HomeMy WebLinkAbout018_Hydrant Flow Test Data
CITY OF BOZEMAN
Fire Flow Request Form
PHONE (406) 582-3200 FAX (406) 582-3201
Date November 11, 2021
Location 1608 West Beall
Pressure Zone South (HGL 5125)
GIS Hydrant ID# 464
Adjacent Main Size 8-inch Cast Iron
Model Scenario Maximum Day Demand, Steady State, Fire Flow
Reference 2017 Water Facility Plan Update1
Hydrant Curves An Excel Spreadsheet with hydrant curves has been provided for the requested
location
Requested Location via the Bozeman Infrastructure Viewer2
If you have questions or need further information feel free to email.
Data Disclaimer: Water distribution information is calculated using hydraulic modeling software and is subject to
variation. Actual field conditions may vary. This information is provided to the requestor for evaluation purposes only,
without warranty of any kind, including, but not limited to any expressed or implied warranty arising by contract, stature, or
law. In no event regardless of cause, shall the City be liable for any direct, indirect, special, punitive or consequential
damages of any kind whether such damages arise under contract, tort, strict liability or inequity.
HOME OF MONTANA STATE UNIVERSITY
GATEWAY TO YELLOWSTONE PARK
1 https://www.bozeman.net/government/engineering/permits-plans-projects 2 https://gisweb.bozeman.net/Html5Viewer/?viewer=infrastructure
GIS Hydrant #Available Flow (gpm) Residual Pressure (psi)16080 127.66200 127.16400 126.38600 125.34800 124.061,000.00 122.551,200.00 120.81,400.00 118.841,600.00 116.661,800.00 114.272,000.00 111.672,200.00 108.862,400.00 105.862,600.00 102.652,800.00 99.253,000.00 95.663,200.00 91.873,400.00 87.893,600.00 83.733,800.00 79.374,000.00 74.834,200.00 70.114,400.00 65.24,600.00 60.114,800.00 54.835,000.00 49.385,200.00 43.745,400.00 37.935,600.00 31.945,800.00 25.776,000.00 19.436,200.00 12.916,400.00 6.226,581.43 0.01Hydrant Curve 0204060801001201400 1000 2000 3000 4000 5000 6000 7000Available Flow (gpm)Hydrant Curve 1608Data Disclaimer: Water distribution information is calculated using hydraulic modeling software and is subject to variation. Actual field conditions may vary. This information is provided to the requestor for evaluation purposes only, without warranty of any kind, including, but not limited to any expressed or implied warranty arising by contract, stature, or law. In no event regardless of cause, shall the City be liable for any direct, indirect, special, punitive or consequential damages of any kind whether suchdamages arise under contract, tort, strict liability or inequity.