HomeMy WebLinkAboutEngineering Report - WaterEngineering Report
Water Main Extension
Six Range Condominiums Development
July 2022
Submitted to:
City of Bozeman Engineering Department
20 East Olive
Bozeman, MT 59715
Prepared by:
Stahly Engineering and Associates
851 Bridger Drive, Suite 1
Bozeman, MT 59715
(406) 522-8594
Water Mains 1 8/8/2022
Water Main Extension Engineering Report
Contents
Note: The Engineering Report format follows DEQ-1 organization. Additional
information required by the City of Bozeman Design Standards is added where
required.
Report Narrative
1.1.1 General Information
1.1.2 Extent of Water Works System
1.1.3 Alternate Plans
1.1.4 Site Conditions
1.1.5 Water Use Data
1.1.6 Flow Requirements
1.1.7 Sources of Water Supply
1.1.8 Proposed Treatment Processes
1.1.9 Sewage System Available
1.1.10 Waste Disposal
1.1.11 Automation
1.1.12 Project Sites
1.1.13 Financing
1.1.14 Future Extensions
Figures and Tables
Figure 1. Vicinity Map
Figure 2. Water Plan
Table 1. Domestic Water Design Flow
Appendices
Hydraulic Analysis
Hydraulic Network Exhibit
Water Mains 2 7/14/2022
1.1.1 General Information
The proposed Six Range Condominiums Development is located
southwest of the intersection of West Babcock Street and South Ferguson
Avenue. The Six Range Condominiums Development consists of 3 large
apartment buildings,4 triplexes, and a smaller commercial building. This
project is located on a currently undeveloped 8.64-acre lot, Tract A1 of
Minor Subdivision #338.
The proposed apartment buildings consist of units ranging from one to
three-bedrooms, and each triplex unit will be three bedrooms. The
apartment buildings will provide 63 one-bedroom units, 102 two-bedroom
units, and 15 three-bedroom units. The four triplexes will provide 12
additional three-bedroom units. The commercial building will provide 2500
sf of office space and 1300 sf of retail space.
The project will be served by extension of City of Bozeman water and
sewer mains throughout the project. City of Bozeman water and sewer
mains currently exist in West Babcock St., Slough Creek Dr., and Mill
Creek Dr. Individual service lines will be provided to each apartment,
triplex, and the single commercial building. City of Bozeman water mains
currently exist in Slough Creek Dr., W. Babcock St., and Mill Creek Dr.
The developer’s contact information is:
Paine Group
Matt Paine
P.O. Box 418
Bozeman, MT 59771
Water supply and wastewater treatment will be provided by the City of
Bozeman’s municipal systems. The system owner’s contact information is:
City of Bozeman Public Service Department
PO Box 1230
Bozeman, MT 59771-1230
The location of the Six Range Condominiums Development is shown on
the Vicinity Map in Figure 1.
Water Mains 3 7/14/2022
Figure 1. Vicinity Map, Bozeman, Montana
1.1.2 Extent of Water Works System
Water supply in this area is provided from an existing 12” main in West
Babcock Street. On the west side of the lot, an 8” looping main is
extended from the West Babcock Street main to provide service to the
residences in the new development. South of the site, an 8” main runs
along Palisade Drive providing service to the single-family residences in
the adjacent development. A water main has been stubbed at the property
line in the southeast corner of the lot from this main, which will be tied into
with the Six Range project and looped.
Water supply for the proposed development will primarily be provided by
extending 8” mains within the site—making looped connections in
Babcock, and Mill Creek Dr. The commercial building will be served off of
a main extended from the 12” Babcock main. Along the southern portion
of the lot, an 8” main will be extended north from the existing main in Mill
Creek Drive, approximately 60 ft, then run east-west within the southern
property boundary approximately 900. Another 8” main will branch off of
the east-west main—running north and servicing the four triplexes and
looping into the Babcock 12” main. Finally, another 8” extension off of the
Water Mains 4 7/14/2022
12” Babcock main at the intersection of Kimball Ave to service Building B.
A total of 9 fire hydrants are proposed for the development to provide
adequate fire protection for the development. A total of 1,824 lineal feet of
8” water main is proposed. Each water main will run within a 30’ wide
water/sewer easement, or within street rights-of-way. Individual water and
fire service connections will be made for each building, with Building B
having 2 service connections. The full extents of the existing and
proposed water system can be seen in the attached C2.0 “Water Plan”
included at the end of this report.
Irrigation will be supplied by a well to be drilled on the southern portion of
the site. The proposed water system improvements are shown on the
Water Plan (Figure 2) at the end of this report.
The development’s water main extension has been designed in
accordance with Montana Department of Environmental Quality Circular 1,
and the City of Bozeman Design Standards and Specifications Policy.
Construction specifications will be Montana Public Works Standards and
Specifications (MPWSS), and the City of Bozeman Modifications to
MPWSS.
New water main will be in 30’ wide water and sewer easements and street
rights-of-way running through the property.
1.1.3 Alternate Plans
Due to the project’s location within the City of Bozeman, extension of
public mains was the only water supply alternative. Distribution
alternatives were explored, and the proposed design was selected to
provide main looping and eliminate dead ends.
1.1.4. Site Conditions
The Six Range Condominiums Development is located at the southwest
quadrant of the intersection of West Babcock Street and South Ferguson
Avenue. The 8.64 acre lot is currently undeveloped. Adjacent
development consists primarily of residential subdivisions. The lot is
bounded by West Babcock Street, South Ferguson Avenue, South Hanley
Drive to the west, and an asphalt path to the south. Due to the adjacent
residential development, water, sewer, and shallow utilities are readily
available for connection in the area. The Vicinity Map, seen in Figure 1 in
this report, shows the existing conditions and surrounding development.
A geotechnical evaluation was conducted by Allied Engineering and is
provided in a separate appendix of this submittal. The soil conditions
Water Mains 5 7/14/2022
across the site are consistent. The geotechnical investigation revealed
that the site consists of predominantly native soils including 12 to 18
inches of topsoil overlaying sandy gravel. A DIPRA analysis was
conducted for the site and determined that neither zinc-coated pipe nor V-
Bio wrap is necessary for the new water main materials. Full geotechnical
evaluation results are available in the attached Appendix A.
Groundwater monitoring was conducted throughout the 2022 groundwater
season. During the initial site evaluation and monitoring well installation,
groundwater depths ranged from 5-6’ below existing grade. Based on
these results, seasonally high groundwater is assumed to be at least 5’
below existing grade. The site is not located within a 100-year floodplain.
Storm Drainage Plan Description
1.1.5. Water Use Data
Domestic water will be provided by the City of Bozeman Municipal system.
This project is located within the planned service area of the City’s system.
Estimated water use for the Six Range Condominiums development has
been determined utilizing values provided in City design standards and
Facility Plans and is shown in Table 1. For water main sizing, typical City
design flows are utilized.
Because the water system will not supply irrigation, large summer peaks
are not anticipated. Typical design flow water use is 65 gallons per day
(gpd) per capita, with an average of 2.17 people per dwelling. To estimate
peak flows, a peaking factor of 4.5 was used to determine the peak hour
flow rate. The estimated total project design flow is 27,175 gpd with a
peak hour flow of 84.91 gpm.
Water Mains 6 7/14/2022
Table 1 – Domestic Water Design Flow
Estimated Domestic Water and Sewer
Demands
Residential #Units Capita/Unit Gpd/Capita Gpd/Unit Gallons/Day
Building A 48 2.17 65 141 6,770
Building B 75 2.17 65 141 10,579
Building C 57 2.17 65 141 8,040
Triplexes 12 2.17 65 141 1,693
Non-Residential Area (Sf) Gpd/1,000 Sf Gallons/Day
Office Space 2,500 30 75
Retail Space 600 30 18
Total Domestic Design Flow (Gpd) 27,175
Average Day Demand (Gpm) 18.87
Peaking Factor 4.5
Peak Hour (Gpm) 84.91
Total Estimated Annual Use (Ac/ft) 30.44
Irrigation will be provided by a new well located at the south end of the site
as shown on Figure 2. Irrigation lines will provide water to site landscaping
and will be maintained by the property owner.
The estimation of the domestic water demand for each building is based
on proposed building use, utilizing standard City of Bozeman design
values. Payment of cash-in-lieu of water rights will be used to provide
water rights for this project.
At $6,000 per ac-ft/yr, the estimate for CILWR fee is $182,649.10.
1.1.6. Flow Requirements
As stated previously, the peak hour water demand is estimated to be
84.91 gpm. Stahly produced a hydraulic model of the site as it fits into the
City of Bozeman’s water distribution system and calibrated the model
based on a hydrant flow test conducted by the City of Bozeman on July 7,
2022 (see enclosed flow report in the appendix).
The hydraulic model shows that fire flows are expected to be 3500 gpm on
the Six Range site without dropping below 20 psi in the system.
The 2017 City of Bozeman Water Facility Plan did not identify any fire flow
capacity limitations in this area.
Water Mains 7 7/14/2022
1.1.7. Sources of Water Supply
This section is not applicable.
1.1.8. Proposed Treatment Process
This section is not applicable.
1.1.9 Sewage System Available
Sewer service is provided by new City mains extended through the site
from the existing sewer main in W. Babcock St. Sewers will be
approximately 8-10 feet deep and primarily cross below water mains and
services.
1.1.10 Waste Disposal
This section is not applicable.
1.1.11 Automation
This section is not applicable.
1.1.12 Project Sites
This section is not applicable.
1.1.13 Financing
This section is not applicable.
1.1.14 Future Extensions
No future extensions of this main are anticipated, as surrounding
properties have all been previously developed.
W. BABCOCK ST. (90' ROW)N. FERGUSON AVE. (50' ROW)
S. HANLEY AVE.KIMBALL AVE.HANLEY AVE.SLOUGH CREEK DR.PROFESSIONALENGINEERS &SURVEYORSSIX RANGE
CONDOMINIUMS STAHLYENGINEERING& ASSOCIATESPAINE GROUP
BOZEMAN MONTANAC2.0WATER PLAN
Appendix A:
Hydraulic Anaylsis
W. BABCOCK ST. (90' ROW)N. FERGUSON AVE. (50' ROW)
S. HANLEY AVE.KIMBALL AVE.HANLEY AVE.RAVALLI ST.SLOUGH CREEK DR.FLOW (GPM)1,680130OBSERVED HYDRANT COMPARISONMEASUREDMODELSTATIC (PSI)RESIDUAL (PSI)1201201,680130FIRE FLOW AVAILABLEHYDRANT IDFLOW (GPM)H1013,500H102H103NOTE: FIRE FLOW CRITERIA IS MINIMUMOF 20 PSI IN SYSTEM. THIS CONDITION ISSTILL SATISFIED AT 3,500 GPM AT ALLPROPOSED HYDRANTS.H105H106H107H108H109H1043,5003,5003,5003,5003,5003,5003,5003,500NEW HYDRANT (H106)NEW HYDRANT (H101)NEW HYDRANT (H102)NEW HYDRANT (H104)NEW HYDRANT (H105)EX. HYDRANT (OBSERVEDHYDRANT IN FIELD TESTS)EX. HYDRANT (FLOWINGHYDRANT IN FIELD TESTS)NEW HYDRANT (H103)NEW HYDRANT (H107)NEW HYDRANT (H108)NEW HYDRANT (H109)NEW 8" WATER LINENEW 8" WATER LINENEW 8" WATER LINENEW 8" WATER LINENEW 8" WATER LINENEW MAX DAY DEMAND FOR PROP.CONSTRUCTION MODELED AT 80.5GPM (16.1 GPM EACH, PLACED ATNODES J101, J102, J103, J107, J108)BABCOCK ST. MAX DAYDEMAND MODELED AT300 GPMEX. 8" WATER LINEEX. 8" WATER LINEEX. 8" WATER LINEEX. 8" WATER LINEEX. 8" WATER LINEEX. 12" WATER LINETOWN SUPPLY MODELEDAS RESERVOIR ANDCALIBRATED TO FIELDMEASUREMENTS. .CONNECTION TOEX. SYSTEMCONNECTION TOEX. SYSTEMCONNECTION TOEX. SYSTEMCONNECTION TOEX. SYSTEMCONNECTION TOEX. SYSTEMSCALE:DRAWN:PROJECT NO:3081-001204270 W Babcock Street, Bozeman MT
Contractor Note: All site conditions and dimensions to be
varified on-site. Inform Architect of design discrepancies.PO box 1001 Bozeman, MT 5977107/11/2022DATE:PROFESSIONALENGINEERS &SURVEYORSSTAHLYENGINEERING& ASSOCIATESSix Range Condominiums
WaterCAD Figure
Paine GroupFig. 2
CITY OF BOZEMAN
HYDRANT PRESSURE/FLOW REQUEST FORM
Date: 7/7/2022
Location Hydrant # Static Pressure Pitot Pressure Residual Pressure
W Babcock & Clifton Dr 1543 84
1135 130 120
Requested By: Zach Lowe (Stahly Engineering)
Phone # 406-522-8594
Nozzle Size Flowed: 2.5”
Done By: MT / CM
Comments: 1,680 GPM
Fire Flow Node FlexTable: Fire Flow Report
Junction w/
Minimum
Pressure (Zone)
Pressure
(Calculated
System Lower
Limit)
(psi)
Junction w/
Minimum
Pressure
(System)
Pressure
(Calculated
Residual)
(psi)
Fire Flow
(Available)
(gpm)
Label
J101105J101743,500H101
J102105J102703,500H102
J10498J104643,500H103
J106107J106723,500H104
J109104J109723,500H105
J110104J110713,500H106
J111103J111693,500H107
J11392J113613,500H108
J7-1118J7-1833,500H109
Page 1 of 127 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
7/11/2022
WaterCAD
[10.03.02.75]
Bentley Systems, Inc. Haestad Methods Solution
Center3081-00120 WaterCAD.wtg
FlexTable: Junction Table
Pressure
(psi)
Hydraulic Grade
(ft)
Demand
(gpm)
Elevation
(ft)
Is Active?Label
1345,113.9504,805.00TrueH3
1305,113.9604,813.00TrueH4
1345,113.9604,805.00TrueH5
1315,114.4904,811.00TrueH101
1305,114.3704,814.00TrueH102
1315,114.1204,812.00TrueH103
1305,114.1004,813.00TrueH104
1295,113.9804,815.00TrueH105
1285,114.0004,817.00TrueH106
1285,114.0404,819.00TrueH107
1305,114.0604,814.00TrueH108
1295,114.0004,815.00TrueH109
1315,113.9804,812.00TrueHYD-1135
1335,114.0204,807.00TrueHYD-1543
1315,114.9104,812.00TrueJ-35
1315,114.4904,810.55TrueJ2-1
1325,114.3804,810.14TrueJ2-2
1325,114.1604,809.31TrueJ2-3
1325,114.0404,808.58TrueJ2-4
1345,114.0204,805.00TrueJ3
1335,114.0204,807.00TrueJ3B
1325,113.9804,808.00TrueJ4
1335,113.8904,806.00TrueJ5
1365,113.793004,800.00TrueJ6
1345,113.9904,805.00TrueJ7
1345,114.0004,805.00TrueJ7-1
1345,113.9704,805.00TrueJ8
1345,113.9604,805.00TrueJ9
1345,113.9604,805.00TrueJ10
1345,113.9604,805.00TrueJ11
1345,113.9704,805.00TrueJ12
1345,113.9604,805.00TrueJ13
1345,113.9304,805.00TrueJ14
1345,113.8904,805.00TrueJ15
1345,113.8704,805.00TrueJ16
1345,113.9504,805.00TrueJ17
1345,113.9404,805.00TrueJ18
1345,113.9004,805.00TrueJ19
1345,113.7804,805.00TrueJ20
1345,113.9904,805.00TrueJ21
1345,113.9904,805.00TrueJ22
1345,113.9204,805.00TrueJ23
1345,113.723004,805.00TrueJ26
1305,114.49164,815.00TrueJ101
1305,114.37164,815.00TrueJ102
1295,114.12164,815.00TrueJ103
1295,114.1204,815.00TrueJ104
1295,114.1004,815.00TrueJ105
1295,114.1004,815.00TrueJ106
Page 1 of 227 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
7/11/2022
WaterCAD
[10.03.02.75]
Bentley Systems, Inc. Haestad Methods Solution
Center3081-00120 WaterCAD.wtg
FlexTable: Junction Table
Pressure
(psi)
Hydraulic Grade
(ft)
Demand
(gpm)
Elevation
(ft)
Is Active?Label
1295,114.06164,815.00TrueJ107
1295,113.98164,815.00TrueJ108
1295,113.9804,815.00TrueJ109
1295,114.0004,815.00TrueJ110
1295,114.0404,815.00TrueJ111
1295,114.0604,815.00TrueJ113
Page 2 of 227 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
7/11/2022
WaterCAD
[10.03.02.75]
Bentley Systems, Inc. Haestad Methods Solution
Center3081-00120 WaterCAD.wtg
FlexTable: Pipe Table
Is Active?Length
(User
Defined)
(ft)
Length
(Scaled)
(ft)
Velocity
(ft/s)
Flow
(gpm)
Minor Loss
Coefficient
(Local)
Hazen-
Williams C
MaterialDiameter
(in)
Stop NodeStart NodeLabel
True0100.0002.700130.0Ductile Iron6.0J3BHYD-1543HL1
True0110.0002.700130.0Ductile Iron6.0J4HYD-1135HL2
True0170.0002.700130.0Ductile Iron6.0H3J17HL3
True0230.0002.700130.0Ductile Iron6.0J9H4HL4
True0200.0002.700130.0Ductile Iron6.0H5J10HL5
True0130.0002.700130.0Ductile Iron6.0H101J101HL101
True0210.0002.700130.0Ductile Iron6.0H102J102HL102
True0210.0002.700130.0Ductile Iron6.0H103J104HL103
True0220.0002.700130.0Ductile Iron6.0H104J106HL104
True0110.0002.700130.0Ductile Iron6.0H105J109HL105
True0120.0002.700130.0Ductile Iron6.0H106J110HL106
True0110.0002.700130.0Ductile Iron6.0H107J111HL107
True0110.0002.700130.0Ductile Iron6.0H108J113HL108
True050.0002.700130.0Ductile Iron6.0H109J7-1HL109
True05840.11170.000130.0Ductile Iron8.0J5J19J5-2
True1,500191.455100.000130.0Ductile Iron12.0J-35R1P1
True500170.271700.000130.0Ductile Iron16.0J22R2P1-2
True05751.455100.000130.0Ductile Iron12.0J2-1J-35P2-1
True01631.404940.000130.0Ductile Iron12.0J2-2J2-1P2-2
True03311.364780.000130.0Ductile Iron12.0J2-3J2-2P2-3
True02891.073790.000130.0Ductile Iron12.0J2-4J2-3P2-4
True0980.802830.000130.0Ductile Iron12.0J3J2-4P3
True0630.0000.000130.0Ductile Iron8.0J3J3BP3B
True01700.802830.000130.0Ductile Iron12.0J4J3P4
True03360.802830.000130.0Ductile Iron12.0J5J4P5
True03700.853000.000130.0Ductile Iron12.0J6J5P6
True01760.61960.000130.0Ductile Iron8.0J7-1J2-4P7-1
True0350.61960.000130.0Ductile Iron8.0J7J7-1P7-2
True04160.29-450.000130.0Ductile Iron8.0J7J8P8
True0470.29-450.000130.0Ductile Iron8.0J8J9P9
True03150.0110.000130.0Ductile Iron8.0J10J9P10
True04240.0110.000130.0Ductile Iron8.0J11J10P11
Page 1 of 227 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA
+1-203-755-1666
7/11/2022
WaterCAD
[10.03.02.75]Bentley Systems, Inc. Haestad Methods Solution Center3081-00120 WaterCAD.wtg
FlexTable: Pipe Table
Is Active?Length
(User
Defined)
(ft)
Length
(Scaled)
(ft)
Velocity
(ft/s)
Flow
(gpm)
Minor Loss
Coefficient
(Local)
Hazen-
Williams C
MaterialDiameter
(in)
Stop NodeStart NodeLabel
True01490.33-510.000130.0Ductile Iron8.0J12J11P12
True0340.33-520.000130.0Ductile Iron8.0J11J13P13
True04610.33-520.000130.0Ductile Iron8.0J13J14P14
True05520.29-460.000130.0Ductile Iron8.0J14J15P15
True02830.29-460.000130.0Ductile Iron8.0J15J16P16
True01970.28-440.000130.0Ductile Iron8.0J9J17P17
True02840.28440.000130.0Ductile Iron8.0J18J17P18
True01640.61950.000130.0Ductile Iron8.0J19J18P19
True07480.50-780.000130.0Ductile Iron8.0J19J20P20
True0590.33510.000130.0Ductile Iron8.0J21J7P21
True06650.33-510.000130.0Ductile Iron8.0J21J18P22
True06710.481700.000130.0Ductile Iron12.0J23J22P23
True04870.501760.000130.0Ductile Iron12.0J16J23P24
True06150.632220.000130.0Ductile Iron12.0J20J16P25
True02110.853000.000130.0Ductile Iron12.0J26J20P26
True01,3270.04-60.000130.0Ductile Iron8.0J14J23P27
True01810.10160.000130.0Ductile Iron8.0J101J2-1P101
True01660.10160.000130.0Ductile Iron8.0J102J2-2P102
True01510.63990.000130.0Ductile Iron8.0J103J2-3P103
True01720.0000.000130.0Ductile Iron8.0J104J103P104
True01310.53830.000130.0Ductile Iron8.0J105J103P105
True0110.0000.000130.0Ductile Iron8.0J106J105P106
True02440.53830.000130.0Ductile Iron8.0J107J105P107
True0590.33-510.000130.0Ductile Iron8.0J108J12P108
True0360.0000.000130.0Ductile Iron8.0J109J108P109
True01830.43-670.000130.0Ductile Iron8.0J110J108P110
True03080.43-670.000130.0Ductile Iron8.0J111J110P111
True01310.43-670.000130.0Ductile Iron8.0J107J111P112
True01470.0000.000130.0Ductile Iron8.0J113J107P113
Page 2 of 227 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA
+1-203-755-1666
7/11/2022
WaterCAD