October 28, 2021
RE: TEXAS ROADHOUSE #TBD
Water Supply Test and Site Flow Analysis
870 Harmon Stream Blvd.
Bozeman, MT
The requested water supply test and site flow analysis for the subject project are detailed in this report
and submitted for review and posting.
Water Model Test Results:
Date/Time Performed: October 7th, 2021
Fire Hydrant Flow Test Effective Point: At the 4” lead-in connection to the 8” main behind proposed
location (Marked on Site Sketch – Attachment #1)
Static = 105 psi; Residual = 94 psi @ 2,000 gpm
Available flow at 20 psi (at effective point) = 6,034 gpm
Static Pressure @ BOR = 96.5 psi
Available Pressure @ 295 gpm at the BOR = 96.5 psi
Available Pressure @ 730 gpm at the BOR = 84.5 psi
Test Elevation Relative to BOR: Even with the assumed finish floor elevation (4870 ft. AMSL)
Safety Factor Utilized in Calculations: 5 psi
A Fire Pump WILL NOT be required
A Water Tank WILL NOT be required
Fireline Backflow Preventer Required: Double Check Type Backflow Preventer.
Device assumed for deduct in calculations: 4-inch Ames 3000SS double check backflow preventer
This needs to be approved by the civil engineer. This is a recommendation only and should not be used
for construction or exact main locations.
Should you have any questions regarding this matter, do not hesitate to contact me.
Sincerely,
Ken Greenfield,
Fire Protection Consultant
Phone: (480) 848-1417
Email: kgreenfield@telgian.com
Attachment #1 – Site Sketch
Attachment #2 – Water Supply Plot – Fire Calculations
Attachment #3 – City of Bozeman Water Model
TEXAS
ROADHOUSE
7,831 sf
±0.44 ACRES
HUFFLINE L
A
N
E
OPEN SPACE 6
± 1.46 ACRES
SITE SKETCH 3 - 7,831 sf
DATE: MAY 27, 2021
GF PROJECT #: 20210037.0
TEXAS ROADHOUSE - BOZEMAN, MT
SEQ HUFFLINE LANE AND HARMON STREAM B;VD
PARKING: REQUIRED PROVIDED
TBV SPACES 197 SHARED
SPACES
2 PAGE 1 OF 5
PROJECT:
LOCATION:
CITY/STATE:
Static (psi) Residual (psi) Flow (gpm)Gauge Hydrant
Elevation (ft)
Building FFE
(ft)
105 94 2000 4870 4870
Outlet
Diameter #1
(in)
Hydrant
Coefficient #1 Pitot #1 (psi)
Outlet
Diameter
#2 (in)
Hydrant
Coefficient #2 Pitot #2 (psi)
Outlet
Diameter #3
(in)
Hydrant
Coefficient
#3
Pitot #3
(psi)
Outlet
Diameter
#4 (in)
Hydrant
Coefficient
#4
Pitot #4
(psi)
Test By: Date: Time:
4‐inch Type: Mfg:AMES Model:
Mfg: Model:
0 730 295 gpm psi
Static (psi)
1. 105 103.5 104.5 730 22
2. 0 0 0 295 32
0 ‐7 ‐1
4.105 96.5 103.5
5.‐3.5 ‐7 ‐2
6. 0 0 0
7. 101.5 89.5 101.5
8.‐5 ‐5 ‐5
9. 96.5 84.5 96.5
10.
11.
Pump Test
Calculated Demands
Additional Demands
3.
Not applicable
Residual (psi)
Pressure available at test
Elevation Adjustment
Pressure loss due to friction
Pressure at base of riser
upstream of BFP & meter
BFP loss/preload
Water meter loss
Pressure at base of riser
downstream of BFP & meter
Safety factor
Total base of riser pressure
Not applicable
Bozeman, MT
ATTACHMENT #
WATER SUPPLY SITE SURVEY Texas Roadhouse
FIRE SPRINKLER DEMAND 870 Harmon Stream Blvd.
Flow Rate (gpm)
Gauge Hydrant Location:Water Model (See attachment)
Flow Hydrant Location:
City of Bozeman Water Model 10/7/2021
Backflow Prevention: Size:3000SSDouble Check
730gpm @ 22psi
295gpm @ 32psi
0
10
20
30
40
50
60
70
80
90
100
110
120
0 250 500 750 1000 1250 1500 1750 2000 2250 2500Pressure (psi)Flow (gpm)
Observed Flow Test Point
Raw Water Flow Test
#4 Below
#7 Below
#9 Below
Target Demand
Target Demand
Target Demand
Additional Demand
Additional Demand
Additional Demand
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 10/28/2021 C:\USERS\KGREENFIELD\DOCUMENTS\HASSDATA\BOZEMAN.SDF
JOB TITLE:
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SRC 105.0 94.0 2000.0 104.7 295.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 295.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 295.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 0.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 4870.0 - - - - 104.7 - - -
BOR 4870.0 HOSE STREAM 103.5 295.0
SRC 4870.0 SOURCE 104.7 295.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 10/28/2021 C:\USERS\KGREENFIELD\DOCUMENTS\HASSDATA\BOZEMAN.SDF
JOB TITLE:
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 1.00 140 0.0
SRC 4870.0 104.7 295.0 BOR D8.000 ---- 0.00 -0.0
1 4870.0 104.7 295.0 8.390 1.00 0.001 0.0
Pipe: 2 H.S. 295.0 Disch E:17.0 20.00 140 1.2
1 4870.0 104.7 0.0 D4.000 T:34.0 54.00 -0.0
BOR 4870.0 103.5 295.0 4.220 G: 3.0 74.00 0.016 1.2
NOTES (HASS):
(1) Calculations were performed by the HASS 2020 D computer program
in accordance with NFPA13 (2016)
under license no. 64622609 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2) The system has been calculated to provide an average
imbalance at each node of 0.037 gpm and a maximum
imbalance at any node of 0.037 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 6.8 ft/sec at pipe 2.
(4) Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
(5) Available pressure at source node SRC under full flow conditions is
104.68 psi with a flow of 294.99 gpm.
(6) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G N F
Ell Tee LngEll ChkVlv BfyVlv GatVlv NPTee F45Ell
4.220 17.00 34.00 10.00 37.00 20.00 3.00 34.00 8.50
8.390 31.00 59.00 22.00 76.00 20.00 7.00 59.00 15.50
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 10/28/2021 C:\USERS\KGREENFIELD\DOCUMENTS\HASSDATA\BOZEMAN.SDF
JOB TITLE:
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SRC 105.0 94.0 2000.0 103.3 730.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 730.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 730.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 0.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 4870.0 - - - - 103.3 - - -
BOR 4870.0 HOSE STREAM 96.9 730.0
SRC 4870.0 SOURCE 103.3 730.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 10/28/2021 C:\USERS\KGREENFIELD\DOCUMENTS\HASSDATA\BOZEMAN.SDF
JOB TITLE:
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 1.00 140 0.0
SRC 4870.0 103.3 730.0 BOR D8.000 ---- 0.00 -0.0
1 4870.0 103.3 730.0 8.390 1.00 0.003 0.0
Pipe: 2 H.S. 730.0 Disch E:17.0 20.00 140 6.4
1 4870.0 103.3 0.0 D4.000 T:34.0 54.00 -0.0
BOR 4870.0 96.9 730.0 4.220 G: 3.0 74.00 0.086 6.4
NOTES (HASS):
(1) Calculations were performed by the HASS 2020 D computer program
in accordance with NFPA13 (2016)
under license no. 64622609 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2) The system has been calculated to provide an average
imbalance at each node of 0.093 gpm and a maximum
imbalance at any node of 0.093 gpm.
(3) Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.7 ft/sec at pipe 2.
(4) Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
(5) Available pressure at source node SRC under full flow conditions is
103.30 psi with a flow of 729.98 gpm.
(6) PIPE FITTINGS TABLE
HASS Pipe Table Name: standard.pip
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G N F
Ell Tee LngEll ChkVlv BfyVlv GatVlv NPTee F45Ell
4.220 17.00 34.00 10.00 37.00 20.00 3.00 34.00 8.50
8.390 31.00 59.00 22.00 76.00 20.00 7.00 59.00 15.50
CITY OF BOZEMAN
Fire Flow Request Form
PHONE (406) 582-3200 FAX (406) 582-3201
Date October 7, 2021
Location Texas Roadhouse, 870 Harmon Stream Blvd
Pressure Zone Northeast HGL 5038
GIS Hydrant ID# 2264
Adjacent Main Size 8-inch DI
Model Scenario Maximum Day Demand, Steady State, Fire Flow
Reference 2017 Water Facility Plan Update1
Hydrant Curves An Excel Spreadsheet with hydrant curves has been provided for the requested
location
Requested Location via the Bozeman Infrastructure Viewer2
If you have questions or need further information feel free to email.
Data Disclaimer: Water distribution information is calculated using hydraulic modeling software and is subject to
variation. Actual field conditions may vary. This information is provided to the requestor for evaluation purposes only,
without warranty of any kind, including, but not limited to any expressed or implied warranty arising by contract, stature, or
law. In no event regardless of cause, shall the City be liable for any direct, indirect, special, punitive or consequential
damages of any kind whether such damages arise under contract, tort, strict liability or inequity.
HOME OF MONTANA STATE UNIVERSITY
GATEWAY TO YELLOWSTONE PARK
1 https://www.bozeman.net/government/engineering/permits-plans-projects 2 https://gisweb.bozeman.net/Html5Viewer/?viewer=infrastructure
GIS Hydrant #Available Flow (gpm) Residual Pressure (psi)22640 105.32200 104.77400 104.14600 103.37800 102.481,000.00101.471,200.00100.351,400.0099.121,600.0097.771,800.0096.332,000.0094.772,200.0093.122,400.0091.372,600.0089.522,800.0087.563,000.0085.513,200.0083.363,400.0081.113,600.0078.773,800.0076.334,000.0073.84,200.0071.174,400.0068.444,600.0065.624,800.0062.715,000.0059.75,200.0056.65,400.0053.415,600.0050.125,800.0046.756,000.0043.286,200.0039.726,400.0036.086,600.0032.346,800.0028.517,000.0024.67,200.0020.597,400.0016.57,600.0012.327,800.008.048,000.003.67Hydrant Curve 0204060801001200 1000 2000 3000 4000 5000 6000 7000 8000 9000Residual Pressure (psi)Available Flow (gpm)Hydrant Curve 2264Data Disclaimer: Water distribution information is calculated using hydraulic modeling software and is subject to variation. Actual field conditions may vary. This information is provided to the requestor for evaluation purposes only, without warranty of any kind, including, but not limited to any expressed or implied warranty arising by contract, stature, or law. In no event regardless of cause, shall the City be liable for any direct, indirect, special, punitive or consequential damages of any kind whether such damages arise under contract, tort, strict liability or inequity.