HomeMy WebLinkAboutMP.1MechanicalSchedulesCODES AND REQUIREMENTS A. COMPLY WITH ALL CURRENT STATE AND LOCAL BUILDING CODES AND APPLICABLE SMACNA MANUALS AND ASHRAE STANDARDS. B. COORDINATE: ALL WORK WITH OTHER TRADES. NO ADDITIONAL COMPENSATION OR TIME SHALL BE GRANTED DUE TO LACK OF COORDINATION. C. DRAWINGS ARE DIAGRAMMATIC IN NATURE. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS, AND FROM THE STRUCTURE ITSEF BEFORE FABRICATING ANY WORK. D. PROVIDE ALL CORE DRILLING, CHANNELING, CUTTING, PATCHING, TRENCHING AND BACKFILL AS REQUIRED FOR INSTALLATION OF MECHANICAL EQUIPMENT. SEAL HOLES, FIREPROOFING WHERE NECESSARY, AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE DAMAGED BY MECHANICAL WORK. USE ONLY APPROVED FIREPROOF MATERIALS WHERE FIREPROOF SEALING IS REQUIRED. REFER TO ARCHITECTURAL PLANS FOR WALLS, FLOORS, AND CEILINGS IDENTIFIED AS FIRE BARRIERS. E. OBTAIN ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK. F. PROVIDE ONE SET OF "AS-BUILT" PLANS AND SPECIFICATIONS CORRECTED UP-TO- DATE AS JOB PROGRESSES. PROVIDE OPERATION AND MAINTENANCE MANUALS FOR ALL EQUIPMENT PROVIDED FOR THIS PROJECT. FLUSHING AND CLEANING A. CLEAN AND FLUSH ALL PIPING SYSTEMS PRIOR TO PLACING IN SERVICE. PROVIDE TEMPORARY CONNECTIONS, VALVES, ETC., REQUIRED FOR THIS PURPOSE. B. AFTER FLUSHING, STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH AWWA STANDARD C651-86, AFTER MINIMUM CONTACT PERIOD, FLUSH THE SYSTEM WITH CLEAN WATER UNTIL THE RESIDUAL CHLORINE IS NO GREATER THAN THE CITY WATER. PROVIDE A TEST ANALYSIS BY THE STATE HEALTH DEPARTMENT OF A RANDOM WATER SAMPLE, IF SAMPLE IS NOT ACCEPTABLE, RE-CLEAN AND RE- TEST. SHOP DRAWINGS A. SUBMIT ONE HARD COPY SET OF SHOP DRAWINGS AND ONE ELECTRONIC SET OF SHOP DRAWINGS OF ALL EQUIPMENT TO BE USED ON THIS PROJECT TO GC. OPERATION AND MAINTENANCE MANUALS A. UPON PROJECT COMPLETION PREPARE AND SUBMIT TWO COMPLETE HARD COPY SETS AND ONE COMPLETE ELECTRONIC SET OF OPERATION MANUALS. OPERATION AND MAINTENANCE MANUALS SHALL CONTAIN ALL INFORMATION NECESSARY TO MAINTAIN, SERVICE, REPAIR, OR REPLACE ALL EQUIPMENT USED ON THIS PROJECT. INCLUDE ALL NECESSARY INFORMATION TO SET AND PROGAM THERMOSTATS OR OTHER USER PROGRAMMABLE DEVICES. HARD COPIES SHALL BE BOUND IN 3 RING BINDERS OF SUFFICIENT SIZE TO CONTAIN ALL INFORMATON. ON INSIDE COVER, PROVIDE PROJECT INFORMATION, GENERAL CONTRACTOR NAME AND CONTACT PHONE NUMBER AND E-MAIL, AND SUBCONTRACTOR NAME AND CONTACT PHONE NUMBER AND CONTACT INFORMATION. SERVICE AND MAINTENANCE A. LOCATE AND INSTALL ALL EQUIPMENT TO FACILITATE MAINTENANCE, SERVICE, REPAIR, AND REPLACEMENT OF EQUIPMENT OR COMPONENTS. EXTEND GREASE FITTINGS FOR EASE OF MAINTENANCE. ENSURE FILTER ACCESSIBILITY AND REPLACEMENT CLEARANCES ARE ADEQUATE. ENSURE COIL REPLACEMENT CLEARANCES ARE ADEQUATE. EQUIPMENT AND PIPE IDENTIFICATION A. PROVIDE EQUIPMENT IDENTIFICATION TAGS WITH IDENTIFICATION AS SHOWN ON EQUIPMENT SCHEDULES. TAGS SHALL BE PERMENANTLY AFFIXED ENGRAVED PLASTIC OR PHENOLIC WITH 1" LETTERING. B. PROVIDE PIPING IDENTIFICATION LABELS SHOWING SERVICE AS INDICATED ON PLANS AND FLOW DIRECTIONS. LOCATE LABELS AT 5 FT INTERVALS IN MECHANICAL ROOMS AND 10 FT INTERVALS ELSEWHERE. VIBRATION ISOLATION A. ALL MOTOR DRIVEN EQUIPMENT SHALL BE SUPPLIED WITH VIBRATION ISOLATION HANGERS OR SUPPORTS. ALL DUCTWORK CONNECTIONS TO MOTOR DRIVEN EQUIPMENT SHALL HAVE FLEXIBLE CONNECTIONS. ALL PIPING CONNECTING TO BASE MOUNTED PIPES SHALL HAVE STAINLESS STEEL FLEXIBLE CONNECTORS. DUCT WORK A. DUCTWORK AND FITTINGS 1. ALL DUCTWORK SHALL BE G-90 GALVANIZED STEEL WITH LOCKING TYPE SEAMS. 2. CONSTRUCT ALL HVAC DUCTWORK PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE, THIRD EDITION. 3. INSTALL DUCTWORK AS SHOWN ON DRAWINGS TIGHT TO STRUCTURE AND PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURE EXCEPT AS NOTED. CONSTRUCT AND INSTALL DUCT HANGERS PER SMACNA STANDARDS. COORDINATE WITH OTHER TRADES. 4. SEAL ALL HVAC DUCTWORK TO CLASS C SEALING STANDARDS (TRANSVERSE JOINTS). 5. DUCT SIZES SHOWN ON DRAWING ARE INSIDE CLEAR FINISHED DIMENSIONS. 6. PROVIDE FLEXIBLE CONNECTION AT ALL FANS AND AIR HANDLING UNITS. FLEXIBLE CONNECTON ARE NOT REQIRED AT EQUIPMENT WITH INTERNAL VIBRATION ISOLATION. 7. FLEXIBLE DUCT SHALL BE LIMITED TO A MAXIMUM LENGTH OF 6 FEET. NO FLEX DUCT IS ALLOWED IN APARTMENT CEILING CAVITIES. 8. INSULATE ALL INTERIOR SUPPLY DUCTWORK WITH 1-1/2" JACKETED BLANKET INSULATION WITH TAPED SEAMS. INSULATE ALL EXTERIOR DUCTWORK WITH 2" RIGID INSULATION WITH SHEET METAL OR PVC COVERING. INSULATION MATERIAL SHALL COMPLY WITH NFPA FLAME SPREAD AND SMOKE DEVELOPMENT STANDARDS. 9. DUCT ACCESS AND INSPECTION DOORS SHALL BE DOUBLE WALL INSULATED WITH HINGE AND CAM LOCK CLOSURES. PROVIDE ACCESS DOOR AT EACH FIRE DAMPER AND AT OTHER EQUIPMENT INSIDE DUCTS REQUIRING ACCESS. 10. FIRE DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH DRAWING DETAILS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. 11. RECTANGULAR DUCT SHALL HAVE TURNING VANES ON ALL SQUARE ELBOWS. 12. RECTANGULAR DUCT SHALL HAVE CENTERLINE DUCT RADIUS EQUAL TO DUCT WIDTH ON ALL RADIUS ELBOWS. 13. ROUND DUCT SHALL HAVE CENTERLINE DUCT RADIUS EQUAL TO DUCT DIAMETER. SQUARE ELBOWS ARE NOT PERMITED ON ROUND DUCT. 14. FIRE DAMPERS- 1-1/2 HR FIRE RATING WITH SLEEVE WHERE CONSTRUCTION FIRE RATING REQUIRES TO MEET NFPA 90A REQUIREMENTS. 15. DUCT SEALANT- NON-HARDENING, WATER RESISTANT, NON COMBUSTIBLE, LIQUID OR MASTIC. ALL SEALANTS SHALL HAVE APPROVED FIRE RATING FOR PLENUM APPLICATION AS REQUIRED BY CODE AUTHORITY. 16. THE BALANCING OF THE SYSTEM SHALL BE PART OF THIS CONTRACT, INCLUDE IN BID THE COST OF BALANCING AND ADJUSTING. THE AIR QUANTITIES LISTED AND A WRTTEN REPORT SHALL BE SUBMITTED TO THE ENGINEER. EQUIPMENT A. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, ACCESSORIES, AND INCIDENTALS NECESSARY WHETHER SPECIFICALLY STATED OR NOT TO MAKE THE REQUIRED MECHANICAL SYSTEMS COMPLETE AND OPERATIONAL. B. THE EQUIPMENT SCHEDULES PROVIDE MANUFACTURER AND MODEL NUMBER. OTHER EQUIPMENT MAY BE USED IF EQUAL AND APPROVED BY ENGINEER WITH A WRITTEN PRIOR APPROVAL. PLUMBING FIXTURES A. PROVIDE PLUMBING FIXTURES AS INDICATED ON THE PLUMBING FIXTURE SCHEDULE. PROVIDE TRAPS, STOPS, ESCUTCHEONS, SEALANTS, GASKETS, CAULKING, ETC. FOR COMPLETE INSTALLATION. PIPE AND DUCTWORK PENETRATIONS A. WHERE HORIZONTAL DUCTS AND PIPE PASS THROUGH WALLS, AND VERTICAL DUCTS AND PIPES PASS THROUGH FLOORING OR ROOFS SEAL OFF VOID BETWEEN OPENING AND DUCT, OR PIPE AND SLEEVE. ALL PENETRATIONS OF EXTERIOR WALL BELOW GRADE SHALL BE SEALED WATERTIGHT. ALL PENETRATIONS FOR EXTERIOR WALLS ABOVE GRADE SHALL BE SEALED WEATHER TIGHT. B. WHEREVER ANY PIPE, CONDUIT, STEEL MEMBER, BRACKET, EQUIPMENT OR OTHER MATERIAL PENETRATES OR PASSES THROUGH FIRE RESISTANT WALL, CEILING OR FLOOR, COMPLETELY SEAL VOIDS IN CONSTRUCTION WITH NON-HARDENING CAULK OR OTHER FIRE RESISTANT MATERIAL AS APPROVED BY ALL AUTHORITIES HAVING JURISDICTION. EMBED SEALING MATERIAL FULL THICKNESS OF MATERIAL BEING PENETRATED. SEALANT USED AT PENETRATIONS OF ITEMS WHICH CAN BE CONSUMED IN A FIRE SHALL BE INTUMESCENT AND SHALL BE INSTALLED SO AS TO FILL THE VOID LEFT IF PENETRANT IS CONSUMED. SEALANTS TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ASTM E-814. MOTORS AND STARTERS A. MOTORS SHALL INCLUDED THERMAL OVERLOAD PROTECTION. B. PROVIDE STARTERS OF CURRENT AND CAPACITY RATINGS TO SERVE THE MOTOR INTENDED. C. UNLESS OTHERWISE INDICATED, ALL DISCONNECTS SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR. D. DISCONNECTS SHALL COMPLY WITH CURRENT ELECTRICAL CODES. INSULATION A. ALL INSULATION AND INSULATING MATERIALS SHALL BE TESTED IN ACCORDANCE WITH ASTM 84 FOR A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPMENT RATING OF 50 OR LESS. ALL COLD WATER AND ROOF DRAIN PIPING SHALL HAVE A VAPOR BARRIER. COVER ALL EXPOSED INSULATION WITH MASTIC. PIPE INSULATION A. PROVIDE JACKETED FIBERGLASS INSULATION. 1. ROOF DRAIN AND COLD WATER PIPING 1" WITH VAPOR BARRIER 2. DOMESTIC HOT WATER AND RECIRC PIPING 1" 3. HEATING WATER SUPPLY AND RETURN PIPING 1-1/2" B. PROVIDE CLOSED CELL FLEXIBLE ELASTOMERIC COMPLYING WITH ASTM C 534 1. REFRIGERATION SUCTION 1" DUCT INSULATION A. EXTERIOR SUPPLY AND RETURN DUCTS, 2" RIGID CLOSES CELL FOAM INSULATION (BLUE BOARD) WITH METAL OR PVC COVERINGS. DOMESTIC WATER PIPING AND PLUMBING SYSTEMS A. ABOVE GROUND DOMESTIC WATER SUPPLY PIPING SHALL BE TYPE "L" COPPER WITH SOLDER JOINED FITTINGS OR MECHANICALLY FORMED JOINTS. SOLDER TO BE 95/5 TIN/ANTIMONY COMPOSITION. SELF- FLUXING SOLDER IS NOT ACCEPTABLE. BELOW GRADE DOMESTICE WATER PIPING SHALL BE TYPE K SOFT COPPER WITH NO JOINTS. B. VALVES: LEAD FREE BRONZE CLASS 125 BALL. INSTALL DIELECTRIC CONNECTIONS BETWEEN DISSIMILAR METALS. C. TEST ALL PIPING IN ACCORDANCE WITH UPC REQUIREMENTS. REPAIR LEAKS AND RE-TEST. WASTE VENT AND STORM DRAIN PLUMBING SYSTEMS A. WASTE, VENT AND ROOF DRAIN LEADER PIPING SHALL BE AS APPROVED BY LOCAL CODES AND SHALL BE SCHEDULE 40 PVC SOLID CORE PLASTIC TYPE DWV PIPE AND FITTINGS WITH SOLVENT WELD JOINTS. B. SLOPE WASTE PIPING AT ¼" PER FOOT. 1/8" PER FOOT ALLOWED ONLY WHERE INDICATED ON DRAWINGS. C. ALL FIXTURES SHALL BE VENTED. HORIZONTAL VENTS SHALL BE SLOPED AT NOT LESS THAN 1/8" PER FOOT TOWARDS DRAIN. D. ISOLATE AND TEST ALL WASTE AND VENT PIPING PER UPC REQUIREMENTS. REPAIR LEAKS AND RE-TEST. HIGH EFFICIENCY APPLIANCE COMBUSTION AIR AND VENT PIPING A. MATERIAL, SIZE, LENGTH, SLOPE, AND TERMINATIONS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONCENTRIC VENTS KITS SHALL BE PROVIDED BY APPLIANCE MANUFACTURER. NATURAL GAS PIPING A.PIPING SHALL BE SCHEDULE 40 ASTM A-120 BLACK STEEL. INSTALL PER IFGC AND NFPA 54. B.FITTINGS UP THROUGH 2" PIPE SHALL BE THREADED OR PRESS FIT WITH APPROVED FITTINGS AND TOOLS. FITTINGS 2-1/2" AND LARGER SHALL BE BUTT WELDED OR SOCKET WELDED OR PRESS FIT WITH APPROVED FITTINGS AND TOOLS. C.PROVIDE DIRT LEG, SHUT OFF COCK AND UNION OR STAINLESS FLEX CONNECTOR ON ALL APPLIANCE CONNECTIONS. D.INSPECT, TEST, AND PURGE ALL GAS PIPING IN ACCORDANCE WITH REQUIREMENTS OF IFGC. MEDICAL GAS PIPING ALL MEDICAL GAS PIPING AND EQUIPMENT SHALL CONFORM TO NFPA 99 CATEGORY 3 DENTAL GAS AND VACUUM SYSTEMS. HYDRONIC AND REFRIGERANT PIPING SYSTEMS A. HEATING WATER SUPPLY AND RETURN PIPING 1. TYPE L COPPER WITH SOLDER OR MECHANICALLY FORMED JOINTS OR SCHEDULE 40 STEEL WITH APPROVED MECHANICAL JOINING SYSTEM. B. REFRIGERATION PIPING 1. ACR GRADE PER ASTM B280 COPPER, CLEANED DEHYDRATED AND CAPPED AT THE FACTORY. C. VALVES AND SPECIALTIES BUTTERFLY VALVES: DUCTILE IRON BALL VALVES: BRONZE, FULL PORT CHECK VALVES: BRONZE STRAINERS: CAST IRON "Y" TYPE BALANCE VALVES: MANUAL- TACO ACCUFLO OR EQUAL, AUTO- FLOW DESIGN OR EQUAL WITH CARTRIDGE TO MATCH FLOW INDICATED. SPECIFICATIONS WARRANTY CONTRACTOR SHALL GUARANTEE THAT ALL WORK WILL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE . CONTRACTOR SHALL FURTHER GUARANTEE THAT HE WILL REPLACE OR REPAIR ALL DEFECTIVE EQUIPMENT AND INSTALLATIONS THAT BECOME DEFECTIVE DURING THE TERM OF THE WARRANTY. THIS DOES NOT INCLUDE EXCESSIVE ABUSE OR DAMAGE INFLICTED BY THE OWNER AND/OR OTHERS. FIRE PROTECTION BUILDING DOES NOT HAVE A FIRE SPRINKLER SYSTEM. LEGENDS VENTILATION CALCULATIONS PER 2018 IMC TABLE 403 Vbz=RpPz+RaAz: Rp=People Outdoor Air Rate (cfm), Pz=Zone Population (people). Ra=Area Ouotdoor Rate (cfm), Az=Zone Floor Area (sq ft) OFFICE Rp = 5 CFM/Person Pz = 5 PEOPLE/1000 S.F. = 4 Ra = 0.06 CFM/sf Az = 683 sf Vbz = (5)(4) + (0.06)(683) = 61 CFM CEILING SUPPLY/RETURN MULTIPLIER: 0.80 RTU-2 CONFERENCE Rp = 5 CFM/Person Pz = 50 PEOPLE/1000 S.F. = 19 Ra = 0.06 CFM/sf Az = 378 sf Vbz = (5)(19) + (0.06)(378) = 118 CFM CEILING SUPPLY/RETURN MULTIPLIER: 0.80 MP-1 DIFFUSER/REGISTER/GRILLE SCHEDULE S-1 PLAN CODE MFGR MODEL SHOEMAKER 700MA SIZE (INXIN)MATERIAL INTEGRAL DAMPER NOTES STEEL 1.2. NOTES: 1. COLOR SELECTED BY ARCHITECT. 2. SEE PLANS FOR NECK SIZES. TYPE CEILING DIFFUSER - LAY-IN NO24X24 S-2 1.3.SPIRAL DUCT DIFFUSER NO12X12 R-1 105P 1..24X24RETURN GRILLE E-1 915 1.2.EXHAUST GRILLE 16X16 TG-1 105P 1..24X24RETURN AIR TRANSFER GRILLE SHOEMAKER SHOEMAKER SHOEMAKER NO NO NO STEEL ALUMINUM STEEL STEEL RTU SCHEDULE PLAN CODE MFGR MODEL AIRFLOW (CFM)SERVICE GROSS COOLING (BTUH) FAN HP NOTES POWER V/HZ/PH NOTES: 1. DRY BULB ECONOMIZER 2. COIL GUARDS 3. 18" DOWNFLOW CURB 4. FILTER RACK 5. OUTSIDE AIR DAMPER CONFIGURATION INPUT HEATING (BTUH) ESP (IN W.C.) HEATING STAGES COOLING CIRCUITS EER/ SEER MCA/ MOP UNIT WEIGHT (LBS) FILTERSDRIVE OUTSIDE AIR (CFM/%) FUEL RTU-2 MAIN FLOOR 1943 208-230/60/11 1. 2. 3. 4. 5.TRANE DOWNFLOW 1150000.4 1 MERV 8DIRECTSEER 14 NG TOTAL OUTSIDE AIR FOR RTU-2: 223 CFM E. SEQUENCES OF OPERATION RTU-1 AND -2 - 7 DAY PROGRAMMABLE THERMOSTATS CONTROL HEATING AND COOLING SET POINTS IN EACH ZONE BY MODULATING ZONE DAMPERS VIA THE ZONE CONTROL PANEL. ZONE CONTROLLER DETERMINES HEAT/COOL OPERATION BASED ON ZONE DEMAND ALGORITHM. ADJUST OCCUPIED/UNOCCUPIED SCHEDULES ACCORDING TO BUSINESS HOURS AND OWNER PREFERENCES. RETURN AIR SMOKE DETECTOR SHUTS DOWN UNIT AND SENDS SIGNAL TO ANNUNCIATOR IN OCCUPIED SPACE UPON SMOKE DETECTION. EF-1 AND -2 - FAN TURNS ON WITH LIGHT SWITCH. BUILT IN OFF TIME DELAY SHUTS FAN OFF. EF-3 - SWITCH ON WALL ENABLES FAN. UH-1 - 24V THERMOSTAT ENABLES UNIT ON A CALL FOR HEAT. BB-1, BB-2 - LINE VOLTAGE THERMOSTAT ENABLES BOTH BB-1 AND BB-2 ON A CALL FOR HEAT. HVAC CONTROLS A. PROVIDE ALL THERMOSTATS, CONTROLLERS, SENSORS, ACTUATORS, AND INCIDENTAL EQUIPMENT FOR A COMPLETE AND OPERATIONAL SYSTEM. B. ZONE THERMOSTATS SHALL BE SHALL BE 24V 7 DAY PROGRAMMABLE WITH SPACE SET POINTS, AUTO SWITCH OVER FROM HEATING TO COOLING, OCCUPIED/UNOCCUPIED SCHEDULES, FAN ON/OFF/AUTO C. ZONE CONTROL PANEL SHALL BE iO HVAC CONTROLS 3 ZONE 2H/2C OR EQUAL AND BUILT IN STATIC PRESSURE CONTROL TO ELIMINATE BYPASS. ZONE DAMPERS SHALL BE 3 WIRE MD SERIES TO BE COMPATIBLE WITH CONTROL PANEL. PROVIDE PROGRAMMING AND TECHNICAL ASSISTANCE FOR ALL START UP AND COMMISSIONING ACTIVITIES. D. RTU'S FIRST STAGE COOLING SHALL BE VIA DRY BULB ECONOMIZER. EXHAUST FAN SCHEDULE EF-1 PLAN CODE MFGR MODEL AIRFLOW (CFM)SERVICE ESP (IN W.C.) FAN HP/WATTS NOTES POWER V/HZ/PH NOTES: 1. FAN SPEED CONTROLLER 2. INTERLOCK FAN WITH LIGHTS 3. SWITCH ON WALL. EF-2 EF-3 GARAGE EXHAUST 975 0.25 115/60/11/2 HP 1. 3.LOREN COOK 120C17DEC RTU-1 MAIN FLOOR 1943 60000 208-230/60/11 1. 2. 3. 4. 5.TRANE 4YCC4060A1115A DOWNFLOW 1150000.4 1 1 39.1/60 586 MERV 8DIRECTSEER 14291/15%NG TOILET 100 0.25 115/60/17.9 WATTS 1. 2.PANASONIC FV-0511VKS2 TOILET 100 0.25 115/60/17.9 WATTS 1. 2.PANASONIC FV-0511VKS2 RTU-1 OFFICE Rp = 5 CFM/Person Pz = 5 PEOPLE/1000 S.F. = 14 Ra = 0.06 CFM/sf Az = 2714 sf Vbz = (5)(14) + (0.06)(2714) = 233 CFM CEILING SUPPLY/RETURN MULTIPLIER: 0.80 TOTAL OUTSIDE AIR FOR RTU-1: 291 CFM GARAGE 0.75 CFM PER SQ FT = 1300 X 0.75 = 975 CFM UH-1 REZNOR UDZ NAT GAS 120/60/1 1 NOTESFUELPOWER V/HZ/PH NOTES 1.SEPARATED COMBUSTION. COMBUSTION AIR DUCTING REQUIRED. UNIT HEATER SCHEDULE PLAN CODE MFGR MODEL GARAGE SERVICE NOMINAL HEATING (BTUH) 75000 AMPS 4.3HORIZ. TYPE BB-1, BB-2 MARLEY 2500 208/60/1 1 NOTESPOWER V/HZ/PH NOTES 1.ONE LINE VOLTAGE THERMOSTAT CONTROLS BOTH BB-1 AND BB-2. THERMOSTAT BY EC. ELECTRIC BASEBOARD HEATER SCHEDULE PLAN CODE MFGR MODEL BONUS RM SERVICE NOMINAL HEATING (WATTS) 1500 AMPS 7.3BASEBOARD TYPELENGTH (IN) 96 4YCC4060A1115A 60000 1 39.1/60 586 SHOEMAKER 223/11% S-3 937 1.2.FIXED BLADE SUPPLY GRILLE 14X6SHOEMAKER YESSTEEL ARCHITECTS STUDIO CH JC - COPYRIGHT 2019 THESE DOCUMENTS, IN PART OR IN WHOLE, AND THE DESIGN THEY REPRESENT; ARE THE SOLE PROPERTY OF STUDIO 4 ARCHITECTS. THESE DOCUMENTS ARE INTENDED FOR THE PROJECT ON THE SITE INDICATED. ANY USE, REPRODUCTION, MODIFICATION, OR ADAPTATION WITHOUT THE EXPRESS WRITTEN CONSENT OF STUDIO 4 ARCHITECTS IS STRICTLY PROHIBITED. - - - 11-3-21 7-8-21 27 Shiloh Road Suite 8 Billings, MT 59106 ph: 406.656.1714 fx: 406.656.1715 web: studio4architects.com Bozeman, Montana PROJECT: C DATES: PRE: CRS: CHECKED BY: DRAWN BY: PROJECT NO. SHEET: REV: REV: CDS: SET:Stillwater Hospice13524PE S T A T E OF MONTANA PROF ESSI ONAL E N G IN EEREDRB E RGECD.YAJ