Loading...
HomeMy WebLinkAbout015 E1SiteParkingPhotometrics LUMINAIRE SCHEDULE SYMBOL TYPE LAMPS DESCRIPTIONS MANUFACTURER CATALOG NO. OR SERIES MOUNTING/ VOLTAGE E1 63W LED FULL-CUTOFF, DECORATIVE, EXTRUDED ALUMINUM FIXTURE WITH BLACK FINISH MOUNTED TO AN ALUMINUM, ROUND, 5 INCH NON-TAPERED, 25' POLE WITH A 24" CANTELEVERED ARM. SECURE POLE TO A CONCRETE BASE AS DETAILED. SEE DETAIL 1 ON THIS SHEET. POLE SHALL BE RATED TO HANDLE FIXTURE AND ARM EPA AT 80 MPH WIND WITH 30% GUST. PROVIDE WITH TWO PIECE DECORATIVE, PHILADELPHIA STYLE BASE COVER. POLE, BASE COVER AND ARM FINISH SHALL MATCH FIXTURE. REFLECTOR SHALL BE A TYPE IV DISTRIBUTION. FUSE EACH FIXTURE AT POLE BASE HAND HOLE. ANTIQUE STREET LAMPS FIXTURE: EH16RT-63LED 350MA- K-GCF-R4- 480-1DS-ANBK ARM: EAC5/2 PNIP3-ANBK POLE: DS340-R450V200-BK-HH-AB-P9/ WHATLEY D21M BLK POLE/ 480 E2 (2) 63W LED FULL-CUTOFF, DECORATIVE, EXTRUDED ALUMINUM FIXTURE WITH BLACK FINISH MOUNTED TO AN ALUMINUM, ROUND, 5 INCH NON-TAPERED, 25' POLE WITH A 24" CANTELEVERED ARM. SECURE POLE TO A CONCRETE BASE AS DETAILED. SEE DETAIL 1 ON THIS SHEET. POLE SHALL BE RATED TO HANDLE FIXTURE AND ARM EPA AT 80 MPH WIND WITH 30% GUST. PROVIDE WITH TWO PIECE DECORATIVE, PHILADELPHIA STYLE BASE COVER. POLE, BASE COVER AND ARM FINISH SHALL MATCH FIXTURE. REFLECTOR SHALL BE A TYPE IV DISTRIBUTION. FUSE EACH FIXTURE AT POLE BASE HAND HOLE. ANTIQUE STREET LAMPS FIXTURE: EH16RT-63LED 350MA- K-GCF-R4- 480-1DS-ANBK ARM: EAC5/2 PNIP3-ANBK POLE: DS340-R450V200-BK-HH-AB-P9/ WHATLEY D21M BLK POLE/ 480 LIGHT POLE ELEVATION (TYP)POLE BASE DETAIL (TYP) LONG REINF. SEE SCHEDULE ANCHOR BOLTS FROM POLE MANF.2'-6"7' HORIZ. TIES SEE SCHEDULE PROVIDE LONG AT ALL FOUR CORNERS OF SQUARE PIER. PROVIDE SPACING OF S/2 AT TOP 1'-0" OF PEIR. DEPTH BELOW FINISHED GRADE. SPACE LONG. STEEL EVENLY AROUND PERIMETER. PROVIDE REINF. CLEARANCE PER ANCI 318. * ** *** **** ***** 3"FINISH GRADE 24" SEE SITE PLAN FOR CONDUIT SIZE 1" CHAMFER REINFORCED CONC. BASE BY E.C. BUSH CONDUITS BASE COVER PROVIDE FUSE(S) IN CKT. TO BALLAST. FUSE(S) SHALL BE BUSS TYP. BBS. FUSE HOLDERS SHALL BE BUSS "TRON" HEB WATERPROOF. SIZE OF FUSE SHALL BE AS REQUIRED BY LUMINAIRE MANUFACTURER. CONNECT GROUND TO POLE BASE W/ BOUNDRY #GB4C PROJECT ANCHOR BOLTS 3" MIN. ABOVE TOP OF BASE. PROVIDE DOUBLE NUTS FOR LEVELING UNIT (ONE ABOVE AND ONE BELOW BASE FLANGE). GROUT VOID BETWEEN BASE FLANGE AND TOP OF CONCRETE, LEAVING DRAIN HOLE. HAND FINISH. THWN CONDUCTOR AS SHOWN ON PLANS PROVIDE 1' OF COILED SLACK ON CONDUCTOR FEED THRU HANDHOLE - 4" X 6" (NOMINAL) LIGHT FIXTURE BASE SCHEDULE ***** POLE HEIGHT SIZE LONG STL HORIZONTAL STL ** 14' - 30' DEPTH ***HEIGHT AFG 7'-0"3"24" Ø (6) # 6 ****#3 AT 12" O.C.NOT FOR CONSTRUCTIONVERIFY SCALE! THESE PRINTS MAY BE REDUCED. LINE BELOW MEASURES ONE INCH ON ORIGINAL DRAWING. MODIFY SCALE ACCORDINGLY! 2021COPYRIGHT © MORRISON-MAIERLE, INC., SHEET NUMBER PROJECT NUMBER DRAWING NUMBER DATEDESCRIPTIONNO.BY N:\6883\001\ACAD\SHEETS\6883.001-LIGHTING PLAN.DWG PLOTTED BY:CODY BENDER ON Aug/26/2021 REVISIONS DRAWN BY: DSGN. BY: APPR. BY: DATE: Q.C. REVIEW DATE: BY: 2880 Technology Blvd West Bozeman, MT 59718 406.587.0721 www.m-m.net engineers surveyors planners scientists MorrisonMaierle BOZEMAN GATEWAY SUBDIVISION PUD COMMON AREA 7 & 8 PARKING PUD 6883.001 MONTANA SITE PARKING PHOTOMETRICS 14 E-1 ARG X JAU 8/2021 BOZEMAN