HomeMy WebLinkAbout005 Accessibility DetailsLanding Ramp Run Landing Ramp Run Landing
Ramp RunFig. 405.7
Edge Protection and Handrail Extensions
(a) Straight
(b) Change in Direction
Lavatories and Mirrors Fig. 602.5
Drinking Fountain Spout Location
(b) ElevationANSI 606 + 1002.11.2.2
Side
Mirror per 603.3
Lever Hardware per 309.4
Bowl Depth shall be 6 1/2" Min. per 606.5
Exposed Pipes shall be Insulated or otherwise
Configured to protect against contact per 606.6
Knee and Toe clearances per 306.3
(a) Plan
Wheelchair AccessibleStanding Persons60" Min.60" Min.60" Min.60" Min.At Least asWide as Ramp RunTo Bottom of Reflecting Surface40" Max.27" Min.34" Min.5" Max.15" Min.36" Max.38" - 43"Reinforced Areas for installation of Grab Bars and Seat
CL
Control Wall
Transfer-Type Shower
36" Min.18" Min.15" Min.
Control Area
per 608.5
Shower Spray Unit shall be
Provided w/ a Hose 59" Long
Min. and can be Used as a
Fixed or Hand-Held Shower
36" Adjustable Shower Bar
shall not Obstruct the use of
Grab Bars
The Control shall be located 10"
from the Center to the Open
Side of the Bathtub and 43"
above the Bathroom Floor 43".48".Reinforced Areas for installation of Grab Bars and Seat
Reinforced Areas for installation of Grab Bars and Seat
Reinforced Areas for installation of Grab Bars and Seat
Reinforced Areas for installation of Grab Bars and Seat
1'-6" Min.
15" - 16"
2 1/2" Max.
36" Min
Back Wall
Seat per 610.3
Note: Grab Bar not
Req'd at Time of
Construction where
reinforment has been
provided per
1002.11.1
Note: Grab Bar not
Req'd at Time of
Construction where
reinforment has been
provided per
1002.11.1
Seat Wall 0' - 0 3/8"0' - 0 9/32"
36" Min.
36" Min.
CL
15".18".48".43".The Control shall be located 10" from the
Center to the Open Side of the Bathtub
and 43" above the Bathroom Floor
Shower Spray Unit shall be Provided
w/ a Hose 59" Long Min. and can be
Used as a Fixed or Hand-Held Shower
36" Adjustable Shower Bar shall
not Obstruct the use of Grab Bars
Control Area per 608.5
60" Min.
0' - 0 1/8"0' - 0 1/8"38".48".27" Max.
Note: Grab Bar not Req'd at Time of
Construction where reinforment has been
provided per 1002.11.1
Control Wal
Roll-in Type Shower
ANSI 608 + 1002.11.2
ANSI 608 + 1002.11.2
Back Wall
15" - 16"
12" Max.24" Max.9".17" - 19"Note: Grab Bar not Req'd at Time
of Construction where reinforment
has been provided per 1002.11.1
Note: Removeable In-tub Seat
not Req'd per 1002.11.6
Head End Wall 33" - 36"12" Min.
Foot End Wall
4" Max.18".4".CL
ANSI 607 + 1002.11.2
Control Area
per 608.5
Tub/Shower Spray Unit shall be Provided
w/ a Hose 59" Long Min. and can be
Used as a Fixed or Hand-Held Shower
The Control shall be located 8"
from the Center to the Open
Side of the Bathtub and 24"
above the Bathroom Floor
Fig. 608.2.3
Alternative Roll-in Type Shower
Compartment Size and Clearance
24" - 36"36" Min.36" Min.CLCL
CL
Note: Inside Finished Dimensions Measure at
the Center Points of the Opposing Sides
CLCL
CL
48" Min.36" Min.36" Min.36" Min.Back Wall
Control Wall
Seat Wall
Fig. 608.2.1
Transfer-Type Shower Compartment Size and
Clearance
Fig. 610.3.2
L-Shape Shower Compartment Seat
2 1/2" Max.
15"-16"
22"-23"1 1/2" Max.14"-15"3" Max.Fig. 608.4.3
Alternative Roll-in Type Shower
Control and Hand Shower Location
Fig. 608.2.2
Standard Roll-in Type Shower Compartment Size and
Clearance
Fig. 608.3.1
Grab Bars in Transfer-Type Showers6" Max.6" Max 6" Max.
Side Wall
Side Wall
Front Wall
CL
CL CL
60" Min.30" Min.30" Min.Back Wall
Side Wall
Side Wall
Back Wall
Control Wall
18".4" Max.Fig. 604.3
Size of Clerance for Water Closet
Communication Features Intercom/Directory
Directory
Highest Control
Lowest Control
70" Max.4"-12"80"-96"ANSI 702 + 1006
Note: Dwelling Unit Smoke Dectector
shall include Audible Notification
complying with NFPA 72
Wall Alarm w/ Smoke Detector
Wall Alarm
(a)
60" Min.56" Min.CL
18" Min.66" Min.Fig. 604.9.2
Wheelchair Accessible Compartments
(b)
60" Min.
(b) Floor Mounted Water Closet -Wall Hung(b) Wall Hung Water Closet
60" Min 56" Min.18".
4" Max.12" Min.52" Min.59" Min.36" Min.6" Max.
0' - 1 5/16"
Clear Floor
Space
42" Min.
CL CL
16"-18"7"-9"15" Min.33"-36"18" Min.33"-36"12" Max.
39"-41"
54" Min.
Dispenser
SideFront17"-19"33"-36"12" Min.24" Min.
36" Min.
ANSI 604 + 609
ANSI 609 + 1002.11.2
SideFront
Dispenser
Toilet Controls to
be on Open Side
17"-19"33"-36"12" Min.24" Min.
36" Min.
Note: Grab Bar not Req'd at Time
of Construction where reinforment
has been provided per 1002.11.1
CL
7"-9"15" Min.33"-36"1 1/2" Min.54" Min.
12" Max.
Fig. 505.10.3
Bottom Handrail Extensions at Stairs
Note: X+ Tread Depth
(a)
Fig. 505.10.1
Top and Bottom Handrail
Extensions at Ramps
12" Min.12" Min.
X X
2" Max.
1 1/4" Min.2 1/4" Max.4" to 6 1/4" Perimeter
(a)(a)(b)
Circular Cross Section Non-Circular Cross Section4" - 7"3 0° M a x.Radius 1/2" Max.
1 1/2" Max.1 1/2" Max.
(c) Curved Nosing (d) Beveled Nosing
(a) Radius of Tread Edge
(Typical for all Profile)
(d) Beveled Nosing
Fig. 504.2
Treads and Riser for Accessible Stairways
34" to 38"(a) Stairs
Fig. 504.5
Stair Nosing
Fig. 505.4
Handrail Height
34" to 38"34" to 38"(b) Ramps (c) Walking Surfaces
1 1/2" Min.1 1/2" Min.Fig. 505.5
Handrail Clearance
SCALE:
DRAWN:
PROJECT NO:
PO box 1001 Bozeman, MT 59771
DATE:
12" = 1'-0"
1/7/2022 11:01:28 AM
A0.11
20001
Accessibilty DetailsSix Range CondominiumsPaine Group4270 W Babcock Street, Bozeman MTDRC Site Plan Resubmittal 2021.01.07