HomeMy WebLinkAboutM.1MechanicalPlant t t t t t t M-1 A.COORDINATE ALL WORK WITH OTHER TRADES. ADDITIONAL COMPENSATION OR TIME WILL NOT BE GRANTED DUE TO LACK OF COORDINATION BETWEEN TRADES B.ALL WORK SHALL BE COMPLETED IN A PROFESSIONAL AND WORKMANSHIP TYPE MANNER. ANY WORK THAT IS SUB STANDARD WILL NEED TO BE REDONE AT NO ADDITIONAL EXPENSE TO THE OWNER. C. PROVIDE MANUAL VOLUME DAMPER AT LOCATIONS INDICATED ON PLANS. VOLUME DAMPERS SHALL BE LEFT IN THE 100% OPEN POSITION UPON COMPLETION OF CONSTRUCTION. VOLUME DAMPERS SHALL BE ADJUSTED TO FINAL CFM BY T&B CONTRACTOR. D. NO BRANCH TAKE-OFFS ARE ALLOWED WITHIN FOUR DUCT DIAMETERS OF AN ELBOW, ZONE DAMPER OR TRANSITION E. MAXIMUM FLEX DUCT LENGTH SHALL NOT EXCEED 72". general notes HVAC PLAN N 13524PE S T A T E OF MONTANA PRO F E SSI ONAL E N G IN EEREDRB ERGECD.YAJUH-1 8"Ø RTU-1 ON ROOF SEE DETAIL RTU-2 ON ROOF SEE DETAIL EF-1 100 EF-2 100 E-1 975 10X10 DUCT UP TO EF-3 ON ROOF SEE DETAIL ZD1-1 ZD1-2 ZD2-1 ZD1-1 ZD2-2 ZD2-1 ZD2-3 BB-2 IN BONUS ROOM BB-1 IN BONUS ROOM ZONE CONTROL PANELS S-3 380 S-1 100 S-1 260 S-1 280S-1 280 S-1 180 S-1 280 S-1 180 12x816X1010x10 S-1 180 S-1 180 S-1 120 S-1 100 S-1 120 S-1 120 S-1 120 S-1 200 S-1 120 S-1 120 S-1 120 S-1 90 10X1014X10 S-1 10016X12 S-2 50 S-2 506"Ø6"ØS-1 100 10X10 10X10 8"Ø 6"Ø ZD1-3 ZD2-2 8"Ø8"Ø8"Ø8"Ø10"Ø20x16 16X14 R-1 120 R-1 120 R-1 120 R-1 120 R-1 595 R-1 120 R-1 100 6"ØS-2 50 10"Ø 8"Ø12X12 R-1 820 R-1 560 R-1 56012"Ø12"Ø14"Ø16X14 16X12R-1 360 R-1 280 TG-1 - 12"Ø 10"Ø12X12 8"Ø 10"Ø 6"Ø 8"Ø 8"Ø 8"Ø8"Ø8"Ø 8"Ø 6"Ø 6"Ø R-1 120 TG-1 -8"Ø 12"Ø 8"Ø8"Ø ZD1-3 ZD2-3 10"Ø 10"Ø 10"Ø 6"Ø 6"Ø 10x1016X14 UNIT HEATER VENT AND COMBUSTION AIR PER MANUFACTURER'S REQUIREMENTS ARCHITECTS STUDIO CH JC - COPYRIGHT 2019 THESE DOCUMENTS, IN PART OR IN WHOLE, AND THE DESIGN THEY REPRESENT; ARE THE SOLE PROPERTY OF STUDIO 4 ARCHITECTS. THESE DOCUMENTS ARE INTENDED FOR THE PROJECT ON THE SITE INDICATED. ANY USE, REPRODUCTION, MODIFICATION, OR ADAPTATION WITHOUT THE EXPRESS WRITTEN CONSENT OF STUDIO 4 ARCHITECTS IS STRICTLY PROHIBITED. - - - 11-3-21 7-8-21 27 Shiloh Road Suite 8 Billings, MT 59106 ph: 406.656.1714 fx: 406.656.1715 web: studio4architects.com Bozeman, Montana PROJECT: C DATES: PRE: CRS: CHECKED BY: DRAWN BY: PROJECT NO. SHEET: REV: REV: CDS: SET:Stillwater HospiceSET OUTSIDE AIR AS FOLLOWS: RTU-1: XXX CFM RTU-2: XXX CFM RTU DETAIL CURB PROVIDED WITH RTU SEE ARCHITECTURAL DETAILS FOR ROOFING AND FLASHING REQUIREMENTS GAS PIPE WITH SHUT OFF VALVE, DIRT LEG, AND UNION. SIZE PER PLANS.FLASHING ROOF SEAL ELECTRICAL DISCONNECT PROVIDED WITH RTU AND INSTALLED BY EC CONDENSATE DRAIN SEE DETAIL SUPPLY AIR DUCT ERICO OR EQUAL PIPE SUPPORTS HAIL GUARDS REQUIRED UNLESS SPECIFICALLY NOTED OTHERWISE POWER EXHAUST EXHAUST FAN DETAIL EXHAUST FAN PER PLANS AND SPECS GALVANIZED DUCT ALL THREAD SUPPORT FROM STUCTURE RUBBER ISOLATORS BACKDRAFT DAMPER EXHAUST FAN DETAIL DUCT SIZE PER PLANS ROOF 18" CONDENSATE DRAIN DETAIL H/2SLOPE TO DRAIN. VENT REQUIRED ONLY IF HORIZONTAL LENGTH EXCEEDS 2 FT SPILL TO ROOF OR DRAIN SCHED 40 PVC SIZE EQUAL TO DRAIN PAN OUTLET H=2.5" DRAIN PAN OUTLET. SECURE WITH UNION OR OTHER METHOD TO ALLOW DISCONNECTION AND DRAINING OF TRAP. VENT 6"Ø 6"Ø 16X10BROAN 646 OR EQUAL WALL CAP 16X12