 Breakable Caps 2½” FPPI Item No. 09-522-00 MISCELLANEOUS Ceiling/Wall Plate - Chrome 2” FPPI Solid Wall Plate – Cast Iron 1/2” – 2” FPPI Spare Head Cabinet 6 FPPI Identification Sign FPPI Series RFII — 5.6 K-factor“Royal Flush II” Concealed Pendent SprinklersQuick & Standard Response, Standard Coverage Page 1 of 4 AUGUST 2020 TFP181 IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description The TYCO Series RFII 5.6 K-factor, “Royal Flush II” Concealed Pendent Sprinklers Quick Response (3-mm bulb) and Standard Response (5-mm bulb), are decorative sprinklers fea-turing a flat cover plate designed to conceal the sprinkler. These sprinklers are optimal for architecturally sensi-tive areas such as hotel lobbies, office buildings, churches, and restaurants. Each sprinkler includes a Cover Plate/Retainer Assembly and a Sprinkler/Support Cup Assembly. The separa-ble, two-piece assembly design pro-vides the following benefits: • Allows installation of the sprinklers and pressure testing of the fire pro-tection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. • Permits the removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protection system and remove sprinklers. • Provides for 1/2 in. (12,7 mm) of ver-tical adjustment to allow a measure of flexibility in determining the length of fixed piping to cut for the sprinkler drops. The Series RFII Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling installation or finish. The tip of the Pro-tective Cap can be used to mark the center of the ceiling hole into plaster board or ceiling tiles by gently pushing the ceiling product against the Pro-tective Cap. When ceiling installa-tion is complete, the Protective Cap is removed and the Cover Plate/Retainer Assembly is installed. As an option, the Series RFII Standard Response (5-mm bulb) “Royal Flush II” Concealed Pendent Sprinklers can be fitted with a silicone Air and Dust Seal. See Figure 5. The Air and Dust Seal is intended for sensitive areas where it is desirable to prevent air and dust from the area above the ceiling to pass through the cover plate. NOTICE The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and with the appli-cable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY3531 — 3 mm bulb TY3551 — 5 mm bulb Technical Data Sprinkler ApprovalsApprovals apply only to the service conditions indicated in the Design Criteria section. • TY3531 (3 mm Bulb) is UL Listed, C-UL Listed and NYC Approved (MEA 353-01-E) as Quick Response. • TY3531 (3 mm Bulb) is VdS Approved (Certificate No. G4090007). • TY3531 (3 mm Bulb) is FM and LPCB Approved (Ref. No. 094a/10) as Standard Response. Note: FM and LPCB do not approve concealed sprinklers for quick response. • TY3551 (5 mm Bulb) is UL Listed, C-UL Listed, FM Approved, LPCB Approved (Ref. No. 094a/9), and NYC Approved (MEA 353-01-E) as Standard Response. Approvals for Air and Dust SealUL and C-UL Listed for use with the RFII Standard Response Concealed Sprinkler (TY3551) Maximum Working PressureMaximum 250 psi (17,3 bar) by UL, C-UL, and NYC Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB Temperature Rating155°F (68°C) Sprinkler with 139°F (59°C) Cover Plate 200°F (93°C) Sprinkler with 165°F (74°C) Cover Plate TFP181 Page 2 of 4 Discharge Coefficient K= 5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Adjustment 1/2 in. (12,7 mm) Finishes See the Ordering Procedure section. Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Support Cup . . . . . . . . . . . . . . . . . . .Plated SteelGuide Pins . . . . . . . . . . . . . . . . . . Stainless SteelDeflector . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeCompression Screw . . . . . . . . . . . . . . . . . .Brass Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Glass Cap .....................Bronze or Copper Sealing Assembly ..Beryllium Nickel w/TEFLON Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass Retainer . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Ejection Spring . . . . . . . . . . . . . . Stainless Steel Design Criteria The TYCO Series RFII 5.6 K-factor, “Royal Flush II” Concealed Pendent Sprinklers are intended for fire protec-tion systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency; for example, UL Listing is based on NFPA 13 and VdS Approval is based on the CEA 4001. For more information on LPCB and VdS Approvals, contact Johnson Controls at the following office: Enschede, NetherlandsTelephone: 31-53-428-4444Fax: 31-53-428-3377 The Series RFII Concealed Pendent Sprinklers are only listed and approved with the Series RFII Concealed Cover Plates having a factory applied finish. NOTICE Do not use the Series RFII in applica-tions where the air pressure above the ceiling is greater than that below. Down drafts through the Sprinkler/Support Cup Assembly can delay sprinkler operation in a fire situation. Operation When exposed to heat from a fire, the Cover Plate, normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup Assembly. The Deflector — supported by the Guide Pins — then drops down to its operational position. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, activating the sprinkler and allowing water to flow. Installation The TYCO Series RFII 5.6 K-factor, “Royal Flush II” Concealed Pendent Sprinklers must be installed in accor-dance with this section. General InstructionsDo not install any bulb-type sprin-kler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diam-eter of the air bubble is approximately 1/16 in. (1,6 mm) for the 155°F (68°C) and 3/32 in. (2,4 mm) for the 200°F (93°C) temperature ratings. A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Sprinkler by under- or over-tightening the Sprin-kler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler only in the pendent position with the center-line of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step 4. Wrench-tighten the sprinkler using only the RFII Sprinkler Wrench. See Figure 3. Apply the RFII Sprinkler Wrench to the Sprinkler as shown in Figure 3. SPRINKLER/SUPPORT CUPASSEMBLY COVER PLATE/RETAINERASSEMBLY GUIDEPINS (2) DEFLECTOR (DROPPED POSITION) COMPRESSION SCREW DEFLECTOR SUPPORT CUP WITH ROLL FORMED THREADS FRAME 1/2" NPT CAP BULB SEALINGASSEMBLY RETAINER WITH THREAD DIMPLES EJECTION SPRING SOLDER TABS (3) COVER PLATE THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING FIGURE 1 MODEL RFII CONCEALED SPRINKLER ASSEMBLY TFP181 Page 3 of 4 A: 3-1/4 in. (82,6 mm)C: 2-3/8 to 2-5/8 in. (60,3 to 66,7 mm) B: 3/16 in. (4,8 mm)D: 1-3/4 to 2-1/4 in. (44,5 to 57,2 mm) Step 5. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. See Figure 4. The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or finish. You can also use the Protective Cap to locate the center of the clearance hole by gently pushing the ceiling material up against the center point of the Pro-tective Cap. NOTICE As long as the Protective Cap remains in place, the system is considered “Out of Service”. Step 6. After the ceiling has been completed with the 2-1/2 in. (63,5 mm) diameter clearance hole and in prep-aration for installing the Cover Plate/Retainer Assembly, remove and discard the Protective Cap. Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the Deflector does not move up and down freely, replace the entire Sprinkler. Do not attempt to modify or repair a damaged sprinkler. Step 7. When installing an Air and Dust Seal, see Figure 5; otherwise, proceed to Step 8. To attach the Air and Dust Seal, verify the angle of the outside edge of the seal is oriented accord-ing to Figure 5. Start the edge of the Retainer in the grooved slot of the Air and Dust Seal and continue around the retainer until the entire Air and Dust Seal is engaged. Step 8. Screw on the Cover Plate/Retainer Assembly until the Retainer, shown in Figure 2, or the Air and Dust Seal, shown in Figure 5, contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly so that it lifts a ceiling panel out of its normal position. If you cannot engage the Cover Plate/Retainer Assembly with the Support Cup or you cannot engage the Cover Plate/Retainer Assembly suf-ficiently to contact the ceiling, you must reposition the Sprinkler Fitting. COVER PLATEPROFILE DEPTHDIMENSION B 1/2" (12,7 mm)THREADEDADJUSTMENTD FACE OFSPRINKLERFITTING MANUFACTURERPRESET GAP3/32" (2,4 mm) FACEOF CEILING,RETAINING RINGMOUNTINGSURFACE SPRINKLERSUPPORT CUPASSEMBLY CLEARANCE HOLEDIAMETERDIMENSION C DEFLECTORIN DROPPEDPOSITION 3/16" to 11/16"(4,8 to 17,5 mm)REFERENCE COVER PLATERETAINERASSEMBLY COVER PLATEDIAMETERDIMENSION A CLEARANCEHOLE FRAME ARM SUPPORT CUP 7/8" (23 mm)SQUARE ACCEPTS1/2" SOCKETDRIVE ALIGNARROWS WITHFRAME ARMS FIGURE 2 SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS FIGURE 4 DISPOSABLE PROTECTIVE CAP FIGURE 3 RFII SPRINKLER WRENCH TFP181 Page 4 of 4 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Care and Maintenance The TYCO Series RFII 5.6 K-factor, “Royal Flush II” Concealed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this action. Absence of the Cover Plate/Retainer Assembly can delay sprinkler opera-tion in a fire situation. When properly installed, there is a nominal 3/32 in. (2,4 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler. If the ceiling requires repainting after sprinkler installation, ensure that the new paint does not seal off any of the air gap. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation Section. Exercise care to avoid damage to sprin-klers before, during, and after instal-lation. Replace sprinklers damaged by dropping, striking, wrench twist-ing, wrench slipping, or the like. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. See the Installation section. If you must remove a sprinkler, do not reinstall it or a replacement without reinstalling the Cover Plate/Retainer Assembly. If a Cover Plate/Retainer Assembly becomes dislodged during service, replace it immediately. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION such as NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor-dance with local requirements and/or national code. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name. Sprinkler/Support Cup AssemblySpecify: Series RFII (specify SIN), K=5.6, “Royal Flush II” Pendent Sprin-klers (specify) temperature rating, P/N* (specify): 155°F (68°C)200°F (93°C) TY3531 51-792-1-155 51-792-1-200 TY3551 51-790-1-155 51-790-1-200 * Use Suffix “I” for ISO 7-1 connection; for example, 51-792-1-155-I Separately Ordered Cover Plate/ Retainer Assembly:Specify: (temperature rating from below) Series RFII Concealed Cover Plate with (finish), P/N (specify). 139°F (59°C)(a) 165°F (74°C)(b) Grey White (RAL9002) . . . .56-792-0-135 56-792-0-165 Brushed Brass . .56-792-1-135 56-792-1-165 Brass . . . . . . . . . .56-792-2-135 56-792-2-165 Pure White (c) (RAL9010) . . . .56-792-3-135 56-792-3-165 Signal White (RAL9003) . . . .56-792-4-135 56-792-4-165 Jet Black (RAL9005) . . . .56-792-6-135 56-792-6-165 Brushed Chrome . . . . . . . .56-792-8-135 56-792-8-165 Chrome . . . . . . . .56-792-9-135 56-792-9-165 Custom . . . . . . . .56-792-X-135 56-792-X-165 (a) For use with 155°F (68°C) sprinklers. (b) For use with 200°F (93°C) sprinklers. (c) Eastern Hemisphere sales only. Sprinkler WrenchSpecify: RFII Sprinkler Wrench, P/N 56-000-1-075 Air and Dust SealSpecify: Air and Dust Seal, P/N 56-908-1-001 SUPPORTCUP SPRINKLER AIR AND DUST SEALCOVER PLATE LIP OF RETAINER FACE OFCEILING ORIENTSEALBEVEL ASSHOWNCOVERPLATERETAINERASSEMBLY FIGURE 5 OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551) Series TY-FRB — 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage Page 1 of 6 JULY 2018 TFP176 IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description The Series TY-FRB, 5.6 K-factor, Hori-zontal and Vertical Sidewall Sprinklers described in this data sheet are quick response -standard coverage, dec-orative 3 mm glass bulb type spray sprinklers designed for use in light and ordinary hazard, commercial occu-pancies such as banks, hotels, shop-ping malls, etc. They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Sidewall sprinklers are com-monly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable. The recessed version of the Series TY-FRB Horizontal Sidewall Sprinkler is intended for use in areas with a fin-ished wall. It uses a two-piece Style 10 Recessed Escutcheon with 1/2 in. (12,7 mm) of recessed adjustment or up to 3/4 in. (19,1 mm) of total adjustment from the flush sidewall position, or a two-piece Style 20 Recessed Escutch-eon with 1/4 in. (6,4 mm) of recessed adjustment or up to 1/2 in. (12,7 mm) of total adjustment from the flush side-wall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe nipples to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo-spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli-cable approval agencies, the testing is not representative of all possible cor-rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit-ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. NOTICE The Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori-ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions. Sprinkler Identification Numbers TY3331. . . . . . . . . . . . . . . . Horizontal TY3431. . . . . . . . . . . . . . . . . . Vertical Technical Data Approvals UL and C-UL Listed FM Approved LPCB Approved NYC Approved (Refer to Table A for complete approval information including corrosion resistant status.) Maximum Working Pressure Refer to Table B Discharge CoefficientK=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Temperature Ratings Refer to Table A TFP176 Page 2 of 6 Poly-Stainless Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeButton ................L316 Stainless Steel*Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GlassCompression Screw . . . . . L316 Stainless Steel*HSW Deflector . . . . . . . . . . . . . .Copper/BronzeSealing Assembly .Gold Plated Beryllium Nickel w/TEFLON*Type L316 stainless steel (UNS 31603) per ASTM A479/479M or BS EN 1008 WN1.4404.Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. FinishesSprinkler: Refer to Table C Recessed Escutcheon: Signal or Pure White, Jet Black, Grey Aluminum, Chrome Plated, or Brass Plated Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeButton . . . . . . . . . . . . . . . . . . . . . .Brass/CopperSealing Assembly ..Beryllium Nickel w/TEFLONBulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GlassCompression Screw . . . . . . . . . . . . . . . . .BronzeHSW Deflector . . . . . . . . . . . . . . . . . . . . .BronzeVSW Deflector . . . . . . . . . . . . . . . . . . . . . Copper Design Criteria The Series TY-FRB, 5.6 K-factor, Hor-izontal and Vertical Sidewall Sprin-klers are intended for fire protection systems designed in accordance with the standard installation rules rec-ognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM’s Loss Prevention Data Sheets). Only the Style 10 or 20 Recessed Escutcheon, as applicable, is to be used for recessed horizontal installations. 3 4 5 6 12 ** *Temperature rating isindicated on Deector Sealing Assembly Compression Screw Bulb Deector ButtonFrame 1/2"NPTWRENCHFLATS 7/16"(11,1 mm)NOMINALMAKE-IN 1-1/2"(38,1 mm) 2-3/16"(55,6 mm) ESCUTCHEON PLATE SEATING SURFACE DEFLECTOR HAT 1-13/16"(46,0 mm) 9/16"(14,3 mm) CENTERLINE OF SPRINKLER WATERWAY 2-7/8" DIA. (73,0 mm) STYLE 10RECESSEDESCUTCHEON - - - - -- 6 4 2 5 3 1 12 3 4 6 5 ** * * ** * Pipe thread connections per ISO 7-1 can be provided on special request Temperature rating isindicated on Deector Sealing Assembly ButtonFrame Bulb Deector Compression Screw ESCUTCHEON PLATE SEATING SURFACE 1-13/16"(46,0 mm) CENTERLINE OF SPRINKLER WATERWAY 2-7/8" DIA. (73,0 mm) STYLE 10 or 20RECESSEDESCUTCHEON 2-3/16"(55,6 mm) DEFLECTOR HAT 9/16"(14,3 mm)WRENCHFLATS 1-1/2"(38,1 mm) 7/16"(11,1 mm)NOMINALMAKE-IN 1/2"NPT -- - - - - 6 4 2 5 3 1 FIGURE 1 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS ALL FINISHES EXCEPT POLY-STAINLESS POLY-STAINLESS FINISH ONLY TFP176 Page 3 of 6 Installation The Series TY-FRB, 5.6 K-factor, Hori-zontal and Vertical Sidewall Sprinklers must be installed in accordance with this section. General InstructionsDo not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286°F (141°C) temperature ratings. A leak tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Higher levels of torque may distort the sprin-kler and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insuf-ficient adjustment in the escutcheon plate by under-or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. Series TY-FRB Horizontal and Vertical Sidewall Sprinkler InstallationThe Series TY-FRB Horizontal and Vertical Sidewall Sprinklers must be installed in accordance with the fol-lowing instructions. Step 1. Horizontal sidewall sprinklers are to be installed in the horizontal position with their centerline of water-way perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. Vertical sidewall sprinklers are to be installed in the pendent or upright position with the arrow on the Deflec-tor pointing away from the wall. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 5), With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. Series TY-FRB Recessed Horizontal Sidewall Sprinkler InstallationThe Series TY-FRB Recessed Horizon-tal Sidewall Sprinklers must be installed in accordance with this section. Step A. Recessed horizontal sidewall sprinklers are to be installed in the hori-zontal position with their centerline of waterway perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the Deflector is to face towards the ceiling. Step B. After installing the Style 10 or 20 Mounting Plate over the sprinkler threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 6). With reference to Figure 1, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprin-kler wrench flats. Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 10 or 20 Closure over the Series TY-FRB Sprin-kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The Series TY-FRB, 5.6 K-factor, Hori-zontal and Vertical Sidewall Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Spriklers ** *** * * PENDENT UPRIGHT SECTION CROSSSHOWNSHOWN 1-1/2" (38,1 mm) ESCUTCHEON PLATE SEATING SURFACE 2-3/16"(55,6 mm) WRENCHFLATS 1/2"NPT 7/16"(11,1 mm)NOMINALMAKE-IN ARROW MUST POINT AWAY FROM AND BE PERPENDICULAR TO THE BACK WALL SURFACE 7 2-3/16"(55,6 mm) 3 1 6 5 2 4 Pipe threadconnectionsper ISO 7-1 canbe provided onspecial request. Temperaturerating isindicated onDeector. 12 Sealing Assembly ButtonFrame--Bulb 3 - 4 - 6 -Deector CompressionScrew5- FLOW EjectionSpring7- FIGURE 2 5.6 K-FACTOR QUICK RESPONSE SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS TFP176 Page 4 of 6 WRENCH RECESS(END "A" USED FOR1/2" NPT MODELS) WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA 1" (25,4 mm) 1-1/4" (31,8 mm) CLOSURE 1/4" (6,4 mm) 1/2" (12,7 mm) 1/2±1/8"(12,7±3,2 mm) 2-7/8" DIA. (73,0 mm) MOUNTINGSURFACE SERIESTY-FRB MOUNTINGPLATE FACE OF SPRINKLER FITTING 2-1/4" DIA. (57,2 mm) 1/8"(3,2 mm) 2-7/8" DIA.(73,0 mm) MOUNTING SURFACE CLOSURE 1-1/4" (31,8 mm) 3/4" (19,1 mm) SERIES TY-FRB MOUNTING PLATE 3/4" (19,1 mm) 1/8" (3,2 mm) 1/4" (6,4 mm) FACE OFSPRINKLERFITTING 5/8±1/4"(15,9±6,4 mm) 2-1/4" DIA.(57,2 mm) FIGURE 5 W-TYPE 6 SPRINKLER WRENCH FIGURE 6 W-TYPE 7 RECESSED SPRINKLER WRENCH FIGURE 4 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON FIGURE 3 SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON TFP176 Page 5 of 6 damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprikler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result. Frequent visual inspections are rec-ommended to be initially performed for corrosion resistant coated sprin-klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprin-kler condition and the long term integ-rity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes. SPRINKLER FINISH (See Note 11) K TYPE TEMP. BULB LIQUID NATURAL BRASS CHROME PLATED POLYESTERc POLY- STAINLESSc LEAD COATED 5.6 1/2 in. NPT HORIZ. SIDEWALL (TY3331) 135°F (57°C)Orange 1, 2, 3, 4, 9, 10 1, 2, 3, 9 1, 2 1, 2, 3, 9 155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green 286°F (141°C)Blue RECESSED HORIZ. SIDEWALL (TY3331)a Figure 3 135°F (57°C)Orange 1, 2, 4, 9, 10 1, 2, 9 1, 2 N/A155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green RECESSED HORIZ. SIDEWALL (TY3331)b Figure 4 135°F (57°C)Orange 1, 2, 3, 4, 9 N/A N/A155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green 5.6 1/2 in. NPT VERTICAL SIDEWALL (TY3431) Installed Pendent or Upright 135°F (57°C)Orange 5, 6, 7, 8, 9 N/A 5, 6, 7, 9 155°F (68°C)Red 175°F (79°C)Yellow 200°F (93°C)Green 286°F (141°C)Blue NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflec- tor to ceiling distance. 2. Listed by Underwriters Laboratories Inc. for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflector to ceiling distance. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflector to ceiling distance. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a 4 to 6 in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 5. Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 6. Listed by Underwriters Laboratories for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies. 7. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies. 8. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06 & 007a/04) as Quick Response Sprinklers. 9. Approved by the City of New York under MEA 354-01-E. 10. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) at a 4 to 6 in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the thermal sensitivity of horizontal sidewall sprinklers. 11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. a. Installed with Style 10 (1/2 in. NPT) 3/4 in.Total Adjustment Recessed Escutcheon. b. Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon. c. Frame and deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS Series EC-5 — 5.6 K-factorExtended Coverage Horizontal Sidewall SprinklersQuick & Standard Response (Light Hazard) Page 1 of 6 AUGUST 2018 TFP298 IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description The Series EC-5, Extended Cover-age Horizontal Sidewall Sprinklers are extended coverage, decorative 3 mm glass bulb type spray sprin-klers designed for use in hydraulically calculated sprinkler systems in light hazard, commercial occupancies such as churches, restaurant seating areas, hotels, educational facilities, offices, etc. With their coverage up to 16 ft (4,9 m) wide by 24 ft (7,3 m) long and maximum deflector to ceiling distance of 18 in. (450 mm), they are designed for installation along a wall or the side of a beam and just beneath a smooth and level ceiling. Horizontal sidewall sprinklers are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction considerations, where piping across the ceiling is not desirable. The fast response thermal sensitiv-ity rating of the Series EC-5, 3 mm Bulb Type Sprinklers provides a quick response extended coverage (QREC) rating for many of the coverage areas detailed in Tables B and C. The recessed version of the Series EC-5 Extended Coverage Horizontal Sidewall Sprinkler utilizes a two-piece Style 50 Recessed Escutcheon. The Style 50 provides up to 3/8 in. (9,5 mm) of total adjustment from the flush side- wall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut. NOTICE The Series EC-5 Sprinklers described herein must be installed and main-tained in compliance with this docu-ment, as well as with the applicable standards of the National Fire Protec-tion Association, in addition to the stan-dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number TY3302 - EC HSW, 5.6KTY3302 is a redesignation for C3302. Technical Data ApprovalsUL and C-UL ListedFM and NYC Approved(Refer to Table A for complete approval information. The approvals apply to the service conditions indicated in the Design Criteria section.) Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection1/2 in. NPT Discharge Coefficient K = 5.6 GPM/psi½ (80,6 LPM/bar½) Temperature RatingsRefer to Table A Finishes Sprinkler: Refer to Table D Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeButton . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeSealing Assembly ..Beryllium Nickel w/TEFLONBulb .....................Glass (3 mm dia.)Compression Screw . . . . . . . . . . . . . . . . .BronzeDeflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The Series EC-5 Extended Coverage Horizontal Sidewall Sprinklers must be installed and utilized in Light Hazard Occupancies, under smooth level ceilings as outlined in the applicable installation standard recognized by the Approval Agency (e.g., UL recog-nizes NFPA 13, and FM recognizes the FM Loss Prevention Data Sheets). Only the Style 50 Recessed Escutcheon, as applicable, is to be used for recessed installations. TFP298 Page 2 of 6 Installation The Series EC-5 Sprinklers must be installed in accordance with this section. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm). A leak tight 1/2 in. NPT sprinkler joint should be obtained with a torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). A maximum of 21 lb-ft (28,5 N·m) of torque may be used to install sprinklers with 1/2 NPT connections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insuf-ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. Series EC-5 Sidewall SprinklerThe Series EC-5 Sidewall Sprinklers must be installed in accordance with the following instructions. Step 1. Horizontal sidewall sprinklers are to be installed with their center-line perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the deflector is to face towards the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figures 1, the W- Type 6 Sprinkler Wrench is to be applied to the sprinkler wrench flats. ** * * * ** 6 12345 2-1/16"(52,4 mm) 1-5/16" (33,3 mm) 5/16"(7,9 mm) SURFACE ESCUTCHEON PLATE SEATING 1-1/2" (38,1 mm) Sealing Assembly Compression Screw Frame-1 Button Deector - - - - -4 6 5 2 3 Bulb Components WRENCH FLATS 7/16" (11,1 mm) NOMINAL MAKE-IN DEFLECTOR HAT 1/2"NPT 7/16"(11,1 mm) CENTERLINEOF SPRINKLERWATERWAY Pipe thread connections per ISO 7-1 can be provided on special request. Temperature rating is indicated on Deector. MOUNTING 7/8" (22,2 mm) 1-1/8" (28,6 mm) CLOSURE MOUNTINGSURFACE 2-1/4" DIA.(57,2 mm) 3/16" (4,8 mm) 7/16" (11,1 mm) 3/32" (2,4 mm) 9/16±1/8"(14,2±3,2 mm) FACE OFSPRINKLERFITTING 2-7/8" DIA.(73,0 mm) FIGURE 1 SERIES EC-5 EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLERS (TY3302) FIGURE 2 SERIES EC-5 RECESSED EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER ASSEMBLY WITH TWO-PIECE 3/8 INCH TOTAL ADJUSTMENT STYLE 50 RECESSED ESCUTCHEON TFP298 Page 3 of 6 Series EC-5 Recessed Sidewall SprinklerThe Series EC-5 Recessed Sidewall Sprinklers must be installed in accor-dance with the following instructions. Step A. Horizontal sidewall sprinklers are to be installed with their center-line perpendicular to the back wall and parallel to the ceiling. The word “TOP” on the deflector is to face towards the ceiling. Step B. After installing the Style 50 sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 4). With reference to Figure 1, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprin-kler wrench flats. Step D. After the wall has been installed or the finish coat has been applied, slide on the Style 50 Closure over the Series EC-5 Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the wall. Care and Maintenance The Series EC-5 Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa-tion Section). The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan-dards of any other authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be con-tacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national code. K TYPE TEMP. RATING BULB LIQUID SPRINKLER FINISH NATURAL BRASS CHROME PLATED POLYESTERb,c 5.6 1/2 in. NPT EC-HSW (TY3302) 135°F (57°C)Orange 1, 2, 4 155°F (68°C)Red 1, 2, 3, 4 200°F (93°C)Green 1, 2, 4 5.6 1/2 in. NPT RECESSED EC-HSWa (TY3302) 135°F (57°C)Orange 1, 2, 4 155°F (68°C)Red 1, 2, 3, 4 200°F (93°C)Green 1, 2, 4 NOTE:1. UL Listed per Table B2. C-UL Listed per Table B3. FM Approved per Table C4. Approved by the City of New York under MEA 113-04-Ea. Installed with Style 50 Recessed Escutcheonb. Frame and deflector onlyc. Sprinkler is available in Polyester color finishes as indicated in Table D WRENCH RECESS(END "A" USEDFOR TY3302) WRENCHRECESS PUSH WRENCHIN TO ENSUREENGAGEMENTWITH SPRINKLERWRENCHING AREA FIGURE 3 W-TYPE 6 SPRINKLER WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH TABLE A LABORATORY LISTINGS AND APPROVALS(REFER TO THE DESIGN CRITERIA SECTION) TFP298 Page 4 of 6 5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302) AND RECESSED HORIZONTAL SIDEWALL SPRINKLER (TY3302) Response Rating Coverage Area1 Ft x Ft (m x m) Minimum Flow2 GPM (LPM) Minimum Pressure2 PSI (BAR) Deflector-to- Ceiling Distance3 In. (mm) Sprinkler Temperature Rating °F Minimum Spacing4 Ft (m) Quick 16 x 16 (4,6 x 4,9)26 (98)21.6 (1,48)4 to 18 (100 to 450)135, 155 8 (2,4) Quick 16 x 16 (4,6 x 4,9)26 (98)21.6 (1,48)4 to 12 (100 to 300)200 8 (2,4) Quick 16 x 18 (4,9 x 5,5)29 (110)26.8 (1,85)4 to 18 (100 to 450)135, 155 8 (2,4) Quick 16 x 20 (4,9 x 6,1)32 (121)32.7 (2,25)4 to 18 (100 to 450)135, 155 8 (2,4) Standard 16 x 18 (4,9 x 5,5)29 (110)26.8 (1,85)4 to 12 (100 to 300)200 8 (2,4) Standard 16 x 20 (4,9 x 6,1)32 (121)32.7 (2,25)4 to 12 (100 to 300)200 8 (2,4) 5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302) NON-RECESSED Quick 16 x 22 (4,6 x 6,7)36 (136)41.3 (2,85)4 to 18 (100 to 450)135 8 (2,4) Standard 16 x 24 (4.9 x 7,3)39 (148)48.5 (3,34)4 to 18 (100 to 450)135 8 (2,4) NOTE: 1. Backwall (where sprinkler is located) by sidewall (length of throw). 2. Requirement is based on minimum flow in GPM from each sprinkler. The indicted residual pressures are based on the nominal K-factor. 3. The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figures 1 and 2). 4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. 5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302) Response Rating Coverage Area1 Ft x Ft (m x m) Minimum Flow2 GPM (LPM) Minimum Pressure2 PSI (BAR) Deflector-to- Ceiling Distance3 In. (mm) Sprinkler Temperature Rating °F Minimum Spacing4 Ft (m) Quick 16 x 16 (4,6 x 4,9)26 (98)22 (1,51)4 to 12 (100 to 300)155 8 (2,4) Quick 16 x 18 (4,9 x 5,5)30 (114)29 (2,00)4 to 12 (100 to 300)155 8 (2,4) Quick 16 x 20 (4.9 x 6,1)33 (125)35 (2,41)4 to 12 (100 to 300)155 8 (2,4) NOTE:1. Backwall (where sprinkler is located) by sidewall (length of throw).2. Requirement is based on maintaining both minimum flow and minimum residual pressure.3. The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figures 1 and 2).4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized. TABLE B UL AND C-UL LISTING DESIGN CRITERIA TABLE C FM APPROVED DESIGN CRITERIA TFP298 Page 5 of 6 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread ConnectionsSpecify: TY3302, 5.6 K-factor, (specify temperature rating), Series EC-5 Extended Coverage Horizontal Sidewall Sprinkler with (specify type of finish or coating), P/N (specify from Table D) Recessed Escutcheon:Specify: Style 50 Recessed Escutch-eon with (specify*) finish, P/N (specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench:Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Recessed Sprinkler Wrench, P/N 56-850-4-001 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE (RAL9010)1 POLYESTER 4 SIGNAL WHITE (RAL9003) POLYESTER 9 CHROME PLATED 1. Eastern Hemisphere sales only TEMPERATURE RATING 135 135°F (57°C) 155 155°F (68°C) 200 200°F (93°C) SIN 053 5.6K EC HSW TY3302 P/N 51 – XXX – X – XXX TABLE D SERIES EC-5 EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLERS PART NUMBER SELECTION TFP298 Page 6 of 6 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Page 1 of 8 MARCH 2022 TFP445 Worldwide Contacts www.tyco-fire.com IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Scan the QR code or enter the URL in a web browser to access the most up-to-date electronic version of this document. Data rates may apply. docs.jci.com/tycofire/series-lfii- res-4_2-k-con-hori-side-wet Series LFII Residential4.2 K-factor Concealed Horizontal Sidewall SprinklerWet Pipe Systems General Description The TYCO Series LFII Residential 4.2 K-factor Concealed Horizontal Side-wall Sprinkler (TY2324) is a decorative, fast response, fusible link sprinkler designed for use in residential occu-pancies such as homes, apartments, dormitories, and hotels. The Series LFII Concealed Horizontal Sidewall Sprin-kler is intended for use in the following scenarios: • Wet pipe residential sprinkler sys-tems for one- and two- family dwell-ings and mobile homes per NFPA 13D • Wet pipe residential sprinkler sys-tems for residential occupancies up to and including four stories in height per NFPA 13R • Wet pipe sprinkler systems for the residential portions of any occu-pancy per NFPA 13 The Series LFII Concealed Horizontal Sidewall Sprinkler is intended for use in areas with finished walls, and provides ¼ in. (6,4 mm) of recessed adjustment. The adjustment reduces the accuracy to which the pipe nipples to the sprin-klers must be cut. The Series LFII Concealed Horizontal Sidewall Sprinkler has been designed with heat sensitivity and water distri-bution characteristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. NOTICE The Series LFII Concealed Horizontal Sidewall Sprinkler described herein must be installed and maintained in compliance with this document and the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor-mance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY2324Technical Data Approvals UL and C-UL Listed (for use with wet pipe systems) Certified to all requirements of NSF/ANSI 61 See the Design Criteria section for details on these approvals. Maximum Working Pressure175 psi (12,1 bar) Discharge Coefficient K=4.2 gpm/psi½ (60,5 lpm/bar½) Temperature Rating 160°F (71°C) Sprinkler with 139°F (59°C) Cover Plate Note: The maximum ambient ceiling tem-perature for the ordinary temperature con-figuration is 100°F (38°C). Horizontal Adjustment ¼ in. (6,35 mm) FinishesSee the Ordering Procedure section Physical CharacteristicsBody . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BrassBridge . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeSealing Assembly ..Beryllium Nickel w/TEFLONSoldered Link Halves . . . . . . . . . . . . . . . . NickelCompression Screw . . . . . . . . . . Stainless SteelTrepan . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BrassDeflector . . . . . . . . . . . . . . . . . . . . . . . . . CopperDeflector Guide Pin . . . . . . . . . . . Stainless SteelPlug .........................PolyethyleneLever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeRetainer ................Copper Plated SteelCover Plate . . . . . . . . . . . . . . . . . . . . . . . CopperCover Plate Ejection Spring . . . . Stainless Steel TFP445 Page 2 of 8 1 –Body 6 –Deflector Guide Pin 11 –Plug 16 –Retainer 2 –1/2 in. NPT 7 –Frame 12 –Lever 17 –Retainer Friction Grip 3 –Wrenching Notch 8 –Button 13 –Compression Screw 18 –Cover Plate Solder Tab 4 –Sprinkler Waterway 9 –Sealing Assembly 14 –Link 19 –Cover Plate 5 –Deflector 10 –Bridge 15 –Protective Cap 20 –Cover Plate Ejection Spring SPRINKLERASSEMBLY COVER PLATEASSEMBLY 1 4 9 2 3 8 7 6 15 14 12 11 13 10 5 19 16 17 18 20 CENTERLINE OF SPRINKLER WATERWAY MOUNTING SURFACE TOP OFDEFLECTOR OPERATEDCOVER PLATEASSEMBLY OPERATED SPRINKLER DEFLECTORIN OPERATEDPOSITION 7/16"(11,1 mm) 7/16"(11,1 mm)7/16" (11,3 mm) MIN. 11/16" (17,5 mm) MAX. FIGURE 1 SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER ASSEMBLY AND FEATURES FIGURE 2 SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER OPERATED CONDITION TFP445 Page 3 of 8 Operation When exposed to heat from a fire, the Cover Plate, which is soldered to the Retainer Ring at three points, falls away to expose the Sprinkler Assembly. The link’s solder melts when exposed to heat. When the rated temperature is reached, the melted solder releases the link, activating the sprinkler and allow-ing water to flow. Design Criteria The Series LFII Concealed Horizon-tal Sidewall Sprinkler is UL and C-UL Listed for installation in accordance with the following criteria. Residential Sprinkler Design GuideWhen conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur-er’s recommendations that may be acceptable to the local authority having jurisdiction. Ceiling TypesSmooth flat horizontal, beamed, or sloped, in accordance with the 2019 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin-kler flow rates are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A as a function of deflector to ceiling distance and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft² over the “design area” comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applica-ble for residential sprinklers as well as with the obstruction criteria described within the TYCO Technical Data Sheet TFP490. Operational SensitivityIn addition the top-of-deflector-to-ceiling distance is to be within the range (see Table A) being hydraulically calculated. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the width of the coverage area (see Table A) being hydraulically calcu-lated, for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 16 ft for a 16 ft x 18 ft coverage area. Maximum Coverage Area Width x Length ft x ft (m x m) Maximum Spacingft (m) Wet Pipe System Minimum Flow and Residual Pressure Ordinary Temp. Rating 160°F (71°C)Top-of- Deflector-to- Ceiling Distance Center-of- Sprinkler-to- Ceiling Distance Minimum Spacing ft (m) Flow gpm (lpm) Pressure psi (bar) 12 x 12 (3,7 x 3,7)12 (3,7)12 (45,4)8.2 (0,57) 4 in. to 6 in.4-7/16 in. to 6-7/16 in. 8 (2,4) 14 x 14 (4,3 x 4,3)14 (4,3)13 (49,2)9.6 (0,66) 16 x 16 (4,9 x 4,9)16 (4,9)18 (68,1)18.4 (1,27) 16 x 18 (4,9 x 5,5)16 (4,9)21 (79,5)25 (1,72) 12 x 12 (3,7 x 3,7)12 (3,7)13 (49,2)9.6 (0,66) 6 in. to 12 in.6-7/16 in. to 12-7/16 in. 14 x 14 (4,3 x 4,3)14 (4,3)15 (56,8)12.8 (0,88) 16 x 16 (4,9 x 4,9)16 (4,9)18 (68,1)18.4 (1,27) 16 x 18 (4,9 x 5,5)16 (4,9)22 (83,3)27.4 (1,89) TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP445 Page 4 of 8 3/16" (4,8 mm) 5/32" (4,0 mm) GAP * * FACE OFSPRINKLERFITTING SPRINKLER ASSEMBLY WRENCHING NOTCHES PROTECTIVE CAP CENTERLINEOF SPRINKLERWATERWAY MOUNTING SURFACE TOP OFDEFLECTOR CAP FULLY SEATED ON SPRINKLER WRENCHING FLANGE1/2" NPT OUTLET SPRINKLER ADAPTER FITTING 2-5/8" (66,7 mm) DIA. CLEARANCE HOLE 3-3/16" DIA. (81,0 mm) COVER PLATE WALLCENTERMARKINGTIP RETAINER FLANGE FLUSH AGAINST MOUNTING SURFACESPRINKLERBODY ENGAGEDBY RETAINERFRICTION GRIPS 1/4" (6,4 mm) ADJUSTMENT COVER PLATE ASSEMBLY 1-9/16" ± 1/8"(39,7 mm ± 3,2 mm) 7/16"(11,1 mm) NOTICE Factory-assembled protectivecap to remain attached duringsprinkler installation. Temporarily remove to verifycorrect deflector orientationand reinstall during wallfinishing. Remove only after installationis complete to allow propersprinkler performance. LDPE cap may berecycled accordingly. RETAINER COVER PLATEMUST FEATURE ONLYFACTORY FINISH,DO NOT PAINT FINISHED CEILING SPRINKLER BODY MARKINGINDICATES CORRECTDEFLECTOR ORIENTATION DEFLECTOR-TO-CEILINGDISTANCESEE TABLE A FIGURE 3 SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER INSTALLATION CRITERIA TFP445 Page 5 of 8 4" (102 mm) MAXIMUM TO MAINTAIN SPRINKLER STABILITY 2-1/8" (54 mm)REF. SPRINKLERAND COVER PLATEASSEMBLIES PIPE GUIDE BRACKET TAB FLUSH AGAINST FACE OF STUD 3/4" (DN20) BRACKET: 2-3/4" (70 mm) 1" (DN25) BRACKET: 2-9/16" (65 mm) (REF.) 3/4" (DN20) OR 1" (DN25) x 1/2" NPT CPVC SPRINKLER ADAPTER FITTING 3/4" (DN20)OR 1" (DN25)CPVC PIPE AND90° ELBOW 1" (DN25) CPVC PIPE AND REDUCING TEE OR STRAIGHT TEE AS APPLICABLE 3/4" (DN20)OR 1" (DN25)PIPE GUIDEBRACKET TYPICAL2 x 4 STUD FRAME AND SHEETROCK WALL STRUCTURE PIPE GUIDE BRACKETLOCATES SPRINKLER ANDCOVER PLATE ASSEMBLIESAT OPTIMAL DISTANCESFROM STUD SURFACES FIGURE 4 SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER PIPE GUIDE BRACKET WALL INSTALLATION TFP445 Page 6 of 8 SPRINKLERASSEMBLY CENTERLINEOF SPRINKLERWATERWAY SOFFITFINISHEDMOUNTINGSURFACE TOP OF DEFLECTOR COVER PLATE ASSEMBLY 7/16"(11,1 mm) FINISHEDCEILING DEFLECTOR -TO-CEILING DISTANCE SEE TABLE A SOFFIT DEPTH FINISHEDWALL SOFFIT DEPTH: 8” (203 mm) MAXIMUM PER NFPA 13, NFPA 13R AND NFPA 13D — or — 12” (305 mm) MAXIMUM DIRECTLY ABOVE CABINETS PER NFPA 13R AND NFPA 13D FIGURE 5 SERIES LFII RESIDENTIAL CONCEALED HORIZONTAL SIDEWALL SPRINKLER SOFFIT INSTALLATION CRITERIA TFP445 Page 7 of 8 Installation The Series LFII Concealed Horizontal Sidewall Sprinkler must be installed in accordance with this section. General InstructionsDamage to the fusible link assembly during installation can be avoided by handling the sprinkler by the body only. Do not apply pressure to the fusible link assembly. A leak-tight ½ in. NPT sprinkler joint should be obtained by applying a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N∙m). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in a Cover Plate by under- or over-tightening the sprin-kler. Re-adjust the position of the sprin-kler fitting to suit. Series LFII Residential Concealed Horizontal Sidewall SprinklersThe Series LFII Concealed Horizontal Sidewall Sprinkler must be installed in accordance with the following instructions. Step 1. To ensure that the sprinkler is located the correct distance from the face of the surface wall, use the pro-vided pipe guide, included with each sprinkler TY2324, and attach it to the 3/4 or 1 in. CPVC pipe and the 2 x 4 inside the wall, as shown in Figure 4. The sprinkler must only be installed with its centerline perpendicular to the back wall and parallel to the ceiling. Use a W-Type 37 Wrench for installa-tion. The wrench contains an outer flat surface reference that correlates with the sprinkler deflector orientation. The word “UP” on the installation wrench is to face towards the ceiling to ensure proper alignment. Note: The TYCO Sprinkler can be installed in both CPVC and standard steel piping/fittings. NOTICE Do not remove the Protective Cap until the Cover Plate Assembly is installed and/or the fire protection sprinkler system is ready to be placed in service. Step 2. With pipe thread sealant applied to the sprinkler threads, align the sprinkler alignment slot with the W-Type 37 Sprinkler Wrench alignment slot and engage by inserting the sprin-kler into the wrench cavity, fully seating the wrench shoulder against the sprin-kler wrenching flange. Hand tighten the sprinkler into the sprinkler fitting. Step 3. Once hand tight, attach an ½ in. (12,7 mm) drive to the sprinkler wrench and wrench tighten to ensure proper seal and alignment. Step 4. After the wall has been com-pleted with the nominal 2-5/8 in. (66,7 mm) diameter clearance hole and in preparation for installing the Cover Plate Assembly, remove and discard the Protective Cap. If the sprinkler has been damaged in any way including accidental over spray from finishing the wall, replace the entire sprinkler. NOTICE The sprinkler must be installed in neutral or negative pressure plenums only. Step 5. Push the Cover Plate Assem-bly onto the sprinkler, and as neces-sary, make the final adjustment of the Cover Plate with respect to the wall by pushing the Cover Plate Assembly until the retainer flange is flush against the wall. If it becomes necessary to remove the Cover Plate, it can be removed by gently pulling the Cover Plate Assembly way from the sprinkler body. WRENCHINGNOTCH PROTECTIVECAP PROTECTIVECAP WRENCHKEY LFIISPRINKLER W-TYPE 37 SPRINKLER WRENCH WRENCHCAVITY SOCKET ACCEPTS 1/2" DRIVE WRENCH ALIGNMENT SLOT READILY ORIENTS WRENCH WITH SPRINKLER ALIGNMENT SLOT THREE WRENCH KEYS UNIQUELY SPACED TO ENGAGE SPRINKLER WRENCHING NOTCHES WRENCHALIGNMENTSLOT SPRINKLERALIGNMENTSLOT WRENCHSHOULDER SPRINKLER WRENCHING FLANGE WRENCHSHOULDERSEATED ONSPRINKLERWRENCHINGFLANGE WRENCH FLATACCOMMODATESLEVEL FOR PRECISEADJUSTMENT TODEFLECTORORIENTATIONAS NEEDED "UP" INDICATESTOP OF DEFLECTORAND CORRECTSPRINKLERORIENTATION 1/2" NPTOUTLETSPRINKLERADAPTERFITTING FIGURE 6 W-TYPE 37 SPRINKLER WRENCH TFP445 Page 8 of 8 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a trademark of The Chemours Company FC, LLC; SHERWIN-WILLIAMS is a registered trademark of SWIMC LLC 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Note: A Cover Plate Assembly not ade-quately engaging the sprinkler body, that is not securely attached, indicates the sprinkler is positioned at a distance from the mounting surface greater than is described if Figure 3. A Cover Plate Assembly fully engaged on the sprin-kler body while the retainer flange is not in contact with the wall indicates the sprinkler is positioned at a distance from the mounting surface lesser than described in Figure 3. If either condi-tion is encountered when attempting to install the Cover Plate Assembly, the sprinkler fitting must me repositioned. Care and Maintenance The Series LFII Concealed Horizontal Sidewall Sprinkler must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes. When properly installed, there is a nominal 5/32 in. (4,0 mm) air gap between the lip and the Cover Plate and the wall, as shown in Figure 3. This air gap is necessary for the proper opera-tion of the sprinkler. If the wall is to be repainted after installation of the sprin-kler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted cover plates must not be repainted. They should be replaced if necessary, by factory painted units. Non-factory applies paints may adversely delay or prevent sprinkler operation in the event of a fire. If removal of the Cover Plate is neces-sary relative to the enclosure, be con-scious not to be too forceful, where separation may result. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modi-fied sprinklers must be replaced. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. If a sprinkler must be removed, do not reinstall it or a replacement without reinstalling the Cover Plate Assembly. If a Cover Plate Assembly becomes dislodged during service, replace it immediately. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or otherwise altered after leaving the factory. Modi-fied or over heated sprinklers must be replaced. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. If a sprinkler must be removed, do not reinstall it or a replacement without reinstalling the Cover Plate Assembly. If a Cover Plate Assembly becomes dislodged during service, replace it immediately. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler AssemblySpecify: Series LFII (TY2324), K=4.2, Residential Horizontal Sidewall Sprin-kler, without Cover Plate Assembly, P/N 50-520-1-160 Note: Sprinkler and Cover Plates are separately ordered. See below for Cover Plate ordering information. Cover Plate Assembly (Separately Ordered)Specify: Series LFII Concealed Sprin-kler Cover Plate Assembly, (specify finish), P/N (specify): Ivory (RAL1015) . . . . . . . . . . . . . . .56-204-0-135Beige (RAL1001) . . . . . . . . . . . . . .56-204-2-135Pure White (RAL9010)* . . . . . . . . .56-204-3-135Signal White (RAL9003)** . . . . . . .56-204-4-135Grey White (RAL9002). . . . . . . . . .56-204-5-135Brown (RAL8028). . . . . . . . . . . . . .56-204-6-135Black (RAL9005) . . . . . . . . . . . . . . 56-204-7-135Brushed Brass................56-204-8-135Brushed Chrome . . . . . . . . . . . . . .56-204-9-135Custom Paint .................56-204-X-135 *Eastern Hemisphere sales only **Previously known as Bright White Note: All Custom Cover Plates are painted using SHERWIN-WILLIAMS Interior Latex Paint. Contact Johnson Controls Customer Service with any questions related to custom orders. Sprinkler WrenchSpecify: W-Type 37 Sprinkler Wrench, P/N 56-320-1-015 Pipe Guide BracketPipe Guide Bracket accessory for sprinkler installation adjacent to framing member such as 2 x 4 within wall structure, includes mounting screws. Specify: Pipe Guide Bracket, (specify) Size, P/N (specify): 3/4 in. (DN20). . . . . . . . . . . . . . . . . . .91-520-1151 in. (DN25) ..................91-520-1-117 Page 1 of 4 JUNE 2022 TFP446 Worldwide Contacts www.tyco-fire.com IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Scan the QR code or enter the URL in a web browser to access the most up-to-date electronic version of this document. Data rates may apply. docs.jci.com/tycofire/series-lfii- res-4_9-k-con-pen-flat-wet Series LFII Residential4.9 K-factor Concealed Pendent SprinklerFlat Plate, Wet Pipe System General Description The TYCO Series LFII Residential 4.9K Concealed Pendent Sprinklers (TY2534) are decorative, glass bulb sprinklers, available in both ordinary 155°F (68°C) and intermediate 200°F (93°C) temperature rated configura-tions. They are designed for use in res-idential occupancies such as homes, apartments, dormitories, and hotels. The cover plate assembly conceals the sprinkler operating components above the ceiling. The flat profile of the cover plate provides the optimum aes-thetically appealing sprinkler design. In addition, the concealed design of the Series LFII Residential Concealed Pendent Sprinklers provides 3/4" (19,1 mm) vertical adjustment. This adjust-ment provides a measure of flexibility when cutting fixed sprinkler drops. The Series LFII Residential Concealed Pendent Sprinklers are intended for use in the following scenarios: • Wet pipe residential sprinkler sys-tems for one and two family dwell-ings and mobile homes per NFPA 13D • Wet pipe residential sprinkler sys-tems for residential occupancies up to and including four stories in height per NFPA 13R • Wet pipe sprinkler systems for the residential portions of any occu-pancy per NFPA 13 The Series LFII Residential Concealed Pendent Sprinklers have been designed with heat sensitivity and water distri-bution characteristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. The Series LFII Residential Con-cealed Pendent Sprinklers (TY2534) are shipped with a Disposable Protec-tive Cap. The Protective Cap is tem-porarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is being installed or finished. The tip of the Pro-tective Cap can also be used to mark the center of the ceiling hole into the plaster board, ceiling tiles, and so on, by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Pro-tective Cap is removed and the Cover Plate Assembly is installed. NOTICE The Series LFII Residential Concealed Pendent Sprinklers (TY2534) described herein must be installed and main-tained in compliance with this docu-ment and with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY2534 Technical Data ApprovalsUL and C-UL Listed Australian WaterMark Certified The TYCO Series LFII Residential Concealed Pendent Sprinklers are Listed only when installed with LFII Concealed Cover Plates having factory-applied finishes. Sprinklers and Cover Plates are separately ordered. See the Ordering Procedure section for more information. Maximum Working Pressure 175 psi (12,1 bar) TFP446 Page 2 of 4 Discharge CoefficientK=4.9 GPM/psi½ (70,6 LPM/bar½) Temperature Rating Ordinary 155°F (68°C) Sprinkler 139°F (59°C) Cover Plate Note: Maximum Ambient Ceiling Tempera-ture for the ordinary temperature configura-tion is 100°F (38°C). Intermediate 200°F (93°C) Sprinkler 165°F (74°C) Cover Plate Note: Maximum Ambient Ceiling Tempera-ture for the intermediate temperature con-figuration is 150°F (65°C). Vertical Adjustment3/4 in. (19,1 mm) Finishes See the Ordering Procedure section Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .BrassSupport Cup . . . . . . . . . . . . . . . . . . .Plated SteelGuide Pins . . . . . . . . . . . . . . . . . Stainless SteelDeflector . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeCompression Screw . . . . . . . . . . . . . . . . . .BrassBulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .GlassButton ...................Phosphor BronzeSealing Assembly ..Beryllium Nickel w/TEFLONCover Plate . . . . . . . . . . . . . . . . . . . . . . . . .BrassRetainer . . . . . . . . . . . . . . . . . . . . . .Plated SteelCover Plate Ejection Spring . . . . Stainless SteelBridge . . . . . . . . . . . . . . . . . . . . . . . . . . . .BronzeOperation When exposed to heat from a fire, the Cover Plate, normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup Assembly. The Deflector, supported by the Guide Pins, then drops down to its operated position. Maximum Coverage Area 1 ft x ft (m x m) Maximum Spacingft (m) Temperature Rating WET PIPE SYSTEM Minimum Flow and Residual Pressure 2, 3 Flow GPM (LPM) Pressure psi (bar) Deflector to Ceiling Installation Type Minimum Spacing ft 12 x 12 (3,7 x 3,7)12 (3,7) 155°F (68°C), 200°F (93°C) 13 (49,2)7.0 (0,48)Smooth Ceilings 3/8 to 1 1/8 in. Beamed Ceilings per NFPA 13D or 13R, or 13. Installed in beam 3/8 to 1 1/8 in. below bottom of beam Concealed 8(2,4) 14 x 14 (4,3 x 4,3)14 (4,3)13 (49,2)7.0 (0,48) 16 x 16 (4,9 x 4,9)16 (4,9)13 (49,2)7.0 (0,48) 18 x 18 (5,5 x 5,5)18 (5,5)17 (64,3)12.0 (0,83) 20 x 20 (6,1 x 6,1)20 (6,1)20 (75,7)16.7 (1,15) Notes:1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated.2. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic Design under the Design Criteria section.3. For NFPA 13 residential applications, the greater of 0.1 GPM/ft² over the design area or the flow in accordance with the criteria in this table must be used. SPRINKLER ASSEMBLY COVER PLATE ASSEMBLY COVER PLATE EJECTIONSPRING DIMPLES WITH THREADRETAINER ASSEMBLY SEALING COMPRESSION SCREW POSITION) (OPERATEDDEFLECTOR FLUSH WITHSURFACE IS SUPPORT CUP UNTIL THREAD INTO SOLDER TAB CEILING DEFLECTOR (1/2" NPT)FRAME FLATS WRENCHSPRINKLER ROLL FORMED THREADS CUP WITHSUPPORT BUTTON GUIDE PIN MOUNTING BULB BRIDGE FIGURE 1 SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY2534) TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER (TY2534) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TFP446 Page 3 of 4 The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, activating the sprinkler and allowing water to flow. Design Criteria The TYCO Series LFII Residential Con-cealed Pendent Sprinklers (TY2534) are UL and C-UL Listed for installation in accordance with this section. Note: When conditions exist that are outside the scope of the provided cri-teria, refer to the Residential Sprinkler Design Guide TFP490 for the manu-facturer's recommendations that may be acceptable to the authority having jurisdiction. Ceiling TypesSmooth flat horizontal, beamed, or sloped in accordance with NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprin-kler flow rates are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Table A as a function of temperature rating and the maximum allowable coverage area • A minimum discharge of 0.1 GPM/ft² over the design area comprised of the four most hydraulically demand-ing sprinklers for actual coverage areas protected by the four sprinklers Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational SensitivityThe sprinklers are to be installed rela-tive to the ceiling mounting surface as shown in Figure 2. Sprinkler SpacingThe minimum spacing between sprin-klers is 8 ft (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (see Table A) being hydraulically calcu-lated, for example, maximum 12 ft for a 12 ft x 12 ft coverage area, or 20 ft for a 20 ft x 20 ft coverage area. The Series LFII must not be used in applications where the air pres-sure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Installation The TYCO Series LFII Residential Con-cealed Pendent Sprinklers (TY2534) must be installed in accordance with this section. General InstructionsDo not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb, With the sprin-kler held horizontally, a small air bubble should be present. A 1/2 in. NPT sprinkler joint should be obtained with a minimum to maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N·m). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Cover Plate Assembly by under-or over- tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Step 1. The sprinkler must only be installed in the pendent position and with the centerline of the sprinkler per-pendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant applied to the pipe threads and using the W-Type 42 Wrench shown in Figure 3, position the wrench recess to first straddle the deflector guide pins from the side and then push the wrench into 3-1/4" DIA.(82,6 mm)PROTECTIVE CAP DISPOSABLE SPRINKLER OPERATED ASSEMBLYSUPPORT CUP SPRINKLER- THREADEDADJUSTMENT 3/4" (19,1 mm) DEFLECTOR IN OPERATED POSITIONTIP 1-5/16" (33,3 mm) 9/16" (14,3 mm) FACE OF SPRINKLERFITTING (2,4 mm)3/32" GAP 5/32"(4,0 mm) SURFACEMOUNTING 2-1/2" DIA.(63,5 mm) COVER- ASSEMBLYRETAINER SPRINKLER-SUPPORT CUPASSEMBLY 2-1/8"±3/8" ±9,5 mm) (54,0 mm RETAINER COVER PLATE RECESS WRENCH DRIVE SOCKET 1/2" SQUARE FIGURE 2 SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER (TY2534) INSTALLATION DIMENSIONS, PROTECTIVE CAP, AND ACTIVATED DEFLECTOR FIGURE 3 W-TYPE 42 SPRINKLER WRENCH TFP446 Page 4 of 4 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a trademark of The Chemours Company FC, LLCSHERWIN-WILLIAMS is a registered trademark of SWIMC LLC 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. the support cup to engage the sprin-kler wrench flats. Rotate clockwise to tighten the Sprinkler/Support Cup Assembly into the fitting. The W-Type 42 Wrench will accept a 1/2 in. ratchet drive. Note: Do not engage the sprinkler frame arms by the wrench, engage only the sprinkler wrench flats. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec-tive Cap helps prevent damage to the Deflector and Guide Pins during ceil-ing installation and/or during applica-tion of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap. Note: As long as the protective Cap remains in place, the system is consid-ered to be “Out Of Service.” Step 5. After the ceiling has been completed with the 2 1/2 in. (63 mm) diameter clearance hole and in prep-aration for installing the Cover Plate Assembly, remove and discard the Pro-tective Cap, and verify that the Deflec-tor moves up and down freely. If the sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 6. Push on the Cover Plate Assembly until its flange comes in con-tact with the ceiling. Do not continue to push on the Cover Plate Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance The TYCO Series LFII Residential Con-cealed Pendent Sprinklers (TY2534) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Absence of a Cover Plate may delay the sprinkler operation in a fire situation. When properly installed, there is an air gap between the lip of the Cover Plate and the ceiling. The Cover Plate assembly has a nominal 3/32 (2,4 mm) air gap, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situ-ation. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not seal off any of the air gap. Factory painted Cover Plates must not be repainted. They should be re placed, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied or over heated sprinklers must be replaced. Care must be exercised to avoid damage before, during, and after instal-lation. Sprinklers damaged by drop-ping, striking, wrench twist/slippage, or the like, must be replaced. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, for example, NFPA 25, in addition to the standards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor-dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N). Sprinkler AssembliesSpecify: Series LFII (TY2534) 4.9K Res-idential Concealed Pendent Sprinkler, P/N (specify): 155°F (68°C)..................51-549-1-155200°F (93°C) .................51-549-1-200 Note: Sprinkler and Cover Plates are separately sold. See below for Cover Plate ordering information. Cover Plate AssembliesSpecify: LFII Concealed Sprinkler Cover Plate Assembly, temperature rating (specify), (specify) finish, P/N (specify): 139°F (59°C)Ivory (RAL1015) . . . . . . . . . . . . . . .56-891-0-135Bright Chrome ...............56-891-9-135BBeige (RAL1001) . . . . . . . . . . . . . .56-891-2-135Pure White (RAL9010)* . . . . . . . . .56-891-3-135Signal White (RAL9003)** . . . . . . .56-891-4-135Grey White (RAL9002). . . . . . . . . .56-891-5-135Brown (RAL8028). . . . . . . . . . . . . .56-891-6-135Black (RAL9005) . . . . . . . . . . . . . . 56-891-7-135Brushed Brass................56-891-8-135Brushed Chrome . . . . . . . . . . . . . .56-891-9-135Custom Paint .................56-891-X-135 165°F (74°C) Ivory (RAL1015) . . . . . . . . . . . . . . .56-891-0-165 Bright Chrome ...............56-891-9-165B Beige (RAL1001) . . . . . . . . . . . . . .56-891-2-165 Pure White (RAL9010)* . . . . . . . . .56-891-3-165 Signal White (RAL9003)** . . . . . . .56-891-4-165 Grey White (RAL9002). . . . . . . . . .56-891-5-165 Brown (RAL8028). . . . . . . . . . . . . .58-891-6-165 Black (RAL9005) . . . . . . . . . . . . . . 56-891-7-165 Brushed Brass................56-891-8-165 Brushed Chrome . . . . . . . . . . . . . .56-891-9-165 Custom Paint .................56-891-X-165 * Eastern Hemisphere sales only** Previously known as Bright White Note: All Custom Cover Plates are painted using SHERWIN-WILLIAMS Interior Latex Paint. Contact Johnson Controls Customer Service with any questions related to custom orders. Sprinkler WrenchSpecify: W-Type 42 Sprinkler Wrench, P/N 56-000-1-079 TFP176 Page 6 of 6 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections: Specify: Series TY-FRB (specify SIN), (specify K-factor), (specify) Horizontal Sidewall or Vertical Sidewall Sprinkler, Standard Response, Standard Coverage, (specify) temperature rating, (specify) finish or coating, P/N (specify from Table C) Recessed EscutcheonSpecify: Style (10 or 20) Recessed Escutcheon with (specify*) finish, P/N (specify*) * Refer to Technical Data Sheet TFP770Sprinkler WrenchSpecify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 NOTES:1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York. SPRINKLER FINISH 1 NATURAL BRASS 2 POLY-STAINLESS GREY ALUMINUM (RAL9007)1 POLYESTER 3 PURE WHITE (RAL9010)2 POLYESTER 4 SIGNAL WHITE (RAL9003) POLYESTER 5 JET BLACK (RAL9005)3 POLYESTER 7 LEAD COATED 9 CHROME PLATED NOTES:1. Available for TY3331 only.2. Eastern Hemisphere sales only.3. Available in 155°F (68°C) or 200°F (93°C temperature rating only. SIN 378 HORIZONTAL SIDEWALL TY3331 375 VERTICAL SIDEWALL TY3431 TEMPERATURE RATINGS 135 135°F (57°C) 155 155°F (68°C) 175 175°F (79°C) 200 200°F (93°C) 286 286°F (141°C) P/N 57 – XXX – X – XXX SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED 5.6 1/2 in. NPT HORIZONTAL SIDEWALL (TY3331)250 PSI (17,2 BAR) or 175PSI (12,1 BAR) (SEE NOTE 1)RECESSED HORIZ. SIDEWALL (TY3331) VERTICAL SIDEWALL (TY3431)175 PSI (12,1 BAR) TABLE B MAXIMUM WORKING PRESSURE TABLE C PART NUMBER SELECTION SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. 1.0 PRODUCT DESCRIPTION Style • Pendent, Concealed Pendent, Horizontal Sidewall K Factor • 5.6/8.1 S.I. For system design purposes, no equivalent length calculations are required. Sprinkler Length • 38"/965 mm, 50"/1270 mm, 58"/1475 mm Nominal Orifice Size • ½"/13 mm Maximum Working Pressure • 175 psi/1200 kPa Factory Hydrostatic Test • 100% @ 500 psi/3450 kPa Minimum Operating Pressure • 7 psi/48 kPa Connections • To branch line (inlet) via 1"/25 mm NPT or 1" BSPT Minimum Bend Radius: • UL: 2"/51 mm • FM: 7"/178 mm Maximum Number of 90° Bends: • UL: 4 • FM: 2 bends for 38", 3 bends for 50", 4 bends for 58" Hazard Classifications • Light and Ordinary Hazard VicFlex™ Style VS1 Dry Sprinkler Models V3505, V3506, V3509, V3510, V3517, V3518 10.91 1 System No.Location Submitted By Date Spec Section Paragraph Approved Date 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 2.0 CERTIFICATION/LISTINGS Approvals/Listings Model V3505 V3505 V3506 V3506 V3509 V3509 V3510 V3517 V3518 Orifice Size (inches)1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2" Orifice Size (mm)13 13 13 13 13 13 13 13 13 Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 Nominal K Factor S.I.8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 Response Standard Standard Quick Quick Standard Standard Quick Standard Quick1 Deflector Type Pendent Recessed Pendent Recessed Hor. SW Rec. Hor. SW Hor. SW, Recessed Hor. Sidewall Conc. Pend.Conc. Pend. w/Clean room gasketApproved Temperature Ratings F°/C° FM 135/57 135/57 135/57 135/57 135/57 135/57 135/57 –135/57 155/68 155/68 155/68 155/68 155/68 155/68 155/68 –155/68 175/79 175/79 175/79 175/79 175/79 175/79 175/79 –175/79 200/93 200/93 200/93 200/93 200/93 200/93 200/93 –200/93 286/141 –––286/141 –––– UL 135/57 135/57 135/57 135/57 135/57 135/57 135/57 135/57 135/57 155/68 155/68 155/68 155/68 155/68 155/68 155/68 155/68 155/68 175/79 175/79 175/79 175/79 175/79 175/79 175/79 175/79 175/79 200/93 200/93 200/93 200/93 200/93 200/93 200/93 200/93 200/93 286/141 286/141 286/141 286/141 286/141 –286/141 –– 1 Model V3518 is a Standard Response FM sprinkler. 3.0 MATERIAL SPECIFICATIONS Deflector: Brass Bulb: Glass with glycerin solution Bulb Nominal Diameter: Quick Response: 3.0 mm Standard Response: 5.0 mm Split Spacers: Stainless steel Load Screw: Brass Pip Cap: Stainless steel Spring Seal Assembly: PTFE tape coated beryllium nickel and stainless steel Frame: Brass Flexible Hose: Stainless steel Collar/Weld Fitting: Stainless steel Gasket Seal: Victaulic EPDM Isolation Ring: Nylon Hose Fittings: Carbon steel, zinc-plated Inlet Fitting: Brass Outer Tube: Stainless steel Concealed Cup: Carbon steel, zinc-plated Brackets: Carbon steel, zinc-plated 3.1 ACCESSORIES SPECIFICATIONS Sprinkler Finishes: Standard: VC-250 White painted RAL 9010 2 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.0 DIMENSIONS Product Details and Optional Components Style VS1 Dry Sprinkler L B C D Sprinkler Length Overall Length (pendent) L Live Length B Outlet End Length C Maximum OD D inches mm inches mm inches mm inches mm inches mm 38 965 39.2 995 25.1 638 6.5 165 2.2 56 50 1270 51.2 1300 37.1 943 6.5 165 2.2 56 58 1475 59.2 1505 45.1 1145 6.5 165 2.2 56 NOTE • Add ½" to Overall Length and Outlet End Length for increased length of sidewall deflector Style VB1 Bracket 2.2"/ 54.6 mm* 2.768.6 mm"/ 2.25"/57.2 mm 3.6"/92.1 mm 4 x Ø .2"5.1 mm 1.0"/25.4 mm / *Note: Theoretical center point of sprinkler in bracket. Style VB2 Bracket Recessed Pendent, Suspended Ceilings Style VB3 Bracket Concealed Pendent, Suspended Ceilings Item Description Item Description 1 24"/610 mm or 48"/1220 mm Square Bar 1 24"/610 mm or 48"/1220 mm Square Bar 2 Patented 1-Bee Center Bracket 2 Patented 1-Bee Center Bracket 3 End Bracket 3 End Bracket 3 2 1 3 12 3 3 3 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.1 DIMENSIONS Sprinkler Finishes: Dimensions and Mounting Conditions: NOTE • Drawings are shown with 5/8" finished ceiling thickness. Adjustments to "B" and "C" dimensions will be required if finished ceiling thickness deviate from drawing. Recessed Pendent: B C D R Collar Finished ceiling face Escutcheon1"/25 mm Min. 1 ¾"/44 mm Max. 2 ¾"/ 70 mm 1"/25 mm /"/16 mm 2⁄"/75 mm Take-out Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 B 7 5/8/193 8 5/8/218 9 5/8/244 10 5/8/269 11 5/8/295 12 5/8/320 C 4 3/4/119 Ceiling Hole Diameter "D"2 – 2 3/8"/50 – 60mm NOTE • Dimensions are shown with 3/4" escutcheon at middle of height adjustment range. 4 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.2 DIMENSIONS B C C D Finished ceiling face 2¾"/70 mm 1"/ 25 mm 1"/25 mm Min. 1¾"/44 mm Max. Escutcheon Collar /"/ 16 mm 2⁄"/75 mm R Take-out Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 B 7 5/8/193 8 5/8/218 9 5/8/244 10 5/8/269 11 5/8/295 12 5/8/320 C 2/50 Ceiling Hole Diameter "D"2 – 2 3/8/50 – 60 NOTE • Dimensions are shown with 3/4" escutcheon at middle of height adjustment range. Recessed Pendent Alternative Bracket Location: 5 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.3 DIMENSIONS Sleeve and Skirt Pendent: B C D /"/ 16 mm Finished ceiling face 3⁄"/82 mm 2½"/64 mm Min.4"/102 mm Max. 1"/ 25 mm Skirt Sleeve 2¾"/ 70 mm R Hose Clearance Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 B 6 ½/163 7 ½/188 8 ½/213 9 ½/239 10 ½/264 11 ½/290 C 3 1/8/79 Ceiling Hole Diameter "D"1 3/4/44 – 2 1/8/54 4.4 DIMENSIONS Concealed Pendent: B C D R Finished ceiling face Cup R Ceiling cover plate with ¼" total adjustment. Shown at mid-range of adjustment. 3 ¼”/83 mm 2 ¾"/ 70 mm 1"/ 25 mm /"/16 mm Hose Clearance Chart Dimension inches/mm Minimum Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 B 9 ½/241 10 ½/267 11 ½/292 12 ½/318 13 ½/343 14 ½/368 C 6 1/4 /157 Ceiling Hole Diameter "D"2 5/8/67 – 2 3/4 /70 6 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.5 DIMENSIONS Concealed Pendent Alternative Bracket Location: B C D R Cup Finished ceiling face 2 ¾"/ 70 mm 1"/ 25 mm /"/16 mm 3 ¼"/83 mm Ceiling cover plate with ¼" total adjustment. Shown at mid-range of adjustment. Hose Clearance Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 B 9 1/8/231 10 1/8/257 11 1/8/282 12 1/8/307 13 1/8/333 14 1/8/358 C 3 1/2/89 Ceiling Hole Diameter "D"2 5/8/67 – 2 3/4/70 4.6 DIMENSIONS Sleeve and Skirt Sidewall: R B A Skirt Sleeve Exterior wall siding 2.70"/ 69 mm 1"/25 mm /"/16 mm(Siding thickness) 3⁄"/82 mm 3⁄"/79 mm Min. 3⁄"/98 mm Max. 1¾"/44 mm Min. Dia. 2½"/64 mm Max. Dia. Hole in wall Hose Clearance Chart Dimension inches/mm Minimum Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 A 6 1/2/163 7 1/2/188 8 1/2/213 9 1/2/239 10 1/2/264 11 1/2/290 B 3 1/8/79 Ceiling Hole Diameter "D"1 3/4/44 – 2 1/8/54 7 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.7 DIMENSIONS Recessed Sidewall: R A B Collar Exterior wallsiding Escutcheon 1⁄"/40 mm Min. 2⁄"/59 mm Max. 2"/51 mm Min. Dia. 2⁄"/60 mm Max. Dia. Hole in wall 2⁄"/59 mm 2.70"/69 mm 1"/25 mm /"/16 mm(Siding thickness) Hose Clearance Chart Dimension inches/mm Minimum Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 A 8/203 9/229 10/254 11/279 12/305 13/330 B 4 3/4/119 Ceiling Hole Diameter "D"2/51 – 2 3/8/60 4.8 DIMENSIONS Recessed Sidewall Alternative Bracket Location: R B A Collar Exterior wall siding Escutcheon 1⁄"/40 mm Min.2⁄"/59 mm Max. 2⁄”/59 mm ⁄"/16 mm (Siding thickness) 1"/25 mm 2.70"/ 69 mm 2"/51 mm Min. Dia. 2⁄"/60 mm Max. Dia. Hole in wall Hose Clearance Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 A 8/203 9/229 10/254 11/279 12/305 13/330 B 2/51 Ceiling Hole Diameter "D"2/51 – 2 3/8/60 8 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 4.9 DIMENSIONS VB2 Recessed Pendent: A 2.3"/58 mm Bracket Assembly Style VB2 /"/16 mmTypical ceiling tile Finished ceiling face Ceiling escutcheon with ¾"/19 mm total adjustment. Shown at maximum recess 24"/610 mm or 48"/1219 mm on Center Recessed Pendent See note See Chart 1.7"/43 mmTypical ceiling grid R Hose Clearance Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 A 6 1/2/163 7 1/2/188 8 1/2/213 9 1/2/239 10 1/2/264 11 1/2/290 NOTE • Victaulic VicFlex Style VB2 Bracket assemblies shall be used only with Style VS1 recessed pendent sprinklers. 4.10 DIMENSIONS VB3 Concealed Pendent: ASee Chart See note1.7"/43 mm Typical ceiling grid 3.0"/76 mm 5/8"/16 mm Typical ceiling tile Bracket Assembly Style VB3 R Finished ceiling face 24"/610 mm or 48"/1219 mm on Center Ceiling escutcheon with ¼"/6.5 mm total adjustment Concealed Pendent Hose Clearance Chart Dimension inches/mm Bend Radius "R"2/50 3/75 4/100 5/125 6/150 7/175 A 7 5/8/193 8 5/8/218 9 5/8/244 10 5/8/269 11 5/8/295 12 5/8/320 NOTE • Victaulic VicFlex Style VB3 Bracket assemblies shall be used only with Style VS1 concealed pendent sprinklers. 9 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 5.0 PERFORMANCE Freeze Protection Y Exterior Face of Fitting Heated Space Unheated Space Y Exterior Heated Space Unheated Space Face of Fitting Ambient Temperature Exposed to Discharge End of Sprinkler Exposed Minimum Barrel Length "Y" inches mm °F °C 40°F/4°C 50°F/10°C 60°F/16°C 40 4 0 0 0 0 0 0 30 -1 0 0 0 0 0 0 20 -7 4 100 0 0 0 0 10 -12 8 200 1 25 0 0 0 -18 12 300 3 75 0 0 -10 -23 14 350 4 100 1 25 -20 -29 14 350 6 150 3 75 -30 -34 16 400 8 200 4 100 -40 -40 18 450 8 200 4 100 -50 -46 20 500 10 250 6 150 -60 -51 20 500 10 250 6 150 NOTE • Exposed minimum barrel lengths are inclusive up to 30-mph/48-kph wind velocities. Maximum Allowable Number of Bends Sprinkler Length Maximum Allowable Number of 90° Bends at Maximum Allowable Number of 90° Bends at inches mm 2"/51mm Bend Radius for UL Listing 7"/178mm Bend Radius for FM Approval 38 965 4 2 50 1270 4 3 58 1475 4 4 10 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 6.0 NOTIFICATIONS WARNING • Read and understand all instructions before attempting to install any Victaulic® VicFlex™ products. • Wear safety glasses, hardhat, and foot protection. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on stainless steel components to confirm system life will be acceptable for the intended service. Failure to follow these instructions could cause improper sprinkler operation and product failure, resulting in death or serious personal injury and property damage. WARNING • Read and understand all instructions before attempting to install any Victaulic products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. • These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc. • The installer shall understand the use of this product and why it was specified for the particular application. • The installer shall understand common industry safety standards and potential consequences of improper product installation. • It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system and external environment. • The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on materials to confirm system life will be acceptable for the intended service. Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system failure, resulting in death or serious personal injury and property damage. 11 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 6.0 NOTIFICATIONS (CONTINUED) Important Installation Notes: 1. Shall be installed only in accordance with NFPA 13 Standard for the the Installation of Sprinkler Systems and applicable FM Data Sheets. 2. Install and tighten swivel hex nut at inlet of sprinkler fitting only. 3. Do not remove deflector or inlet end of sprinkler. Continuous Downward Slope ACCEPTABLE Inlet Outlet Heated Space Unheated Space Outlet Low Point UNACCEPTABLE Unheated Space Inlet Heated Space Continuous Downward Slope ACCEPTABLE Inlet OutletHeated Space Unheated Space Inlet Outlet Low Point UNACCEPTABLE Unheated SpaceHeated Space 12 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 6.0 NOTIFICATIONS (CONTINUED) FOR DRY SYSTEMS ONLY: • The Style VS1 Dry Sprinkler’s inlet shall be installed only into the outlet of a fitting (excluding elbows) or welded outlet that meets the dimensional requirements of ANSI B16.3 and ANSI B16.4, Class 125 and Class 150. Use a sample fitting to confirm proper engagement and to verify that there is no interference between the sprinkler and the fitting. Style VS1 Dry Sprinklers in an unheated space shall be installed with a continuous downward slope along its entire length from the branch line fitting to the sprinkler. No localized low points shall be present along the length of the Style VS1 Dry Sprinkler. Style VS1 Dry Sprinklers in an unheated space are not permitted to be installed into the top of the branch line piping. Style VS1 Dry Sprinklers shall be installed into the side or from the bottom of the branch line piping. In a heated space, if a portion of the Style VS1 Dry Sprinkler is installed from the top of a branch line and then extends into an unheated space, it shall be installed with a continuous downward slope along the entire length from the inside wall to the outlet of the sprinkler. No localized low points shall be present along the length of the sprinkler in the unheated space. Refer to the drawing below. Heated SpaceUnheated SpaceInlet Outlet Downward Slope FOR WET SYSTEMS ONLY: • DO NOT install Victaulic® VicFlex™ Style VS1 Dry Sprinklers into any threaded elbow, threaded-by-thread coupling, or fitting that interferes with thread penetration. The inlet of the Victaulic® VicFlex™ Style VS1 Dry Sprinkler SHALL NOT bottom out in the fitting. Use a sample fitting to confirm proper engagement. • To ensure unobstructed flow during operation, the Victaulic® VicFlex™ Style VS1 Dry Sprinkler shall be installed into a fitting that will prevent water and debris from accumulating at the dry sprinkler’s inlet. • Verify that the exposed minimum barrel length in the heated space is measured and maintained in accordance with the table on page 1. In a heated space, if a portion of the Style VS1 Dry Sprinkler extends into an unheated space, it shall be installed with a continuous downward slope along the entire length from the inside wall to the outlet end of the dry sprinkler. No localized low points shall be present along the length of the sprinkler in the unheated space. Refer to the drawing above. 13 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 7.0 REFERENCE MATERIALS ONE BEND TWO BENDS 90° Minimum bend radius Minimum bend radius Minimum bend radius 2X Minimum bend radius OR Minimum bend radius Minimum bend radius Minimumbend radius 2XMinimum bend radius Minimumbend radius OR NOTE For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torsional stress on the sprinkler. 14 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com 7.0 REFERENCE MATERIALS BillTo:ShipTo:TagEmailPhone No.Fax No.State/ProvinceCompany NameQuantity (as specied below):If units of dierent size, type or other option are required, please attach additional form(s) with their specication(s) separately.AddressOrder No.Company NameAddressState/ProvinceZip Code/Postal CodeZip Code/Postal CodeDateVicFlex™ Dry Sprinkler Model VS1––––––––––A43FClassStyleThreadDeectorStyleResponseK FactorTemperatureFinishRecessedEscutcheonMaterialCodeInchesEscutcheonStyle †380 = 38"500 = 50"580 = 58"3F = V35A4 = K5.6Q = QuickS = Std.3 = 1" NPT8 = 25 mm BSP12 = Recessed13 = Sleeve and Skirt15 = ConcealedA = 135°F/57°CC = 155°F/68°CE = 175°F/79°CF = 200°F/93°CJ = 286°F/141°CW = White Stainless SteelX = Stainless Steel0 = Concealed4 = WhiteN = VC-250 ‡B = PendentC = Horizontal SidewallP - ConcealedSize‡ VC-250 sprinkler nish sold standard on the VicFlex Dry Sprinkler Model VS1.15 victaulic.com 10.91 9374 Rev K Updated 12/2019 © 2019 Victaulic Company. All rights reserved. victaulic.com User Responsibility for Product Selection and SuitabilityEach user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end-use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms “Patented” or “Patent Pending” refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. NoteThis product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. TrademarksVictaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 7.0 REFERENCE MATERIALS (CONTINUED) 29.01: Victaulic Terms and Conditions of Sale I-VICFLEX.VS1: Victaulic® VicFlex™ Style VS1 Dry Sprinkler Installation Instructions 16 victaulic.com Installation Tyco®CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in accordance with Installation Hand- book IH-1900 dated June 2008. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stallingcontractor orproductmanufac- turer should be contacted relative to any questions. Automatic sprinkler systemsshouldbe inspected, tested, and maintained by a qualified Inspection Service in accord- ance with local requirements and/or national codes. NOTICE Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls, permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities andadvisethoseresponsibleformoni- toring proprietary and/or central sta- tion alarms. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeensubjecttomisuse,improper installation,corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes anypersontoassumeforit, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not beresponsiblefor sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer’s repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,specialorconsequentialdam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. Theforegoingwarrantyismadeinlieu of any and all other warranties, ex- press or implied, including warranties ofmerchantabilityandfitnessforapar- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Page2of2 TFP1915 © 2008 TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 General Description Tyco Fire & Building Products (TFBP) BlazeMaster CPVC Pipe and Fittings are designed exclusively for use in wet pipe automatic fire sprinkler systems. They are made from a specially devel- oped thermoplastic compound com- posed of post chlorinated polyvinyl chloride (CPVC) resin and state of the art additives. TFBP BlazeMaster CPVC products are easier to install than traditional steel pipe systems, and at the same time, provide superior heat resistance and strength as com- pared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapters are available to connect CPVC pipe to metallic pip- ing. All female pipe thread adapters have brass inserts for durability. Grooved adapters connect directly to grooved end valves and metallic pipe, with flexible grooved end couplings. WARNING Tyco Fire & Building Products (TFBP) BlazeMaster CPVC Pipe and Fittings described herein mustbe installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction.Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Sizes 3/4" to 3" Maximum Working Pressure 175 psi Approvals UL, FM, CUL, NSF, Dade County, LPCB, MEA, and the City of Los Ange- les. (Refer to IH-1900, Rev. 0, Janu- ary 2005 “Installation Instruction & Technical Handbook” for exact list- ing/approval information.) Manufacture Source U.S.A. Material •Pipe: ASTM F442, SDR 13.5 •Fittings: ASTM F438 (Sch. 40) and ASTM F439 (Sch. 80), ASTM F1970 Color Orange BlazeMaster ® CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet Page 1 of 6 TFP1915JANUARY, 2006 Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500 BlazeMaster®is a registered trademark of Noveon IP Holding Corp. Installation Tyco Fire and Building Products (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- ance with IH-1900, Rev. 0, January 2005“Installation Instruction &Techni- cal Handbook”. Care and Maintenance The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stallingcontractor orproductmanufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls, permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise thoseresponsibleformoni- toring proprietary and/or central sta- tion alarms. Page2of6 TFP1915 FIGURE 1 — PIPE DIMENSIONS 2" 1" 1-1/4" 1-1/2" 3/4" 2.375" 2.003" 1.315" 1.660" 1.900" 1.050" 1.101' 1.394" 1.598" 0.874" SIZE NOMINAL 2.200.84 0.67 0.44 1.08 1.41 0.26 0.42 0.54 0.18 3" 2-1/2" 3.500" 2.952" 2.875" 2.423" 4.831.87 3.261.26 10841260 1320 1339 1191 1213 5040 2835 2205 7875 1344720 15311215 O.D. AVERAGE lbs./ft. WEIGHTAVERAGE I.D.FILLED WEIGHT WATER lbs./ft. FT. OF PIPE PER LIFT WEIGHT PER LIFT lbs. TFP1915 Page3of6 FIGURE 2 — FITTING DIMENSIONS (Part 1 of 4) NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE PART NUMBER (T/O) T/O T/O 80004 80003 80002 TEE T/O 80001 80000 2" 1-1/4" 1-1/2" 3/4" 1" 1-3/8" 1-1/16" 7/8" 0.90 0.51 0.26 5/8" 11/16"0.19 0.11 REDUCING TEE 1-1/2" x 1-1/2" x 1-1/4" 80266 80267 80274 80264 80275 80261 80262 80263 80260 2" x 2" x 3/4" 2" x 2" x 1" 2" x 2" x 1-1/2" 1-1/2" x 1-1/2" x 1" 7/8" 1-1/8" 1-1/16" 7/8" 9/16" 1-1/2" x 1-1/2" x 3/4" 1-1/4" x 1-1/4" x 3/4" 1-1/4" x 1-1/4" x 1" 1" x 1" x 3/4" 5/8" 9/16" 3/4" 5/8" 1-3/8" 1-3/8" 1-3/8" 7/8" 9/16" 1" 1-1/16" 0.66 0.78 0.74 0.45 0.38 7/8"5/8" 9/16" 3/4" 1" 7/8" 5/8" 13/16" 0.23 0.36 0.26 0.16 YXx YxZ XZ 80132 3/4" x 3/4" x 1" 3/4" 3/4" 5/8"0.14 80133 9/16"1" x 3/4" x 3/4" 9/16"0.143/4" 80134 1" x 3/4" x 1" 3/4" 11/16" 3/4"0.17 80135 1-1/4" x 1" x 3/4" 5/8"5/8"0.2115/16" 80136 1-1/4" x 1" x 1" 3/4" 3/4" 15/16"0.22 15/16"1-1/4" x 1" x 1-1/4"80137 15/16"0.267/8" 80138 1-1/4" x 1-1/4" x 1-1/2"1" 1" 1" 0.43 80140 1-1/2" x 1-1/4" x 3/4" 9/16" 9/16"1" 0.36 1-1/2" x 1-1/4" x 1"80141 9/16" 9/16"0.381-1/16" 80265 3/4" 1-3/8"0.61 T/O T/O T/O X Y Z 7/8" 1-1/8" 1-1/16" 3/4" WEIGHT (lb.) T/O T/O T/O T/O CROSS & REDUCING CROSS 1-1/16" 80009 80010 80011 80013 80012 0.139/16" 1-5/16" 11/16" 15/16" 1.00 0.23 0.34 0.67 80006 80005 3" 2-1/2" 1-13/16" 1-9/16" 2.41 1.59 2-1/2" x 2-1/2" x 1-1/2" 80270 80269 80268 80272 80273 80271 3" x 3" x 1-1/2" 3" x 3" x 2" 3" x 3" x 2-1/2" 2-1/2" x 2-1/2" x 1-1/4" 1-13/16" 1-13/16" 1-13/16" 1-9/16" 1-9/16" 2-1/2" x 2-1/2" x 1" 1-9/16" 1-13/16" 1-13/16" 1-3/4" 1-9/16" 1-9/16" 1-9/16" 1-9/16" 2.28 2.44 2.25 1.48 1.46 1-9/16" 1-9/16"1.43 80276 2-1/2" x 2-1/2" x 2" 1-9/16" 1-9/16"1.50 1-13/16" 1-13/16" 1-13/16" 1-9/16" 2" x 2" x 1-1/4" 1-9/16" 80008 80014 1-13/16" 2.89 1.91 2" 1-1/4" 1-1/2" 3/4" 1" 3" 2-1/2" 80015 0.281" x 1" x 3/4" x 3/4" 7/8" SCHD. 80 40 80 40 40 80 80 80 80 80 80 40 40 40 40 40 40 40 40 40 80 80 80 80 80 80 80 80 80 80 80 80 80 80 40 80 40 40 80 80 40 T/O T/O 90° ELBOW & 1-1/16" 80029 80026 80025 80027 80028 2" 3/4" 1" 1-1/4" 1-1/2" 0.791-5/16" 5/8" 3/4" 7/8"0.21 0.14 0.40 0.09 Y X 1-9/16" 80031 80030 3" 2-1/2" 1.821-13/16" 1.14 XxY 80032 1" x 3/4"0.16 X 11/16" Y 13/16" REDUCING ELBOW 80 40 80 40 40 80 80 40 Page4of6 TFP1915 FIGURE 2 — FITTING DIMENSIONS (Part 2 of 4) 0.2580078 T/O 80079 0.38 T/O COUPLING & T/O 45° ELBOW 80053 80054 80075 80076 80077 80050 80051 80052 0.311/2" 1/8" 3/4" 0.11 0.07 0.12 0.56 3/8" 3/8" 3/4" 0.08 0.11 0.20 1/8" 3/16" 3/16" 3/16" 80203 80206 80205 80204 80200 80201 80202 80207 80208 80209 T/O REDUCER BUSHING 2" x 1-1/4" 2" x 1-1/2" 2" x 1" 1-1/2" x 3/4" 1-1/2" x 1-1/4" 1-1/4" x 3/4" 1-1/2" x 1" 2" x 3/4" 1-1/4" x 1" 1" x 3/4" 11/16" 9/16" 7/16" 5/8" 1/2" 13/16" 3/8" 5/16" 1/2" 7/16" 0.26 0.24 0.19 0.16 0.27 0.17 0.14 0.04 0.12 0.11 NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE PART NUMBER (T/O) 2" 3/4" 1" 1-1/4" 1-1/2" 13/16" 80056 80055 3" 2-1/2" 1.191" 0.89 80 40 80 40 40 80 80 REDUCING COUPLING 2" 3/4" 1" 1-1/4" 1-1/2" 1/4" 80081 80080 3" 2-1/2" 0.913/16" 0.67 80 40 80 40 40 80 80 80220 0.081" x 3/4"1/8"40 80 40 80 40 40 80 80 80 80 80 80 80 80 80 80 80 80215 2-1/2" x 1" 15/16"0.42 80214 2-1/2" x 1-1/4" 13/16"0.45 80213 2-1/2" x 1-1/2" 11/16"0.46 80211 2-1/2" x 2"5/8"0.29 80210 3" x 2"3/4"0.72 80212 3" x 2-1/2"1/2"0.47 WEIGHT (lb.)SCHD. T/O 80104 80103 80102 CAP 80101 80100 2" 1-1/4" 1-1/2" 3/4" 1" 5/8" 11/16" 7/16" 0.31 0.20 0.10 5/16" 3/8"0.06 0.04 80106 80105 3" 2-1/2" 1" 7/8" 0.88 0.58 80 40 80 40 40 80 80 1-1/4" x 1-1/4" Groove 2-5/16" 80161 80162 T/O 1-1/2" x 1-1/2" Groove 2" x 2" Groove 2-5/16" 2-5/16" 80160 COUPLING ADAPTER 0.95 1.42 0.78 GROOVED 80163 2-1/2" x 2-1/2" Groove 2-5/16"2.28 80164 3" x 3" Groove 2-1/4"3.00 80169 2-1/2" x 76,1 mm Groove 2-5/16"2.28 40 80 80 80 80 80 PIPE O.D. T/O PIPE O.D. 1-1/4" (1.660") 2" (2.375") 1-1/2" (1.900") 2-1/2" (2.875") 3" (3.500") 76,1 mm (3.000") TFP1915 Page5of6 3/4" x 3/4" NPT 13/16" 80145 80146 T/O 1' x 1" NPT 1-1/4" x 1-1/4" NPT 1-1/8" 7/8" 80142 0.63 1.03 0.41 80147 1-1/2" x 1-1/2" NPT 1-3/8"1.42 80148 2" x 2" NPT 1-11/16" 2.66 40 40 80 40 80 3/4" x 3/4" NPT 1-5/16" 80158 1' x 1" NPT 1-3/8" 80157 0.56 0.3340 40 T/O 80177L 3/4" x 1/2" NPT 0.16401/2" 80178 1" x 1/2" NPT 0.20409/16" T/O 80258 80253 80256 2" x 1-1/2" x 1/2" NPT 2" x 2" x 1/2" NPT 1-1/4" x 1" x 1/2" NPT 1/2" 1/2" 7/16" 1-11/16"5/8" 1/2" 1-11/16" 9/16" 1-5/16" 0.56 0.62 0.30 80250 3/4" x 3/4" x 1/2" NPT 9/16" 9/16"1" 0.22 80251 11/16"1" x 1" x 1/2" NPT 11/16"0.291-3/16" 80249 1" x 1" x 1" NPT 15/16" 15/16" 1-9/16"0.73 80252 1-1/4" x 1-1/4" x 1/2" NPT 7/16"7/16"0.311-5/16" 80257 1-1/2" x 1-1/4" x 1/2" NPT 1/2" 11/16" 1-7/16"0.43 1/2"1-1/2" x 1-1/2" x 1/2" NPT80254 1/2"0.461-7/16" 80 80 40 40 40 40 40 80 80 T/OT/O Z XY T/O 80175E 3/4" x 1/2" NPT 0.20 80176E 1" x 1/2" NPT 0.22 80 80 7/16" 7/16" 80175WL 3/4" x 1/2" NPT 0.16407/16" 80179 1" x 3/4" NPT 0.434013/16" NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE PART NUMBER (T/O) FEMALE ADAPTER MALE ADAPTER WEIGHT (lb.)SCHD. ADAPTER (SPIGOT) SPRINKLER HEAD YXx YxZ XZ ADAPTER TEE SPRINKLER HEAD ADAPTER SPRINKLER HEAD ADAPTER SPRINKLER HEAD 80175W 3/4" x 1/2" NPT 0.19401/2" 80176W 1" x 1/2" NPT 0.18401/2" T/O T/O 80180 1" x 3/4" NPT 0.40407/8" FIGURE 2 — FITTING DIMENSIONS (Part 3 of 4) Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeensubjecttomisuse,improper installation,corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes any person to assume forit, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer’s repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,specialorconsequentialdam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. Theforegoingwarrantyismadeinlieu of any and all other warranties, ex- press or implied, including warranties ofmerchantabilityandfitnessforapar- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Page6of6 TFP1915 TYCO FIRE & BUILDING PRODUCTS,451 North Cannon Avenue, Lansdale, Pennsylvania 19446 FIGURE 2 — FITTING DIMENSIONS (Part 4 of 4) 5/8" 5/8" X Y, Z 1-5/16" 1-3/16" Xx YxZ 80459 1" x 1/2" NPT x 1/2" NPT 0.48 80460 1" x 1/2" NPT x 1/2" NPT 0.46 40 40 BACK-TO-BACK TEE T/O T/OT/O T/O T/OT/O T/O Z X X Z W Y Y 5/8" 5/8" X, Y Z, W 1-3/16" 1-5/16" X x Y x Z x W 80462 1" x 1" x 1/2" NPT x 1/2" NPT 0.46 80463 1" x 1" x 1/2" NPT x 1/2" NPT 0.47 40 40 BACK-TO-BACK CROSS NOMINAL TAKE-OUTFITTINGNOMINAL SIZETYPE PART NUMBER (T/O) WEIGHT (lb.)SCHD. T/O T/O X Y ADAPTER 90° ELBOW SPRINKLER HEAD 9/16" 3/4" XY 1" 1-1/4" XxY 80199 3/4" x 1/2" NPT 0.20 80198 1" x 1/2" NPT 0.26 40 40 1-1/16" 1-7/16"80196 1" x 3/4" NPT 0.2640 Schedule 10 and Schedule 40 FM Approved and UL Listed Sprinkler Pipe Bull Moose Tube Company is a recognized producer of quality pipe products. Our Schedule 10 and Schedule 40 are FM Approved and UL Listed (for U.S. and Canada), even though these products do not require separate approvals and listings. Bull Moose Tube made the decision to have them approved and listed for your peace of mind. Our Sch. 10 and Sch. 40 have been through the same rigorous testing as our other fine pipe products. Bull Moose Tube’s Sch. 10 and Sch. 40 pipes are made to ASTM A135 and ASTM A795. These products are typically supplied with our protective coating but can be supplied without the coating so they can be hot-dip galvanized to meet FM requirements for use in dry systems in accordance with the zinc coating specifications of ASTM A795 or ASTM A53. All Schedule 10 and Schedule 40 pipe has a pressure rating of 300 PSI. Schedule 10 Pipe Nominal Pipe Size (in) Nominal O.D. (in) Nominal I.D. (in) Weight/Ft Bundle Size 1 1.315 1.097 1.41 lbs/ft 91 1 1/4 1.660 1.442 1.81 lbs/ft 61 1 1/2 1.900 1.682 2.09 lbs/ft 61 2 2.375 2.157 2.64 lbs/ft 37 2 1/2 2.875 2.635 3.53 lbs/ft 30 3 3.500 3.260 4.34 lbs/ft 19 4 4.500 4.260 5.62 lbs/ft 19 Schedule 40 Pipe Nominal Pipe Size (in) Nominal O.D. (in) Nominal I.D. (in) Weight/Ft Bundle Size 1 1.315 1.049 1.68 lbs/ft 70 1 1/4 1.660 1.380 2.27 lbs/ft 51 1 1/2 1.900 1.610 2.72 lbs/ft 44 2 2.375 2.067 3.66 lbs/ft 30 2 1/2 2.875 2.468 5.80 lbs/ft 30 3 3.500 3.068 7.58 lbs/ft 19 4 4.500 4.026 10.80 lbs/ft 19 PIPE PREPARATION For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket, pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer’s instructions for the specific fitting used. A company 1819 Clarkson Road Chesterfield, MO 63017 (800) 325-4467 FAX: (636) 537-2645 www.bullmoosetube.com e-mail: sales@bullmoosetube.com For additional information, contact your salesperson today at (800) 325-4467 or (636) 537-2600 in the USA, or from Canada call (800) 882-4666 All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 12/09 General Description Tyco®CPVC Pipe and Fittings pro- duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively for use in wet pipe automatic fire sprin- kler systems. The Tyco CPVC Pipe and Fittings are produced from Blaze- Master®CPVC compound that is a specially developed thermoplastic compound composed of post chlorin- ated polyvinyl chloride (CPVC) resin and state of the art additives. Tyco CPVC Pipe and Fittings are easier to install than traditional steel pipe sys- tems, and at the same time, provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapters are available to connect CPVC pipe to me- tallic piping. All female pipe thread adapters have brass inserts for dura- bility. Grooved adapters connect di- rectly to grooved end valves and me- tallic pipe, with flexible grooved end couplings. NOTICE Tyco®CPVC Pipe and Fittings pro- duced with BlazeMaster ®CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to thestandardsofanyauthoritieshaving jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Sizes 3/4" to 3" Maximum Working Pressure 175 psi Approvals UL, FM, C-UL, NSF, LPCB, MEA, and the City of Los Angeles. (Refer to In- stallation Handbook IH-1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.S.A. Material •Pipe: ASTM F442, SDR 13.5 •Fittings: ASTM F438 (Sch. 40) and ASTM F439 (Sch. 80), ASTM F1970 Color Orange BlazeMaster ® CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet Page 1 of 2 TFP1915JUNE, 2008 Technical Services:Tel: (800) 381-9312 / Fax: (800) 791-5500 BlazeMaster®is a registered trademark of The Lubrizol Corporation MALLEABLE IRON Malleable IronCast IronSmall Steel FittingsPipe Nipples &Pipe CouplingsForged SteelFittings & UnionsAnviletsCatawissaJ.B. Smith ProductsCarton Information www.anvilintl.com 17 Anvil Class 150/300 Malleable Iron Fittings conform to ASME B16.3 and Unions conform to ASME B16.39. ALL ELBOWS & TEES 3⁄8" (10 DN) and LARGER ARE 100% GAS TESTED AT A MINIMUM OF 100 PSI. (6.9 bar) Malleable Iron Threaded Pipe Unions Pressure - Temperature Ratings Temperature Pressure Class 150 Class 250 Class 300 (°F) (°C)psi bar psi bar psi bar -20° to 150° -28.9° to 65.6° 300 20.7 500 34.5 600 41.4 200°93.3°265 18.3 455 31.4 550 37.9 250°121.1°225 15.5 405 27.9 505 34.8 300°148.9°185 12.8 360 24.8 460 31.7 350°176.7°150 10.3 315 21.7 415 28.6 400°204.4°110 7.6 270 18.6 370 25.5 450°232.2°75 5.2 225 15.5 325 22.4 500°260.0°––180 12.4 280 19.3 550°287.8°––130 9.0 230 15.9 Note: Unions with Copper or Copper Alloy seats are not intended for use where temperature exceeds 450°F Malleable Iron Threaded Fittings Pressure - Temperature Ratings Temperature Pressure Class 150 Class 300 Sizes 1⁄4"–1" (6–25 mm) Sizes 11⁄4"–2" (32–51 mm) Sizes 21⁄2"–3" (64–76 mm) (°F)(°C)psi bar psi bar psi bar psi bar -20° to 150° -28.9° to 65.6° 300 20.7 2,000 137.9 1,500 103.4 1,000 68.9 200°93.3 265 18.3 1,785 123.1 1,350 93.1 910 62.7 250°121.1 225 15.5 1,575 108.6 1,200 82.7 825 56.9 300°148.9 185 12.8 1,360 93.8 1,050 72.4 735 50.7 350°176.7 150 10.3 1,150 79.3 900 62.1 650 44.8 400°204.4 ––935 64.5 750 51.7 560 38.6 450°232.2 ––725 50.0 600 41.4 475 32.8 500°260.0 ––510 35.2 450 31.0 385 26.5 550°287.8 ––300 20.7 300 20.7 300 20.7 For Listings/Approval Details and Limitations, visit our website @ www.anvilintl.com or contact an Anvil/AnvilStar Sales Representative. PF-11.10 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com79 Ductile Iron Threaded Fittings TemperatureDegrees F Working Pressure, Nonshock PsIG300# Class Threaded Fittings -20 to 100 500 150 500 200 480 250 460 300 440 350 420 400 400 450 380 500 360 550 340 600 320 650 300 Specifications • The branded Ductile Iron threaded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 WSP • Ductile Iron castings conform to ASTM A536 • Fitting dimensions conform to ASME B16.3 • Bushings and plugs conform to ASME B16.14 • Fittings are 100% air tested • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical & physical properties • Manufacturing facilities are ISO 9001:2000 and ISO 14001 The FireLock EZ Style 009H coupling is a rigid, installation-ready coupling for fire protection pipe joining. The coupling’s unique design eliminates loose parts, insures consistent installation and provides substantial gains in productivity. IMPORTANT FireLock EZ Style 009H couplings are recommended for use ONLY on fire protection systems. LISTINGS/APPROVALS * The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Standard Pipe Size cULus/FM VdS LPCB NominalSizeInches/mm Sch. 5psi/KPa Sch.10psi/kPa Sch. 40psi/KPa psi/kPa psi/kPa 1¼175 365 365 365 36532120625172517251725171½175 365 365 365 3654012062517251725172517 2 175 365 365 365 3655012062517251725172517 2½N/A 365 365 365 365 65 2517 2517 2517 2517 76.1 mm N/A N/A 365**365 3652517**2517 2517 3 N/A 365 365 365 365802517251725172517 108 mm N/A 365***365***N/A N/A2517***2517***4 N/A 365 365 365 3651002517251725172517 133 mm N/A 290***365***N/A N/A1999***2517*** 139.7 mm N/A N/A 290**232 365 1999**1600 2517 165.1 mm N/A N/A 290**232 3651999**1600 2517 6#N/A 290 365 232 365150#1999 2517 1600 2517 * Listed/Approved for wet and dry pipe systems (> –40°F/–40°C). Please refer to the Victaulic Installation Manual (I-009H_009_009V.pdf) for details concerning when supplemental lubrication is required. ** EN-10219(L) for 76.1mm size; EN-10255(M) # Regional availability only# *** FM Approved only. 10.61_1 FireLock EZ® Rigid Coupling STYLE 009H 10.61IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_G PATENTED SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS LISTINGS/APPROVALS * Speciality Pipe Pipe Size Pressure Rating – psi/kPa Pa Pipe Size Pressure Rating – psi/kPakPa Pipe Size Pressure Rating – psi/kPa/kPa Sch.Inches cULus FM Sch.Inches cULus FM Sch.Inches cULus FM BLT 1 1/4 – 2 300 3002068 EZT 1 1/4 – 2 3002068 3002068 MT 1 1/4 – 2 3002068 30020682068 DF 1 1/4 – 4 300 3002068 FF 1 1/4 – 4 3002068 3002068 MLT 1 1/4 – 2 N/A 30020682068 DT 1 1/4 – 2 300 3002068 FLF 1 1/4 – 4 N/A 3002068 ST 1 1/4 – 2 N/A 300 20682068 EF 1 1/4 – 4 175 1751206 FLT 1 1/4 – 2 N/A 3002068 STF 1 1/4 – 4 N/A 30020681206 EL 1 1/4 – 2 300 3002068 FLTL 1 1/4 – 2 N/A 3002068 TF 2 1/4 – 4 N/A 30020682068 ET40 1 1/4 – 2 300 3002068 GL 1 1/4 – 2 3002068 3002068 WLS 1 1/4 – 2 3002068 30020682068 EZF 3 – 4 300 3002068 MF 1 1/4 – 4 3002068 3002068 WST 1 1/4 – 2 N/A 17512062068 XL 1 1/4 – 2 3002068 3002068 Note: The Specialty Pipe table only applies to imperial sizes, NOT to metric sizes. 10.61_2 FireLock EZ® Rigid Coupling STYLE 009H 10.61IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_G STYLE 009H DIMENSIONS X ZY STYLE 009H PRE-ASSEMBLED (PUSH ON CONDITION) X ZY STYLE 009H JOINT ASSEMBLED Size Max. Work.Press. * Max. EndLoad * Allow. Pipe EndSep. †@ Bolt/NutNo. – Size Dimensions – Inches/mm Aprx.Wgt. Ea. NominalSizeInchesmm ActualOutsideDia.Inchesmm psikPa Lbs.N Inchesmm Inches Pre-assembled(Stab in condition)Joint Assembled Lbs.kgXYXYZ 1 1/4 1.660 365 790 0.10 2 - 3/8 x 2 2.95 4.77 2.70 4.63 1.93 1.43242.4 2517 3514 2.54 - M10 x 2 75 121 69 118 49 0.7 1 1/2 1.900 365 1035 0.10 2 - 3/8 x 2 3.19 4.97 2.94 4.79 1.93 1.54048.3 2517 4604 2.54 - M10 x 2 81 126 75 122 49 0.7 2 2.37 5 365 1616 0.12 2 - 3/8 x 2 3.79 5.53 3.45 5.42 1.93 1.95060.3 2517 7193 3.05 - M10 x 2 96 140 88 138 49 0.9 2 1/2 2.875 365 2370 0.12 2 - 3/8 x 2 1/2 4.29 6.09 3.92 5.85 1.93 2.16573.0 2517 10542 3.05 - M10 x 2 1/2 109 155 100 149 49 1.0 76.1 mm 3.000 365 2580 0.12 2 - 3/8 x 2 1/2 4.40 6.31 4.05 5.90 1.93 2.1 76.1 2517 11476 3.05 - M10 x 2 1/2 112 160 103 150 49 1.0 3 3.500 365 3512 0.12 2 - 3/8 x 2 1/2 4.91 6.70 4.55 6.46 1.93 2.38088.9 2517 15622 3.05 - M10 x 2 1/2 125 170 116 164 49 1.0 108 mm 4.250 365 5178 0.17 2 - 3/8 x 2 1/2 5.56 7.61 5.27 7.51 2.14 2.8108.0 2517 23030 4.32 - M10 x 2 1/2 141 193 134 191 54 1.2 4 4.500 365 5805 0.17 2 - 3/8 x 2 1/2 5.95 7.82 5.54 7.47 2.14 2.9100114.3 2517 25822 4.32 - M10 x 2 1/2 151 199 141 190 55 1.3 133 mm 5.250 365 7900 0.17 2 - 3/8 x 2 1/2 6.66 9.11 6.36 9.01 2.14 4.3133.0 2517 35140 4.33 - M10 x 2 1/2 169 232 162 229 55 1.9 139.7 mm 5.500 365 8620 0.17 2 - 3/8 x 2 1/2 6.75 9.29 6.46 9.23 2.09 4.6139.7 2517 38340 4.32 - M10 x 2 1/2 172 236 164 234 53 2.1 165.1 mm 6.500 290 9623 0.17 2 - 5/8 x 3 1/4 7.84 10.93 7.55 10.85 2.11 5.69165.1 1999 42805 4.32 - M16 x 3 1/4 199 278 192 276 54 2.6 6 6.625 290 9997 0.17 2 - 5/8 x 3 1/4 7.96 11.08 7.67 11.99 2.11 5.92150168.3 1999 44469 4.32 - M16 x 3 1/4 202 281 195 305 54 2.69 * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. See page 1 of this document for Listed/Approved ratings on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 ½ times the figures shown in the chart on page 1, specific to pipe schedule and size. † The allowable pipe separation dimension shown is for system layout purposes only. FireLock EZ couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. @ Number of bolts required equals number of housing segments. 10.61_3 FireLock EZ® Rigid Coupling STYLE 009H 10.61IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_G MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: • Orange enamel (North America, Asia Pacific) • Red enamel (Europe) Optional Coatings: • Hot dipped galvanized Gasket: • Grade “E” EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009H couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps con- taining the “QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009H couplings. IMPORTANT: Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009H coupling. There is no interchanging of gaskets or housings between coupling styles. GENERAL NOTES INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. USE OF FLUSHSEAL GASKETS FOR DRY PIPE SYSTEMS FireLock EZ couplings are supplied with FireLock EZ Grade “E” Type A gaskets. These gaskets include an integral pipe stop, that once installed provides the same benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard FlushSeal gaskets are not compatible and cannot be used with the FireLock EZ couplings. 10.61 FireLock EZ® Rigid Coupling STYLE 009H 10.61IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.61 5731 REV G UPDATED 09/2012 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. victaulic.com 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. Exaggerated for clarity1 – 8"/DN25 – DN200 Exaggerated for clarity 1.0 PRODUCT DESCRIPTION Available Sizes • 1 – 8"/DN25 – DN200 Pipe Material • Carbon steel • Stainless steel • For exceptions see section 6.0 Notifications Maximum Working Pressure • Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) up to 500 psi/3447 kPa/34 bar • Working pressure dependent on material, wall thickness and size of pipe Application • Joins standard roll grooved and cut grooved pipe, as well as grooved fittings, valves and accessories • Provides a flexible pipe joint which allows for expansion, contraction and deflection • Up to 50% lighter in weight than standard Victaulic Style 77 or Style 177N flexible couplings 2.0 CERTIFICATION/LISTINGS NOTES • Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide. • See publication 02.06: Victaulic Potable Water Approvals ANSI/NSF for potable water approvals if applicable. Victaulic® Flexible Coupling Style 75 06.05 1 System No.Location Submitted By Date Spec Section Paragraph Approved Date 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 3.0 SPECIFICATIONS – MATERIAL Housing: Ductile iron conforming to ASTM A536, Grade 65-45-12. Ductile iron conforming to ASTM A395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) Standard: Orange enamel Optional: Hot dipped galvanized Optional: Contact Victaulic with your requirements for other coatings. Gasket: (specify choice1) Grade “E” EPDM EPDM (Green stripe color code). Temperature range –30ºF to +230ºF/–34ºC to +110ºC. May be specified for hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot +180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR USE WITH PETROLEUM SERVICES OR STEAM SERVICES. Grade “T” Nitrile Nitrile (Orange stripe color code). Temperature range –20ºF to +180ºF/–29ºC to +82ºC. May be specified for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; not compatible for hot dry air over +140°F/+60°C and water over +150°F/+66°C. NOT COMPATIBLE FOR USE WITH HOT WATER. Others For alternate gasket selection, reference publication 05.01: Victaulic Seal Selection Guide - Elastomeric Seal Construction. 1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference should always be made to the latest Victaulic Seal Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: (specify choice2) Standard: Carbon steel oval neck track bolts meeting the mechanical property requirements of ASTM A449 (imperial) and ISO 898-1 Class 9.8 (M10-M16) Class 8.8 (M20 and greater). Carbon steel hex nuts meeting the mechanical property requirements of ASTM A563 Grade B (imperial - Heavy Hex nuts) and ASTM A563M Class 9 (metric - hex nuts). Track bolts and hex nuts are zinc electroplated per ASTM B633 ZN/FE5, finish Type III (imperial) or Type II (metric). Optional (imperial): Stainless steel oval neck track bolts meeting the mechanical property requirements of ASTM F593, Group 2 (316 stainless steel), condition CW. Stainless steel heavy nuts meeting the mechanical property requirements of ASTM F594, Group 2 (316 stainless steel), condition CW, with galling reducing coating. 2 Optional bolts/nuts are available in imperial sizes only. 2 victaulic.com 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 4.0 DIMENSIONS Style 75 Flexible Coupling Z X Y Size Pipe End Separation3 Deflection from Centerline3 Bolt/Nut Dimensions Weight Nominal Actual Outside Diameter Allowable Per Cplg.Pipe Qty.Size X Y Z Approx. (Each) inches DN inches mm inches mm Degrees inches/ft. mm/m imperial metric inches mm inches mm inches mm lb kg 1 DN25 1.315 33.7 0–0.06 0–1.6 2º–43’0.57 48 2 3⁄8 x 2 M10 x 51 2.38 61 4.27 108 1.77 45 1.3 0.6 1 1/4 DN32 1.660 42.4 0–0.06 0–1.6 2º–10’0.45 38 2 3⁄8 x 2 M10 x 51 2.68 68 4.61 117 1.77 45 1.4 0.6 1 1/2 DN40 1.900 48.3 0–0.06 0–1.6 1º–56’0.40 33 2 3⁄8 x 2 M10 x 51 2.91 74 4.82 122 1.77 45 1.5 0.6 2 DN50 2.375 60.3 0–0.06 0–1.6 1º–31’0.32 26 2 3⁄8 x 2 M10 x 51 3.43 87 5.22 133 1.88 48 1.7 0.8 2 1/2 2.875 73.0 0–0.06 0–1.6 1º–15’0.26 22 2 3⁄8 x 2 M10 x 51 3.88 98 5.68 144 1.88 48 1.9 0.9 DN65 3.000 76.1 0–0.06 0–1.6 1º–12’0.26 22 2 3⁄8 x 2 M10 x 51 4.00 102 5.90 150 1.88 48 1.9 0.9 3 DN80 3.500 88.9 0–0.06 0–1.6 1º–2’0.22 18 2 1/2 x 2 3/4 M12 x 70 4.50 114 7.00 178 1.88 48 2.9 1.3 3 1/2 DN90 4.000 101.6 0–0.06 0–1.6 0º-54’0.19 16 2 1/2 x 2 3/4 M12 x 70 5.00 127 7.50 191 1.88 48 2.9 1.3 4 DN100 4.500 114.3 0–0.13 0–3.2 1º–36’0.34 28 2 1/2 x 2 3/4 M12 x 70 5.80 147 8.03 204 2.13 54 4.1 1.9 4.250 108.0 0–0.13 0–3.2 1º–41’0.35 29 2 1/2 x 2 3/4 M12 x 70 5.55 141 7.79 198 2.13 54 3.7 1.7 5.000 127.0 0–0.13 0–3.2 1º–26’0.25 21 2 5⁄8 x 3 1/4 M16 x 83 6.13 156 9.43 240 2.13 54 5.5 2.5 5.250 133.0 0–0.13 0–3.2 1º–21’0.28 24 2 5⁄8 x 3 1/4 M16 x 83 6.55 166 9.37 238 2.13 54 6.0 2.7 DN125 5.500 139.7 0–0.13 0–3.2 1º–18’0.28 24 2 5⁄8 x 3 1/4 M16 x 83 6.80 173 9.59 244 2.13 54 6.3 2.9 5 5.563 141.3 0–0.13 0–3.2 1º–18’0.27 23 2 5⁄8 x 3 1/4 M16 x 83 6.88 175 10.07 256 2.13 54 5.8 2.6 6.000 152.4 0–0.13 0–3.2 1º–12’0.21 18 2 5⁄8 x 3 1/4 M16 x 83 7.38 187 10.48 266 1.88 48 6.2 2.8 6.250 159.0 0–0.13 0–3.2 1º–9’0.24 20 2 5⁄8 x 3 1/4 M16 x 83 7.63 194 10.49 266 2.13 54 6.8 3.1 6.500 165.1 0–0.13 0–3.2 1º–7’0.23 58 2 5⁄8 x 3 1/4 M16 x 83 7.84 199 10.66 271 2.08 53 6.6 3.0 6 DN150 6.625 168.3 0–0.13 0–3.2 1º–5’0.23 18 2 5⁄8 x 3 1/4 M16 x 83 8.00 203 11.07 281 2.13 54 7.0 3.2 200A4 216.3 0–0.13 0–3.2 0º–51’0.18 46 2 3/4 x 4 1/4 M20 x 108 10.19 259 13.75 350 2.32 59 13.2 6.0 8 DN200 8.625 219.1 0–0.13 0–3.2 0º–50’0.18 14 2 3/4 x 4 1/4 M20 x 108 10.34 263 13.97 355 2.13 59 12.4 5.6 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50% for 3/4 – 3 1/2"/DN20 – DN90; 25% for 4"/DN100 and larger. 4 Japanese Industrial Standard (JIS) size NOTE • Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. 3 victaulic.com 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com 5.0 PERFORMANCE Style 75 Flexible Coupling Size Maximum Working Pressure5 Maximum End Load5Nominal Actual Outside Diameter inches DN inches mm psi kPa lb N 1 DN25 1.315 33.7 500 3447 680 3025 1 1/4 DN32 1.660 42.4 500 3447 1080 4805 1 1/2 DN40 1.900 48.3 500 3447 1420 6320 2 DN50 2.375 60.3 500 3447 2215 9860 2 1/2 2.875 73.0 500 3447 3245 14440 DN65 3.000 76.1 500 3447 3535 15730 3 DN80 3.500 88.9 500 3447 4800 21360 3 1/2 DN90 4.000 101.6 500 3447 6300 28035 4 DN100 4.500 114.3 500 3447 7950 35380 4.250 108.0 450 3103 6380 28395 5.000 127.0 450 3103 8820 39250 5.250 133.0 450 3103 9735 43325 DN125 5.500 139.7 450 3103 10665 47460 5 5.563 141.3 450 3103 10935 48660 6.000 152.4 450 3103 12735 56670 6.250 159.0 450 3103 13800 61405 6 DN150 6.625 168.3 450 3103 15525 69085 6.500 165.1 450 3103 14930 66412 200A4 216.3 450 3103 25625 113986 8 DN200 8.625 219.1 450 3103 26280 116945 4 Japanese Industrial Standard (JIS) size 5 Working Pressure and End Load are total, from all internal and external loads, based on ANSI B36.10 sized carbon steel pipe, grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. NOTE • WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. 4 victaulic.com 06.05 1470 Rev Q Updated 05/2020 © 2020 Victaulic Company. All rights reserved. victaulic.com User Responsibility for Product Selection and SuitabilityEach user bears final responsibility for making a determination as to the suitability of Victaulic products for a particular end-use application, in accordance with industry standards and project specifications, and the applicable building codes and related regulations as well as Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any other document, nor any verbal recommendation, advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Company's standard conditions of sale, installation guide, or this disclaimer. Intellectual Property Rights No statement contained herein concerning a possible or suggested use of any material, product, service, or design is intended, or should be constructed, to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such material, product, service, or design in the infringement of any patent or other intellectual property right. The terms “Patented” or “Patent Pending” refer to design or utility patents or patent applications for articles and/or methods of use in the United States and/or other countries. NoteThis product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Installation Reference should always be made to the Victaulic installation handbook or installation instructions of the product you are installing. Handbooks are included with each shipment of Victaulic products, providing complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. TrademarksVictaulic and all other Victaulic marks are the trademarks or registered trademarks of Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. 6.0 NOTIFICATIONS WARNING • Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products. • Always verify that the piping system has been completely depressurized and drained immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products. • Wear safety glasses, hardhat, and foot protection. Failure to follow these instructions could result in death or serious personal injury and property damage. NOTICE • Victaulic RX grooving rolls must be ordered separately. They are identified by a silver color and the designation RX on the front of the roll sets. NOTICE • Victaulic does not recommend the use of any furnace butt-welded pipe with sizes NPS 2”/DN50 and smaller Victaulic gasketed joint products. This includes, but is not limited to, ASTM A53 Type F pipe. 7.0 REFERENCE MATERIALS 02.06: Victaulic Potable Water Approvals ANSI/NSF 05.01: Victaulic Seal Selection Guide - Elastomeric Seal Construction 06.15: Victaulic Pressure Ratings and End Loads for Victaulic Couplings on Steel Pipe 10.01: Victaulic Products for Fire Protection Pipings Systems - Regulatory Approval Reference Guide 17.01: Victaulic Pipe Preparation for Use on Stainless Steel Pipe With Victaulic Products 17.09: Victaulic Ductile Iron Grooved Couplings Performance Data for Stainless Steel Pipe 25.01: Victaulic Standard Groove Specifications 26.01: Victaulic Design Data 29.01: Victaulic Terms and Conditions of Sale I-100: Victaulic Field Installation Handbook I-ENDCAP: Victaulic End Cap Installation Safety Instructions 5 victaulic.com victaulic.com 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT. 1.0 PRODUCT DESCRIPTION Available Sizes • 1 ¼ – 8"/DN32 – DN200 Maximum Working Pressure • Pressure ratings for Victaulic FireLock™ Fittings conform to the ratings of Victaulic FireLock EZ™ Style 009N couplings (refer to publication 10.64 for more information). Application • FireLock™ fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. • Connects pipe, provides change in direction and adapts sizes or components Pipe Materials • Carbon steel 2.0 CERTIFICATION/LISTINGS EN 10311 Regulation (EU) No. 305/2011 3.0 SPECIFICATIONS – MATERIAL Fitting: Ductile iron conforming to ASTM A536, Grade 65-45-12. Fitting Coating: Orange enamel. R ed enamel in Europe, Middle East, Africa, and India. O ptional: Hot dipped galvanized. Victaulic® FireLock™ Fittings 10.03 1 System No.Location Submitted By Date Spec Section Paragraph Approved Date 4.0 DIMENSIONS C to E Cto E C to E Cto E CtoE T No. 001 No. 003 No. 002 No. 006 Nominal Size inches DN Actual Outside Diameter inches mm No. 001 90° Elbow No. 003 45° Elbow No. 002 Straight Tee No. 006 Cap C to E inches mm Approximate Weight Each lb kg C to E inches mm Approximate Weight Each lb kg C to E inches mm Approximate Weight Each lb kg T inches mm Approximate Weight Each lb kg 1 1/4 1.660 — — — — — — 0.82 0.3 DN32 42.4 ——————21 0.1 1 1/2 DN40 1.900 48.3 — — — — — — — — — — — — 0.82 21 0.4 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 DN50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 2 1/2 2.875 73.0 3.00 76 3.1 1.4 2.25 57 2.2 1.0 3.00 76 3.6 1.6 0.88 22 1.0 0.5 DN65 3.000 3.00 3.30 2.25 2.4 3.00 3.8 ——76.1 76 1.5 57 1.1 76 1.7 3 DN80 3.500 88.9 3.38 86 4.0 1.8 2.50 64 3.1 1.4 3.38 86 5.3 2.4 0.88 22 1.2 0.5 4.250 4.00 5.7 3.00 5.1 4.00 7.5 ——108.0 102 2.6 76 2.3 102 3.4 4 DN100 4.500 114.3 4.00 102 6.7 3.0 3.00 76 5.6 2.5 4.00 102 8.7 3.9 1.00 25 2.4 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 141.3 124 5.7 83 3.8 124 7.1 25 1.9 DN125 5.500 139.7 4.88 124 12.4 5.6 3.25 82.6 8.2 3.7 4.88 124 15.4 6.9 —— 6.250 5.50 12.6 3.50 9.2 5.50 17.9 ——158.8 140 5.7 89 4.2 140 8.0 6 DN150 6.625 168.3 5.50 140 18.3 8.3 3.50 89 11.7 5.3 5.50 140 22.7 10.3 1.00 25 5.9 2.7 6.500 5.43 17.6 3.50 11.4 5.50 22.0 ——165.1 140 7.9 89 5.2 140 9.9 8 DN200 8.625 219.1 6.81 173 25.5 11.6 4.25 108 20.4 9.3 6.94 176 38.7 17.6 1.13 29 12.7 5.8 8.515 6.81 23.1 ——6.94 33.6 —— 216.3 173 10.5 ——176 15.2 —— 2 victaulic.com 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 5.0 PERFORMANCE Flow Data Size Frictional Resistance Equivalent of Straight Pipe1 Actual Elbows No. 002 Straight Tee Nominal Size inches DN Outside Diameter inches mm No. 001 90° Elbow feet meters No. 003 45° Elbow feet meters Branch feet meters Run feet meters 1 1/4 1.660 ———— DN32 42.4 ———— 1 1/2DN40 1.90048.3 ———————— 2 2.375 3.5 1.8 8.5 3.5 DN50 60.3 1.1 0.5 2.6 1.1 2 1/2 2.875 73.0 4.3 1.3 2.2 0.7 10.8 3.3 4.3 1.3 DN65 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 DN80 3.500 88.9 5.0 1.5 2.6 0.8 13.0 4.0 5.0 1.5 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 DN100 4.500 114.3 6.8 2.1 3.4 1.0 16.0 4.9 6.8 2.1 5 5.563 8.5 4.2 21.0 8.5 141.3 2.6 1.3 6.4 2.6 DN125 5.500 139.7 8.3 2.5 4.1 1.3 20.6 6.3 8.3 2.5 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6DN150 6.625 168.3 10.0 3.0 5.0 1.5 25.0 7.6 10.0 3.0 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 8 DN200 8.625 219.1 13.0 4.0 5.0 1.5 33.0 10.1 13.0 4.0 8.515 13.0 —33.0 13.0 216.3 4.0 —10.1 4.0 1 T he flow data listed is based upon the pressure drop of Schedule 40 pipe. 3 victaulic.com 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com 10.03 1539 Rev N Updated 09/2017 © 2017 Victaulic Company. All rights reserved. victaulic.com User Responsibility for Product Selection and Suitability NoteEach user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All productVictaulic products for a particular end-use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations.instructions. Nothing in this or any other document, nor any verbal recommendation, Installationadvice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to the Victaulic installation handbook or installation or waive any provision of Victaulic Company's standard conditions of sale, installation instructions of the product you are installing. Handbooks are included with each shipmenguide, or this disclaimer.of Victaulic products, providing complete installation and assembly data, and are availabl Intellectual Property Rights in PDF format on our website at www.victaulic.com. No statement contained herein concerning a possible or suggested use of any material, Warrantyproduct, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details.under any patent or other intellectual property right of Victaulic or any of its subsidiaries or affiliates covering such use or design, or as a recommendation for the use of such Trademarks material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of property right. The terms “Patented” or “Patent Pending” refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries. or patent applications for articles and/or methods of use in the United States and/or other countries. s t e 6.0 NOTIFICATIONS General Notes NOTE: When assembling FireLock EZ™ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ™ Style 009N/009H couplings, use FireLock™ No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the “QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings. 7.0 REFERENCE MATERIALS 10.64: Victaulic® FireLock™ Rigid Coupling Style 009N 10.02: Victaulic® FireLock™ Rigid Coupling Style 005H with Vic-Plus™ Gasket System 29.01: Victaulic® Terms and Conditions of Sale 4 victaulic.com 514 OFFSET HANGER CPVC - COPPER STEEL• SIZE SYSTEM PIPE: MATERIAL FINISH PATENT No. 6,648,278. FUNCTION INSTALLATION WOOD - #905 STEEL- FEATURES #905 ORDERING 906 - 3/4" thru 3" - Carbon Steel. - Mil. Galvanized.. - -S rovid vertical ateral restraint revents upward movement of pipe that supplies a pendent sprinkler below ceiling. - including NFPA13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. Snap over pipe then squeeze strap back allowing pipe to slide freely. CPVC pipe - screw- no pre-drill. Copper pipe - Steel pipe - 1/4 x1 lag screw - 5/8 gypsum board - 1/4 x lag screw min. * 1 1/2 Offset * 3/4 and 1 pipe size a e common center-line. * Patented design for superior strength. * Offset edge eliminates abrasion. * screw included - 5/16" hex head. - Part # and pipe size. # backing nut sold separately. AFCON AFCON LISTING/APPROVAL- 203 - EX 4231, EX 2551 Per these instructions FASTENERS #905 CONCRETE each = upport horizontal piping: 3/4" -3" CPVC or Copper. Support horizontal piping: 3/4" - 2" Steel. Size 3/4" - 2" p es listed /l and p a Stabilize vertical piping. When #905 threads are exposed in wood, install #906 backing nut. - UL Listed per NFPA13 3/4" - 3" 3/4" - 2" screw- no pre-drill. 3/4" - 2" " 1/2" no pre-drill. Thru " " 2" . 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw. 3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw. : Required minimum load fastener " - loose fit allows pipe to slide. " " m d with • 5(wt)+250lbs. 2 1.5000 #905 #906 Listed Restraint Listed Restraint Specific products are exclusively designed to be compatible with other products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. the following warranty restriction will apply. - will warrant against the failure of its products when used in combination with other products, partsor systems not manufactured or sold by . shall be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to loss of business or profit, when non- products have been, or are used. AFCON AFCON AFCON AFCON AFCON AFCON ONLY Be advised DISCLAIMER NOT NOT 3.00 10/08 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 3/4 thru 2"" 3/4 thru 2"" CADCADCAD Size Range: 1” through 12” IPS Material: Steel Function: For bracing against sway and seismic disturbance. Approvals: Factory Mutual Approved for 1” through 12” IPS pipe. For Underwriters Laboratories Listing information see document 4LA-UL-13. Installation Note: The Fig. 4LA can be used as the system attachment component of a longitudinal or lateral seismic brace assembly. It is intended to be combined with a “bracing member” and TOLCO™ brand transitional attachment and structural attachment to form a complete bracing assembly. For fire sprinkler applications NFPA 13 guidelines should be followed. To Install: Place the Fig. 4LA pipe clamp component over the pipe to be braced and tighten down the break –off nuts until the hex head portion breaks off to verify correct installation torque. Next, engage brace member (pipe or strut) with jaw component and tighten break-off head bolt until the hex head breaks off to verify correct installation torque. Pivot jaw for correct angle and attach to structure using TOLCO™ brand transitional attachment and structural attachment. Finish: Plain or EG Order By: Figure number, pipe size and finish www.tolco.com COOPER B-Line 1375 Sampson Ave • Corona, CA 92879 • 800.786.5266 • FAX: 951.737.0330 Longitudinal / Lateral Loads except where noted FM Max. Design Load Part No. Pipe Size 30°-44°45°-59°60°-74°75°-90° in.(mm)lbs.(kN)lbs.(kN)lbs.(kN)lbs.(kN) 4LA-1 1”(25)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-1 ¼1 ¼”(32)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-1 ½1 ½”(40)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-2 2”(50)680 (3.02)860 (3.82)1030 (4.58)1150 (5.11) 4LA-2 ½2 ½”(65)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-3 3”(80)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-3 ½3 ½”(90)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-4 4”(100)680 (3.02)970 (4.31)1190 (5.29)1320 (5.87) 4LA-5 5”(125)-------- 4LA-6 6”(150)1620 (7.20)Note 1 Note 3 Note 5 4LA-8 8”(200)1620 (7.20)Note 2 Note 4 Note 6 4LA-10 10”(250)1620 (7.20)Note 2 Note 4 Note 6 4LA-12 12”(300)1620 (7.20)Note 2 Note 4 Note 6 Fig. 4LA - Longitudinal “In-Line” Sway Brace Attachment © 2013 Cooper B-Line, Inc. 4LA-FM-13 Part No. Pipe Size A C D Bolt Size Approx. Wt./100 in.(mm)in.(mm)in.(mm)in.(mm)lbs.(kg) 4LA-1 1”(25)3 19/32”(91.2)1 5/16”(33.5)1 5/16”(33.5)3/8”-16 119 (54.0) 4LA-1 ¼1 ¼”(32)3 29/32”(99.3)1 3/8”(35.3)1 3/8”(35.3)3/8”-16 123 (55.8) 4LA-1 ½1 ½”(40)4 5/32”(105.7)1 1/2”(38.5)1 1/2”(38.5)3/8”-16 127 (57.6) 4LA-2 2”(50)5 11/32”(135.6)2 1/32”(51.9)2 1/16”(51.9)3/8”-16 142 (64.4) 4LA-2 ½2 ½”(65)5 27/32”(148.7)2 5/16”(58.5)2 5/16”(58.5)3/8”-16 173 (78.5) 4LA-3 3”(80)6 ½”(164.9) 2 5/8”(66.6)2 5/8”(66.6)3/8”-16 187 (84.8) 4LA-3 ½3 ½”(90)7 13/32”(188.1)2 7/8”(73.1)2 7/8”(73.1)3/8”-16 198 (89.8) 4LA-4 4”(100)7 13/32”(190.8)3 1/8”(79.5)3 1/8”(79.5)3/8”-16 209 (94.8) 4LA-5 5”(125)8 3/4”(222.3)3 5/8”(92.1)3 5/8”(92.1)½”-13 298 (135.2) 4LA-6 6”(150)10 5/8”(269.9)4 9/16”(115.9)4 9/16”(115.9)½”-13 521 (236.3) 4LA-8 8”(200)12 13/16”(325.5)5 9/16”(143.7)5 9/16”(143.7)½”-13 629 (285.3) 4LA-10 10”(250)16 ½”(419.1)7 ¼”(184.2)7 ¼”(184.2)½”-13 1320 (598.7) 4LA-12 12”(300)18 ½”(469.9)8 ¼”(209.6)8 ¼”(209.6)½”-13 1496 (678.6) Note 1: Longitudinal load 2,260 lbs. (10.05kN) - Lateral Load 2,300 lbs. (10.23kN) Note 2: Longitudinal load 1,660 lbs. (7.38kN) - Lateral Load 2,300 lbs. (10.23kN) Note 3: Longitudinal load 2,010 lbs. (8.94kN) - Lateral Load 2,820 lbs. (12.54kN) Note 4: Longitudinal load 1,570 lbs. (6.98kN) - Lateral Load 2,820 lbs. (12.54kN) Note 5: Longitudinal load 2,220 lbs. (9.87kN) - Lateral Load 3,140 lbs. (13.96kN) Note 6: Longitudinal load 1,740 lbs. (7.74kN) - Lateral Load 3,140 lbs. (13.96kN) AD C AD C 5”-12” 1”-4” Seismic BracingAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Seismic Bracing 60 Size Range:One size fits bracing pipe 1"(25mm)thru 2"(50mm), Cooper B-Line 12 gauge (2.6mm)channel, and all structural steel up to 1/4"(31.7mm)thick. Material:Steel Function:Multi-functional attachment to structure or braced pipe fitting. Features:This product’s design incorporates a concentric attachment opening which is critical to the performance of structural seismic connections. NFPA 13 indicates clearly that fastener table load values are based only on concentric loading. Mounts to any surface angle. Break off bolt head assures verification of proper installation. Installation:Fig.980 is the structural or transitional attachment component of a longitudinal or lateral sway brace assembly. It is intended to be combined with the "bracing pipe" and Cooper B-Line/TOLCO "braced pipe" attachment, Fig. 1000, 1001, 2002, 4L, 4A or approved attachment to pipe to form a complete bracing assembly. NFPA 13 guidelines should be followed. To Install:Place the Fig. 980 onto the "bracing pipe". Tighten the set bolt until the head breaks off. Attachment can pivot for adjustment to proper brace angle. Approvals:—Underwriters Laboratories Listed in the USA (UL)and Canada (cUL). For FM Approval information refer to page 61. Note:Fig. 980 Swivel Attachment and Fig. 1001, 1000, 2002, 4A or approved attachment to pipe that make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association (NFPA) Finish:Plain. Contact Cooper B-Line for alternative finishes and materials. Order By:Figure number and finish. Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174, Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730, Pat. #7,669,806 Cooper B-Line, Inc.’s (“Cooper B-Line”) seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly. Cooper-B-Line’s warranty for seismic bracing components will be the warranty provided in Cooper B-Line’s standard terms and conditions of sale made available by Cooper B-Line, except that, in addition to the other exclusions from Cooper B-Line’s warranty, Cooper B-line makes no warranty relating to Cooper B-Line’s seismic bracing components that are combined with products not provided by Cooper B-Line. Longitudinal BraceLateral Brace Fig. 980 - Universal Swivel Sway Brace Attachment - 3/8” to 3/4” Part Mtg. Hdw.Mounting Hole Max. Design Approx. Number Size ABDLoad (cULus) Wt./100 in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) 980-3/8 3/8”(9.5)51/4”(133.3)17/8”(47.6)13/32”(10.3)2765 (12.30)133 (60.3) 980-1/2 *1/2”(12.7)51/4”(133.3)17/8”(47.6)17/32”(13.5)2765 (12.30)132 (59.7) 980-5/8 5/8”(15.9)51/4”(133.3)17/8”(47.6)11/16”(17.5)2765 (12.30)131 (59.4) 980-3/4 3/4”(19.0)51/4”(133.3)17/8”(47.6)13/16”(20.5)2765 (12.30)130 (58.9) * Standard size. B D A 980 Mounting Hardware Is Not Included Set Bolt Included Fig. 4L Fig. 980 Size ½” ¾” 1” 1 ¼” 1 ½” 2” A 2.22 2.47 2.97 3.56 4.06 4.69 B 2.03 2.38 2.75 3.00 3.72 3.72 C (closed) 3.38 3.50 4.25 4.75 5.50 5.50 Ship Wt. (lbs.) 0.69 0.94 1.76 2.50 3.26 5.32 Qty. Unit Pack 12 6 6 4 2 2 Qty. Per Case 72 60 36 24 12 12 UNITED BRASS WORKS, INC. 714 S. Main St., Randleman, NC 27317 Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com Model 125SUL Globe Valve Soft Disc UL Listed for Fire Sprinkler Service at 250 WOG 200 WOG @ 180 ° Max 100% Pressure Tested Threaded Ends • Integral Seat Rising Stem Swivel Disc Holder MATERIAL LIST NO. DESCRIPTION MATERIAL 1 Hex Nut Steel 2 Hand Wheel Aluminum 3 Packing Nut Brass 4 Packing Graphite Non-Asb. 5 Bonnet (½” – 1”) Bonnet (1¼” – 2”) Brass Bronze 6 Stem & Disc Assm. Brass 7 Disc Buna N 8 Body Bronze MATERIAL LIST NO. DESCRIPTION MATERIAL 1 Screw Stainless Steel 2 Hand Wheel Aluminum 3 Packing Nut Brass 4 O-Ring Nitrile 5 Washer Brass 6 Stem Brass 7 Body Bronze Size ¼” A 1.750 B 1.734 C 2.469 Ship Wgt. (lbs.) 0.34 Qty. Per Ctn. 25 Model 76 Gauge Test Valve 300 WOG @ 180 ° Max 100% Pressure Tested Screwed Ends UNITED BRASS WORKS, INC. 714 S. Main St., Randleman, NC 27317 Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD- designed for hydrodynamic efficiency and available in 2"/50 mm – 3"/80 mm (Series 717H) and 2 ½"/65 mm – 12"/300 mm (Series 717) sizes. Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa. See chart below for approved services for the Series 717 valves. In both valve designs, the single-disc mechanism incorporates a spring-assisted feature for non- slamming operation. This spring-assisted, single-disc design achieves a leak-free seal with as little as 5ft /1.5m of head. Series 717 and 717H FireLock Check Valves can be installed either vertically (flow upwards only) or horizontally. A cast flow arrow indicator is provided to assist with proper valve orientation. Both valves include upstream and downstream pressure taps. Each valve is factory-tested to the rated working pressure. For systems requiring a Riser Check option, refer to publication 10.09. Grooved ends allow fast, easy installation with just two Victaulic couplings or the valve may be mounted to flanged (ANSI CL.150) equipment using either to Victaulic Style 741 Vic-Flange® or Style 744 FireLock flange adapters on either end. Size Approval/Listing Service Pressures Series 717H cULus FM LPCB Vds 2"/50 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 2 1/2"/65 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 76.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 3"/80 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 4"/100 mm n/a n/a n/a n/a 5"/125 mm n/a n/a n/a n/a 139.7 mm n/a n/a n/a n/a 6"/150 mm n/a n/a n/a n/a 165.1 mm n/a n/a n/a n/a 8"/200 mm n/a n/a n/a n/a 10"/250 mm n/a n/a n/a n/a 12"/300 mm n/a n/a n/a n/a Approval/Listing Service Pressures Size Approval/Listing Service Pressures Series 717 cULus FM LPCB VdS 2"/50 mm n/a n/a n/a n/a 2 1/2"/65 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa n/a 76.1 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 3"/80 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 4"/100 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 5"/125 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 139.7 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 6"/150 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 165.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 8"/200 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 348 psi/2400 kPa up to 16bar/232 psi 10"/250 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 12"/300 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 10.08_1 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ WWW.VICTAULIC.COM VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_P SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS Series 717 (4 − 12"/100 − 300 mm) Series 717H High Pressure Check Valve (2 – 3"/50 – 80 mm) Series 717 (2½ − 3"/65 − 80 mm) DIMENSIONS – Series 717 C A B TYPICAL 2 1/2 – 3"/65 – 80 MM R A 3 C ED 1J 2 BK P 2 1 3 ½" NPT Upstream Drain ½" NPT Downstream Drain 2" NPT (Drain Optional) TYPICAL 4 – 8"/100 – 200 MM A C ED J 2 1 P BK 12 ½" NPT Upstream Drain ½" NPT Downstream Drain TYPICAL 10 – 12"/250 – 300 MM Size Dimensions- Inches/millimeters Approx.Wgt. Ea. NominalSizeInchesmm ActualOutside DiameterInchesmm E to EA B C D E J K P R Lbs.kg 2 1/2 2.875 3.88 4.26 3.57 ——————3.66573.0 99 108 91 1.6 76.1 mm 3.000 3.88 4.26 3.57 ——————3.676.1 99 108 91 1.6 3 3.500 4.25 5.06 4.17 ——————4.58088.9 108 129 106 2.0 4 4.500 9.63 6.00 3.88 2.75 3.50 2.00 4.50 3.50 3.35 20.0100114.3 245 152 99 70 89 51 114 89 85 9.1 5 5.563 10.50 6.80 4.50 —4.17 2.15 5.88 4.08 3.98 27.0125141.3 267 173 114 106 55 149 104 101 12.3 139.7 mm 5.500 10.50 6.80 4.50 —4.17 2.15 5.88 4.08 3.98 27.0139.7 267 173 114 106 55 149 104 101 12.3 6 6.625 11.50 8.00 5.00 —4.50 2.38 6.67 4.73 3.89 38.0150168.3 292 203 127 114 61 169 120 99 17.2 165.1 mm 6.500 11.50 8.00 5.00 —4.50 2.38 6.67 4.73 3.89 38.0165.1 292 203 127 114 61 169 120 99 17.2 8 8.625 14.00 9.88 6.06 5.05 5.65 2.15 8.85 5.65 5.75 64.0200219.1 356 251 154 128 144 55 225 144 146 29.0 10 10.750 17.00 12.00 7.09 5.96 6.69 2.15 10.92 6.73 —100.0250273.0 432 305 180 151 170 55 277 171 45.4 12 12.750 19.50 14.00 8.06 6.91 7.64 2.51 12.81 7.73 —140.0300323.9 495 356 205 176 194 64 925 196 63.5 Size Dimensions- Inches/millimeters Approx.Wgt. Ea. NominalSizeInchesmm A B C D E J K P R Lbs.kg 2 8.66 6.46 3.23 1.48 3.02 2.80 ——4.25 10.760.3 219.8 164.1 82.1 37.5 76.7 71.0 108.0 4.9 2 1/2 9.37 6.94 3.31 1.66 3.40 3.38 ——4.38 13.873238.0 176.3 84.1 42.2 86.4 85.9 111.3 6.3 76.1 mm 9.37 6.94 3.31 1.66 3.40 3.38 ——4.38 13.8238.0 176.3 84.1 42.2 86.4 85.9 111.3 6.3 3 9.62 7.44 3.53 1.91 3.65 3.38 ——4.63 20.088.9 244.3 189.0 89.7 48.5 92.7 85.9 117.6 9.1 TYPICAL 2"/60.3 mm − 3"/88.9 mm DIMENSIONS - Series 717H "D" BA C E R J 10.08_2 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_P MATERIAL SPECIFICATIONS Body: Ductile Iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Body Coating: Series 717H Body: Black Paint Series 717H Endface: Electroless Nickel Series 717 (2 ½ – 3"): PPS Coating Series 717 (4 – 12"): Black Paint Body Seat: Series 717H – Nitrile O-ring installed into an electroless nickel plated endface Series 717 (2 ½ – 3"): PPS Coated ductile iron Series 717 (4 – 12"): Welded Nickel Disc Seal or Coating: • Grade “T” Nitrile (Series 717H ONLY) Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range; except hot, dry air over +140°F/+60°C and water over +150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. • Grade “E” EPDM (Series 717 ONLY) EPDM (green color code). Temperature range -30ºF to +230ºF/-34ºC to +110ºC. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2 – 3"/50 – 80 mm): CF8M Cast Stainless Steel • Series 717 (2 ½ – 3"): Aluminum bronze with elastomer seal • Series 717 (4 – 12"/100 – 300 mm) Elastomer-coated ductile iron Shaft: • Series 717H (2 – 3"/50 -80 mm): Brass • Series 717 (2 ½ – 3"): Type 416 Stainless Steel • Series 717 (4 – 12"/100 – 300 mm) Type 316 Stainless Steel Spring: All sizes Type 302/403 Stainless Steel Shaft Plug: • Series 717H (2 – 3"/50 – 80 mm): Type 416 Stainless Steel • Series 717 (2 ½ – 12"/65 – 300 mm): Carbon steel zinc plated Pipe Plug: • Series 717H (2 – 3"/50 – 80 mm): carbon steel zinc plated • Series 717 (4 – 12"/100 – 300 mm): Carbon steel zinc plated 10.08_3 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_P FLOW CHARACTERISTICS The charts below express the flow of water at 60ºF/16ºC through valve. S717H / 717HR 0.1 1 10 10 100 1000 Flow (GPM)Pressure Loss (psi)2"3"2.5" S717H / 717HR 1.00 10.00 100.00 100 1000 10000 Flow Rate (L/Min)Pressure Loss (Kpa)2"2.5"3"PRESSURE LOSS - P.S.I.0.1 1 10 10 100 1000 FLOW RATE - G.P.M. S717H / 717HR 100 1000 100001.00 10.00 100.00 FLOW RATE (Litres/Min) S717H / 717HR PRESSURE LOSS - (kPa)2" & 50 mm 2½" & 76 mm 3" & 80 mm 2" & 50 mm 2½" & 76 mm3" & 80 mm 10.08_4 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_P FLOW CHARACTERISTICS The charts below express the flow of water at 60ºF/16ºC through valve. S717 / 717R 0.1 1 10 10 100 1000 10000 100000 Flow (GPM)Pressure Loss (psi)4"5"6"8"10"12"2-1/2"3" S717 / 717R 1.00 10.00 100.00 10 100 1000 10000 100000 Flow Rate (L/Min)Pressure Loss (Kpa)4"5"6"8"10"12"2.5"3" S717 / 717R FLOW RATE - G.P.M.PRESSURE LOSS - P.S.I.0.1 1 10 10 100 1000 10000 1000006" & 165 mm"8" & 200 mm10" & 250 mm12" & 300 mm2½" & 76 mm3" & 80 mm4" & 100 mm5" & 139 mm"S717 / 717R 100.00 PRESSURE LOSS - (kPa)FLOW RATE (Litres/Min) 10.00 1.0010.00 100 1000 10000 1000002½" & 76 mm3" & 80 mm4" & 100 mm5" & 139 mm6" & 165 mm8" & 200 mm10" & 250 mm12" & 300 mm10.08_5 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_P WARRANTY This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE Refer to the Warranty section of the current Price List or contact Victaulic for details. Series 717 and Series 717H Check Valves can be installed either vertically (flow up only) or horizontally (with hinge on top) - making sure the flow arrow matches the flow direction through the pipeline. Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. INSTALLATION 10.08 FireLock® Check Valves SERIES 717 – cULus, FM, VdS, LPCB SERIES 717H HIGH PRESSURE – cULus, FM, VdS, LPCB 10.08IPS CARBON STEEL PIPE - FIRE PROTECTION VALVES For complete contact information, visit www.victaulic.com 10.08 1479 REV P UPDATED 6/2011 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2011 VICTAULIC COMPANY. ALL RIGHTS RESERVED. Model RM-1 Riser Manifold Commercial and Residential Page 1 of 8 AUGUST 2018 TFP963 Worldwide Contacts www.tyco-fire.com IMPORTANTRefer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. General Description The TYCO commercial and residential Model RM-1 Riser Manifold provide the necessary waterflow alarm, pres-sure gauge, alarm test orifice, drain, and sight glass equipment in a single assembly for use in NFPA 13 com-mercial sprinkler systems and in NFPA 13D/13R residential sprinkler systems as follows: NFPA 13*• 1-1/2 in. (DN40)Male Thread x Female Thread • 2 in.– 6 in. (DN50 – DN150)Groove x Groove NFPA 13D• 1 in. (DN25)Female Thread x Female Thread NFPA 13R• 1-1/2 in. (DN40)Male Thread x Female Thread • 2 in. (DN50)Groove x Groove * Although the Riser Manifold described in this techni- cal data sheet is intended for NFPA 13 sprinkler sys- tems, it may be used for NFPA 13D or 13R residential sprinkler systems, where a test orifice of 2.8K or 4.2K is acceptable. The variety of sizes and grooved end connections allow cost effective and easy transition to check valves, control valves, and system piping. The Model RM-1 Riser Manifolds may be installed either horizontally (flow switch on top) or vertically (flow going up) orientation, for both single sprinkler rises and floor control in high-rises. Optional Pressure Relief Kits feature a 175 psi pressure relief valve and trim components for convenient integration into commercial and residential riser manifold assemblies. The pressure relief valve, installed in manifold assemblies above the nor-mally closed test and drain or drain valve, automatically bleeds system pressure exceeding 175 psi through a flexible hose connected to the mani-fold drain outlet (Ref. Figure 5), reduc-ing system pressure to 175 psi. NOTICE The Model RM-1 Riser Manifolds described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions. Technical Data Approvals UL and ULC Listed FM Approved Listed by California State Fire Marshall Maximum Working Pressure300 psi (20,7 bar) Test Orifice 1 in.– 3 in. (DN25 – DN80) Manifolds: 2.8K 4 in.– 6 in. (DN100 – DN150) Manifolds: 4.2K FinishRed Painted TFP963 Page 2 of 8 Nominal Riser Size Inches (DN) End Connections Nominal Dimensions Inches (mm) Nominal Drain Size Inches (DN) Inlet Outlet A B C D E F G H 1-1/2 (40)Thread MNPT Thread FNPT 10 (254)15-1/2 (394)2-1/4 (57)5-5/8 (143)8-3/8 (213)15 (381)4-3/8 (111)1-1/4 (32) 2 (50)Groove Groove 13 (330)18 (457)2-1/16 (53)5-5/8 (143)8-3/8 (213)15-1/4 (388)4-3/8 (111)1-1/4 (32) 2-1/2 (65)Groove Groove 13 (330)18-1/16 (460)2-1/16 (53)5-5/8 (143)8-3/8 (213)15-1/4 (388)4-3/8 (111)1-1/4 (32) 3 (80)Groove Groove 13 (330)18-1/16 (460)2-1/16 (53)5-7/8 (150)8-5/8 (219)15-3/4 (400)4-3/8 (111)1-1/4 (32) 4 (100)Groove Groove 13 (330)20-1/4 (514)4-1/4 (108)6-3/4 (172)10-3/4 (273)18-3/8 (467)5-3/16 (132)2 (50) 6 (150)Groove Groove 13 (330)20-1/4 (514)4-1/4 (108)7-3/4 (197)11-3/4 (300)21 (533)6-3/4 (172)2 (50) NO DESCRIPTION P/N 1 300 psi/2000 kPaWater Pressure Gauge . .90050001 2 Test and Drain Valve, Model TD-1: 1-1/2 – 3 Inch(DN40 – DN80)Size Manifolds,1-1/4”, 2.8K Orifice.....A61G0420 4 – 6 Inch(DN100 – DN150)Size Manifolds,2”, 4.2K Orifice ........A61G0601 3 Flow Switch, VSR-M: 1-1/2” (DN40).........91144815 2” (DN50) ............91144802 2-1/2” (DN65).........91144825 3” (DN80) ............91144803 4” (DN100) ...........91144804 6” (DN150) ...........91144806 4 Field Replaceable Retard/Switch......... 91144800 G E F H 2 D INLET OUTLET A C 3, 4FLOW1 B OPTIONAL PRESSURE RELIEF TRIM CONNECTION FIGURE 1 MODEL RM-1 COMMERCIAL RISER MANIFOLDS 1-1/2 – 6 INCH (DN40 – DN150) TFP963 Page 3 of 8 NO DESCRIPTION P/N 1 300 psi/2000 kPa Water Pressure Gauge . .90050001 2 Ball Valve, 1” (DN25)....97111603 3 Flow Switch, VSR-M,1” (DN25) ............911448014Field ReplaceableRetard/Switch.........91144800 NO DESCRIPTION P/N 1 300 psi/2000 kPa Water Pressure Gauge . .90050001 2 Ball Valve, 1” (DN25)....97111603 3 Flow Switch, VSR-M,1-1/2” (DN40).........91144815 4 Field Replaceable Retard/Switch.........91144800FLOW1" NPT(FEMALE) 2-1/2"(64 mm) 3-7/8"(100 mm) 10-1/8"(257 mm) 4-5/8"(118 mm) 3-3/4" (96 mm) 1"NPTDRAIN 10"(254 mm) 2 1" NPT (FEMALE) 3, 4 11"(280 mm) 1 OPTIONALPRESSURERELIEF TRIMCONNECTION 3-7/8"(100 mm) 10" (254 mm) 1-1/2" NPT (MALE) 7/16" (11 mm) 1-1/2" NPT (FEMALE) 4-3/4" (121 mm) 3-7/8"(100 mm) 1 FLOW2 3, 4 11-3/8"(290 mm) 13-1/4"(337 mm) OPTIONALPRESSURERELIEF TRIMCONNECTION 1"NPTDRAIN FIGURE 2 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1 INCH (DN25) FIGURE 3 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1-1/2 INCH (DN40) TFP963 Page 4 of 8 Manifold Installation TYCO Model RM-1 Riser Manifold must be installed in accordance with this section. The Model RM-1 Riser Manifold may be installed either horizontally (flow switch on top) or vertically (flow going up). The inlet of the Riser Manifold may be con-nected directly to a shut-off control valve. Notes: Where applicable pipe thread sealant is to be applied sparingly. Use of a non-hardening pipe thread sealant is recommended. Never remove any piping component nor correct or modify any piping defi-ciencies without first depressurizing and draining the system. Provisions for an alarm test flow on Residential Models must be made. The alarm test flow is to be through an orifice having a flow capacity equal to or smaller than the smallest orifice sprinkler in the system. One of two options can be considered. The first option is to temporarily install a test orifice in the outlet of the drain line prior to performing the alarm test. The second option is to install an Inspec-tor’s Test Connection downstream of the Waterflow Alarm Switch. Step 1. Install the manifold body with the flow arrow pointing in the down-stream position using threaded con-nections and/or listed mechanical grooved connections, as applicable. Step 2. Connect the drain line and on commercial manifolds set the Model TD-1 Test and Drain Valve to the OFF position or on residential manifolds close the drain valve. Step 3. Refer to Figure 6 for wiring guidance. All wiring must be performed in accordance with the authority having jurisdiction and/or the National Electri-cal Code. Step 4. Refer to Figure 5 for Optional Pressure Relief Trim installation. Step 5. Place the system in service by filling the system with water. When filling the system, partially open the control valve to slowly fill the system. Filling the system slowly will help avoid damaging the waterflow alarm switch. After the system is fully pressurized, completely open the control valve. Step 6. Secure all supply valves open. NO DESCRIPTION P/N 1 300 psi/2000 kPaWater Pressure Gauge . .90050001 2 Ball Valve, 1” (DN25)....97111603 3 Flow Switch, VSR-M,2” (DN50) ............91144802 4 Field ReplaceableRetard/Switch.........91144800 3-7/8"(100 mm) 1/2" (13 mm) 5" (127 mm) 4-1/8"(105 mm) 2" (GROOVED) 2" (GROOVED) 13"(330 mm) 2 3, 4 1 FLOW11-7/8"(300 mm) 16"(406 mm) OPTIONALPRESSURERELIEF TRIMCONNECTION 1"NPTDRAIN FIGURE 4 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 2 INCH (DN50) TFP963 Page 5 of 8 Optional Pressure Relief Trim Installation Model RM-1 commercial and resi-dential riser manifold assemblies are designed to accommodate an optional pressure relief valve and trim compo-nents (Ref. Figure 5). Optional pressure relief trim must be installed in accordance with the follow-ing procedures. Notes: For assembly in Riser Manifolds installed and in service, verify the fire protection system is de-pressurized and drained. Close the system supply control valve, set commercial manifold test and drain valve to DRAIN or open residential drain valve to relieve resid-ual pressure and drain system. Make certain that drainage water will not cause any damage or injury. Refer to Care and Maintenance section for other requirements when closing a fire protection system control valve and placing system in service. Apply thread sealant or TEFLON tape on all threaded connections, with the exception of internally sealed flexible hose connections. Commercial Manifolds Refer to Figure 1 for commercial riser manifold features and Figure 5 for pres-sure relief trim components described in this procedure. Step 1. Remove 1/2 in. pipe plug from manifold tee. Inspect exposed female tee threads, remove thread sealant remnants or debris as necessary. Step 2. Install Pressure Relief Valve (1) in manifold tee, orienting valve outlet port perpendicular to and facing away from manifold body. Step 3. Install 1/2 in. x Close Nipple (2) in pressure relief valve outlet port. Step 4. Disconnect drain piping from grooved outlet of manifold TD-1 test and drain valve as applicable and install Figure 323 Grooved Reducing Tee (4) on valve outlet by securing with Fig-ure 577 Grooved Coupling (5), align-ing tee threaded branch outlet parallel with pressure relief valve outlet port. Reconnect drain piping to Figure 323 tee drain outlet as necessary. Note: Refer to Technical Data Sheet G901 for Figure 577 Grooved Coupling installation and assembly instructions. Step 5. Install Flexible Hose (3) by threading female ends onto 1/2 in. x close nipple installed on relief valve outlet port and onto Figure 323 reduc-ing tee branch outlet. Note: Assure Flexible Hose is not sus-ceptible to being caught or snagged by other moving equipment. Residential Manifolds Refer to Figures 2, 3 or 4 for residen-tial riser manifold features and Figure 5 for pressure relief trim components described in this procedure. Step 1. Remove 1/2 in. pipe plug from manifold tee. Inspect exposed female tee threads, remove thread sealant remnants or debris as necessary. Step 2. Install Pressure Relief Valve (1) in manifold tee, orienting valve outlet port perpendicular to and facing away from manifold body. Step 3. Disconnect drain piping from threaded outlet of manifold drain valve as applicable and install 1 in. x Close Nipple (5) in valve outlet. Step 4. Install Figure 815 Reducing Tee (4) onto 1 inch x close nipple, align-ing tee branch outlet parallel with pres-sure relief valve outlet port. Reconnect drain piping to Figure 815 tee drain out-let as necessary. Step 5. Install 1/2 in. x Close Nipples (2) in pressure relief valve outlet port and in Figure 815 reducing tee branch outlet. Step 6. Install Flexible Hose (3) by threading female ends onto 1/2 in. x close nipples installed on relief valve outlet port and Figure 815 reducing tee branch outlet. Note: Assure Flexible Hose is not sus-ceptible to being caught or snagged by other moving equipment. Residential Riser Manifolds NO DESCRIPTION P/N 1 Pressure Relief Valve, 175 psi, 1/2” NPT..........1001184-01 2 1/2” x Close Nipple, Qty 2 . . . 1001023-01 3 Flexible Hose, 1/2” x 16” . . . . 1001266-03 4 Figure 815 Threaded Reducing Tee, 1” x 1” x 1/2” NPT .........1001259-07 5 1” x Close Nipple . . . . . . . . . . 1001025-01 Commercial Riser Manifolds NO DESCRIPTION P/N 1 Pressure Relief Valve, 175 psi, 1/2” NPT..........1001184-01 2 1/2” x Close Nipple ........1001023-01 3 Flexible Hose: 1-1/2 – 3 Inch (DN40 – DN80) Size Manifolds, 1/2” x 24”................1001266-02 4 – 6 Inch (DN100 – DN150)Size Manifolds,1/2” x 30”................1001266-01 4 Figure 323 Reducing Tee, Grooved x NPT Threaded: 1-1/2 – 3 Inch (DN40 – DN80)Size Manifolds,1-1/4” x 1-1/4” x 1/2”.......3231305GS 4 – 6 Inch (DN100 – DN150)Size Manifolds,2” x 2” x 1/2” .............3232005GS 5 Figure 577 Rigid Grooved Coupling: 1-1/2 – 3 Inch (DN40 – DN80)Size Manifolds,1-1/4”...................57713AGCP 4 – 6 Inch (DN100 – DN150) Size Manifolds, 2” ......................57720AGCP 3 45 MODEL RM-1 COMMERCIAL RISER MANIFOLD 12 MODEL RM-1 RESIDENTIAL RISER MANIFOLD 1 3 2 5 4 2 FIGURE 5 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLDS OPTIONAL PRESSURE RELIEF TRIM INSTALLATION TFP963 Page 6 of 8 NOTE: NOTE: CONTACT RATINGS: SWITCH TERMINAL CONNECTIONS IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD CAUTION: For supervised circuits, see "Switch Terminal Connections" above. The Waterow AlarmSwitch has two switches, one can be used to operate a central station, proprietary or remotesignaling unit, while the other contact is used to operate a local audible or visual annunciator. When connecting to a UL Listed control panel, use panel resistor rating for circuit supervision Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC An uninsulated section of a single conductor is notpermitted to be looped aroundthe terminal and serve as twoseparate connections. Thewire must be severed to serveas two separate connections,thereby providing supervisionof the connection in the eventthat the wire becomesdislodged from the terminal. NO NC COM COM NONC WIRE NUT FIRE PANEL ORADDRESSABLEMODULE WIRE NUT LOCALAUDIBLE/VISUALANNUNCIATOR BLACKWHITENEUTRALWHITE BLACK(LINE/HOT)CIRCUITBREAKERLOAD OUT TOAUDIBLE/VISUALANNUNCIATORINCOMING OUTGOING SINGLECONDUCTOR UNINSULATEDLOOPED SECTION CLAMPING PLATE TERMINAL SEPARATE CONDUCTORS CLAMPINGPLATETERMINAL SEVEREDSTRIPPEDENDS FIGURE 6 MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD WIRING GUIDANCE TFP963 Page 7 of 8 Care and Maintenance TYCO Riser Manifolds RM-1 must be serviced and maintained in accordance with this section. Before closing a fire protection system control valve for inspection or main-tenance work on the fire protection system that it controls, permission to shut down the effected fire protection system must first be obtained from the proper authorities and all person-nel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni-toring proprietary and/or central station alarms. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA 25), in addi- tion to the standards of any authority having jurisdiction. Contact the install-ing contractor or product manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes. Note: No attempt is to be made to repair any Riser Manifold component in the field. Only the pressure gauge, waterflow alarm switch, or relief valve can be replaced. If any other problems are encountered the entire riser mani-fold must be replaced. The alarm/flow test procedure will result in operation of the associated alarms. Consequently, notification must be given to the owner and the fire department, central station, or other signal station to which the alarms are connected, and notification must be given to the building occupants. The following inspection procedure must be performed as indicated, in addition to any specific requirements of the NFPA, and any impairment must be immediately corrected: Alarm/Flow Test ProcedureStep 1. Place the Model TD-1 Test and Drain Valve in the TEST position (Ref. Figure 7). On residential assemblies without a test orifice, temporarily install a test orifice in the drain outlet and fully open the Drain Valve. Make certain that drainage water will not cause any damage or injury. Step 2. Verify operation of associated alarms. Step 3. Verify that the residual (i.e., flowing) pressure indicated by the pres-sure gauge is no less that originally recorded for the system when it was first installed. Step 4. Close the Drain Valve on the Residential models and the Test and Drain valve on commercial models. Step 5. Verify that the static (i.e., not flowing) pressure indicated by the pres-sure gauge is no less that originally recorded for the system when it was first installed. DRAIN MARKINGON HANDLEPOSITIONEDON DETENT OFF MARKINGON HANDLEPOSITIONEDON DETENT SET CONDITION FRONT VIEW SIGHTFLOW TEST CONDITION DRAINCONNECTION TEST MARKINGON HANDLEPOSITIONEDON DETENT DRAIN CONDITION MODEL TD-1TEST ANDDRAINVALVE FIGURE 7 MODEL RM-1 COMMERCIAL RISER MANIFOLD TD-1 TEST AND DRAIN VALVE OPERATION TFP963 Page 8 of 8 NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indi-cate the full product name, including description and part number (P/N). Riser ManifoldsSpecify: Size (specify) Connection Type (specify inlet x outlet) Model RM-1 Riser Manifold, P/N (specify): Commercial1-1/2 in. (DN40) MT x FT . . . . . . . . . . . . . .405512 in. (DN50) G x G . . . . . . . . . . . . . . . . . . .406012-1/2 in. (DN65) G x G . . . . . . . . . . . . . . . . 406113 in. (DN80) G x G . . . . . . . . . . . . . . . . . . .406214 in. (DN100) G x G . . . . . . . . . . . . . . . . . .406516 in. (DN150) G x G. . . . . . . . . . . . . . . . . . .40661Residential1 in. (DN25) FT x FT. . . . . . . . . . . . . . . . . .406711-1/2 in. (DN40) MT x FT . . . . . . . . . . . . . .405712 in. (DN50) G x G . . . . . . . . . . . . . . . . . . .40591 Optional 175 psi Pressure Relief KitSpecify: Pressure Relief Kit, Model RM-1 Riser Manifold, (specify Commer-cial or Residential application), (specify size range), P/N (specify): Commercial 1-1/2 in. – 3 in. (DN40 – DN80) 40721 4 in. – 6 in. (DN100 – DN150) 40731 Residential 1 in.– 2 in. (DN25 – DN50) . . . . . . . . . . . . . . 40711 Replacement PartsSpecify: Model RM-1 Riser Manifold (specify part description), P/N (specify from Figures 1, 2, 3, 4 or 5) Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. MATERIAL LIST NO. DESCRIPTION MATERIAL 1 Body Brass 2 Tail Piece Brass 3 Ball Stainless Steel Size ½” ¾” Ship Wgt. (lbs.) 0.43 0.56 Qty. Unit Pack 12 12 UNITED BRASS WORKS, INC. 714 S. Main St., Randleman, NC 27317 Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com Model 235 Ball Drip Valve 200 lbs. WOG Valve unseats only by force of gravity causing ball to fall off seat. Use only in horizontal position. Do Not Use with more than 1 ft. of head (water pressure) on ball check. MFG. #5401076 - REV H 5/08 UL Listed Strobe Horn Dimensions: 9-1/4" h x 10" w x 4" d Voltages Available: SASH-24 (24VDC) SASH-120 (120VAC) Environment: Indoor or Outdoor use Weatherproof backbox is included with both models Termination: Separate terminals for horn and strobe Finish: Red with white lettering SASH-24 Stock No. 1000555 SASH-120 Stock No. 1000560 The SASH series is a multitone horn/strobe combination designed for use as an audio visual indication for automatic sprinkler systems. It can be installed in conjunction with or in place of water motor gongs. SASH SERIES SPRINKLER ALARM STROBE HORN/SIGN COMBINATION PAGE 1 OF 1PRINTED IN USA Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com Strobe Intensity, dBA, and Current Ratings Model SASH-24 Input Current SASH-120 Input Current Typical Anechoic dBA at 10 ft. Tone Amps at 24V DC Amps at 115V AC At Nominal Input Voltage HI STD HI STD HI STD Horn 0.038 0.024 0.050 0.040 99 93 Bell 0.019 0.012 0.040 0.038 92 87 March Time Horn 0.038 0.024 0.050 0.040 99 93 Code-3 Horn 0.038 0.024 0.050 0.040 99 93 Code-3 Tone 0.027 0.016 0.042 0.038 95 90 Slow Whoop 0.047 0.025 0.050 0.040 99 94 Siren 0.034 0.022 0.045 0.040 98 93 Hi/Lo 0.020 0.013 0.041 0.039 93 88 Strobe Candella 75 15 Strobe Current (If the strobe and audible operate on the same circuit, add the strobe current to the tone current.) 0.102 0.060 Wiring Information SASH-24 STROBE AND HORN POWERED BY THE SAME CIRCUIT SASH-24 STROBE AND HORN POWERED FROM SEPA- RATE CIRCUIT SASH-120 OPERATED BY WATERFLOW SWITCH DWG# 1076-1 STR AUD STR AUD CONTACTS CLOSE ON ALARM WATERFLOW SWITCH N STR L N AUD L Fire Sprinkler Accessories 1 800 344-1822 • www.fppi.com31 Fire Department Connections Open Snoot Assembly Each kit contains one open snoot, 2½" IPS brass wall plate(AUTOSPRINKLER) and a 2½" plug with chain, boxed and labeled. 2" FNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 24 09-590-00 09-590-01 09-590-08 09-590-10 09-590-11 09-590-06 09-590-12 09-590-07QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-590-02 09-590-14 09-590-09 09-590-03 09-590-04 09-590-13 09-590-15 09-590-052½" MNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 18 09-616-00 09-616-01 09-616-08 09-616-10 09-616-11 09-616-06 09-616-12 09-616-07QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-616-02 09-616-14 09-616-09 09-616-03 09-616-04 09-616-13 09-616-15 09-616-052½" FNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 24 09-600-00 09-602-00 09-600-08 09-600-10 09-600-11 09-612-00 09-600-12 09-614-00QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-602-00 09-600-14 09-600-09 09-606-00 09-608-00 09-600-13 09-600-15 09-610-003" MNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 10 09-630-00 09-630-01 09-630-08 09-630-10 09-630-11 09-630-06 09-630-12 09-630-07QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-630-02 09-630-14 09-630-09 09-630-03 09-630-04 09-630-13 09-630-15 09-630-053" MNST x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 16 09-631-003" FNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 10 09-632-00 09-632-01 09-632-08 09-632-10 09-632-11 09-632-06 09-632-12 09-632-07QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-632-02 09-632-14 09-632-09 09-632-03 09-632-04 09-632-13 09-632-15 09-632-053" MNPT x 3" NSTBox Qty. 10 09-634-003" FNPT x 3" NSTBox Qty. 10 09-636-00 Open Snoots (Continued) NEW REGIONALTHREADS Rough Brass - Female Pin Lug, Hose Thread Swivels2½" FNPT x 2½" NST BCT CF CIN-new CIN-old CLV Dayton DETBox Qty. 10 09-650-00 09-652-00 09-650-08 09-650-10 09-650-11 09-662-00 09-650-12 09-664-00QSTNovaScotiaNYFDONTPHXRaleighRichmondTEM09-654-00 09-650-14 09-650-09 09-656-00 09-658-00 09-650-13 09-650-15 09-660-00 Installation Each wall pipe should be installed on the corresponding pipe size to maintain proper fit and performance. The wall plates’ rigid construction requires that it be installed as the pipe to be fitted is put in place. As the pipe is being installed through the surface to which the plate will provide stability, install the wall plate over the end of the pipe and move to it’s desired location. Once the length of pipe has been properly installed and the pipe hangers have been adjusted to their final elevation, move the wall plate to it’s final desired location. Tighten the set screw while maintaining the wall plate in its’ desired final location. If the wall plate is being used to prevent the movement of pipe through the “wall” or floor penetration. It is necessary to use one wall plate on each side of the wall or floor to secure the pipe from additional movement. This product is not suitable or approved as earth quake bracing. Specifications Material: Malleable Iron Finish: Galvanize coating Sizes & Dimensions: 1” (31/4 OD) 11/4” (4” OD) 11/2” (41/4” OD) 2” (43/4” OD) 21/2” (51/2” OD) 3” (6 1/4” OD) 4” (7 1/4” OD) 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description Designed for “light” stabilization of pipe penetrating wall or floor structures. Features one piece rigid construction. Each wall plate has been galvanized to resist corrosion and is provided with a set screw to keep the wall plate in place. Available in sizes 1” IPS through 4” IPS. WWW.FPPI.COM Wall Plate w/Set Screw Galvanized Malleable Iron 8 8 5 8 Installation Installation of the wall plate occurs after installation of piping materials and appropriate fire stop materials (if required) has occurred. Simply open the wall plate, install around piping and close, making sure to secure the two halves with the clasp. The wall plate will “automatically” center itself on the pipe. No tools are required for proper installation. Specifications Type: Steel hinged w/springs Material: .046” colded rolled steel Finish: Chrome Available sizes: 1/2” thru 10” IPS 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description Fire Protection Products’ plated steel hinged wall plate has been designed to offer aesthetically pleasing concealment of pipe penetrations through walls. Utilizing two piece hinged construction allows for easy installation and closure around pipe diameters from 1/2” IPS to 10” IPS. Centering springs are used for “automatic” alignment and a secure installation on the pipe. A simple clasp allows for the wall plate to stay in place. Available in chrome finish. Caution: May not provide proper sealing to provide fire wall or smoke penetration ratings. An approved fire stop material should be used for this purpose. WWW.FPPI.COM Steel Hinged Wall Plates w/Springs Specifications Material: Painted Plain Steel Finish: Red enamel Styles: 3 Spare sprinklers, 1/2 or 3/4 6 Spare sprinklers, 1/2 or 3/4 6 Spare, ESFR, 1/2, 3/4 or 1” 12 Spare sprinklers 1/2 or 3/4 24 Spare sprinklers 36 Spare sprinklers 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets are available in six configurations. Three head, six head, six head ESFR, twelve head, twenty-four head and thirty-six head. All six styles are manufactured with “knockouts” to accommodate the most common size sprinklers. The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red enamel finish. Each spare head cabinet comes with a hinged door which remains closed to protect the spare sprinklers from the elements and features two holes on the back panel to allow for attachment to most surfaces utilizing the appropriate fasteners. Not intended for exposed or harsh environments. WWW.FPPI.COM Spare Sprinkler Head Storage Cabinet Installation Select the correct Spare Sprinkler Head Cabinet in accordance with the Automatic Sprinkler Systems Handbook. As per the 1989 Edition the correct number of spare sprinkler is as follows: 0-300 sprinklers, not less than 6; 300-1000, not less than 12; 1000 or more, not less than 24. Stock of spare sprinklers shall include all types and ratings installed.* Once the correct Spare Sprinkler Head Cabinet has been selected, installation is accomplished by inserting the correct fastener in each of the two holes inside the cabinet, securing the cabinet securely to the wall. The insert the correct number and type of sprinklers in accordance with the “handbook”. *Final determination is subject to approval by the AHJ. Installation Installation of aluminum signs is accomplished by several methods. The most common installation procedure is to use #16 Single Jack chain to hang the sign on the area being identified. Since all of the above mentioned signs are predrilled at all four corners, the last link of the chain can be opened and hooked through the top holes on the signs and hung on the appropriate valve or piping. The signs may also be fastened to a flat surface with fasteners appropriate to the base material. (The 9” x 7” Fire Alarm Bell sign must be drilled with a 1/4” hole if it is to be attached directly to the bell gong.) Specifications Material: .020” aluminum with removable plastic coating Sizes: 6” x 2” 4” x 6” 5” x 7” 9” x 7” 12” x 10” 8.5” x 11” 7” Round See current catalog for a full listing of all available signs. 3198 LIONSHEAD AVE CARLSBAD, CA 92010 TEL + 1 760 599-1168 + 1 800 344-1822 FAX + 1 800 344-3775 © 2012 Fire Protection Products, Inc. Description Manufactured from .020” white coated aluminum. All sign types are screen printed with a fade resistant red ink. Each sign is shipped with a clear protective plastic coating which can be re- moved at time of installation. Each sign type meets or exceeds NFPA13 requirements. All signs (except 7” round) are drilled in four corners to allow for easy installation. All signs (except 7” round) may be installed with sign chain or with any fastener that is suitable for the material that the sign is being attached. The 7” round bell signs are center drilled to allow for installation directly to the bell gong assembly. Type “A” 9” x 7” Control valve signs are drilled with the same four hole pattern as Type “B” 6” x 2” signs to allow for attachment of Type “B” to Type “A”. WWW.FPPI.COM Identification Signs 1/238