ABBREVIATIONS AND SYMBOLS GENERAL NOTES
A. THE ABBREVIATIONS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL ABBREVIATIONS APPEAR ON THIS PROJECT.
B. THE SYMBOLS ON THIS SHEET COMPRISE A STANDARD LIST; NOT ALL SYMBOLS APPEAR ON THIS PROJECT.
C. ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE. ELECTRICAL CONTRACTOR
SHALL COORDINATE WITH OTHER CONTRACTORS, MAKING ADJUSTMENTS AS REQUIRED TO AVOID INTERFERENCE WITH EQUIPMENT SUCH
AS BASEBOARD FIN-TUBE, CABINET UNIT HEATERS, ETC. ARCHITECT/ENGINEER SHALL BE NOTIFIED OF ALL SUCH HEIGHT ADJUSTMENTS.
MOUNTING HEIGHTS INDICATED ON ARCHITECTURAL WALL ELEVATIONS OR AS NOTED SPECIFICALLY ON THE DRAWINGS OR IN THE
SPECIFICATIONS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.
ELECTRICAL ABBREVIATIONS LEGEND
A, AMP AMPERES
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
AF AMP FUSE
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
AS AMP SWITCH
ATS AUTOMATIC TRANSFER SWITCH
BAS BUILDING AUTOMATION SYSTEM
BKR BREAKER
BOF BOTTOM OF FIXTURE
C RACEWAY/CONDUIT
CB CIRCUIT BREAKER
CCT COLOR RENDERING TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
C.O. RACEWAY/CONDUIT ONLY, WITH PULL STRING
COD CENTER OF DEVICE
CNTRL CONTROL
CU COPPER
(D) EXISTING TO BE DEMOLISHED
DISC DISCONNECT
DIST DISTRIBUTION
DPDT DOUBLE POLE DOUBLE THROW
DWG DRAWING
EA EACH
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ELEC ELECTRIC
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
EX, EXIST EXISTING
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
FACP FIRE ALARM CONTROL PANEL
FD FUSED DISCONNECT
FLR FLOOR
FO FIBER OPTIC
FSD FIRE SMOKE DAMPER RELAY, CONTROLLED BY
ASSOCIATED SMOKE DETECTOR AND CIRCUITED
BACK TO FACP
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEC GROUNDED ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HVAC HEATING, VENTILATION & AIR CONDITIONING
HZ HERTZ
J-BOX JUNCTION BOX
KVA KILOVOLT-AMPERES
KW KILOWATTS
LCP LIGHTING CONTROL PANEL
LPW LUMENS PER WATT
LTG LIGHTING
LM LUMENS
LV LOW VOLTAGE
MAG MAGNETIC STARTER
MAN MANUAL
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MH METAL HALIDE
MIN MINIMUM
MSS MOTOR STARTER SWITCH WITH THERMAL OVERLOADS
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NFD NON-FUSED DISCONNECT
NIC NOT IN CONTRACT
NO NORMALLY OPEN
# NUMBER
OAE OR APPROVED EQUAL
OC ON CENTER
OCPD OVERCURRENT PROTECTIVE DEVICE
OH OVERHEAD
P POLE
PB PUSHBUTTON
PC PLUMBING CONTRACTOR
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
(R) EXISTING TO REMAIN
RCPT RECEPTACLE
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RVNR REDUCED VOLTAGE NON-REVERSING
RVR REDUCED VOLTAGE REVERSING
SP SINGLE POLE TOGGLE SWITCH
SPD SURGE PROTECTIVE DEVICE (TVSS)
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SSPB START-STOP PUSHBUTTON
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TELEPHONE BOARD
TC TIME CLOCK
TD TIME DELAY
TEL TELEPHONE
TR TAMPER RESISTANT
TSP TWISTED SHIELDED PAIR
TTB TELEPHONE TERMINAL BOARD
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHERPROOF
W/O WITHOUT
XFMR TRANSFORMER
Y WYE-CONNECTED
Δ DELTA-CONNECTED
ø PHASE
ELECTRICAL LIGHTING FIXTURE LEGEND
RECESSED LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
EXIT SIGN - WALL MOUNT, CEILING MOUNT. ARROW
INDICATES DIRECTION OF TRAVEL, SHADING
INDICATES LIGHTED FACE.
RECESSED EMERGENCY LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
SURFACE LED FIXTURE - "a" & "b" DESIGNATES
SWITCH
SURFACE EMERGENCY LED FIXTURE - "a" & "b"
DESIGNATES SWITCH
SURFACE WALL MOUNT LED FIXTURE
LED STRIP OR INDUSTRIAL, SURFACE OR CHAIN
HUNG
EMERGENCY LED STRIP OR INDUSTRIAL, SURFACE
OR CHAIN HUNG
POLE MOUNTED FIXTURE
LIGHTED BOLLARD
PENDANT FIXTURE; HIGH BAY, LOW BAY,
DECORATIVE
DUAL HEAD EMERGENCY EGRESS BATTERY PACK,
WALL MOUNT OR CEILING MOUNT
WALL MOUNTED SCONCE
SURFACE DOWNLIGHT
SURFACE EMERGENCY DOWNLIGHT
RECESSED CAN DOWNLIGHT
RECESSED CAN EMERGENCY DOWNLIGHT
RECESSED CAN WALL WASHER
TRACK LIGHTING. SEE FIXTURE SCHEDULE AND
LIGHTING PLANS.
COMBINATION EXIT SIGN/ EGRESS LIGHTING UNIT -
WALL MOUNT, CEILING MOUNT. ARROW INDICATES
DIRECTION OF TRAVEL, SHADING INDICATES LIGHTED
FACE.
LIGHTING CONTROL LEGEND
OCCUPANCY SENSOR - DUAL TECHNOLOGY
CEILING MOUNT: WATTSTOPPER DT-300, OR EQUAL
WALL MOUNT: WATTSTOPPER DT-200, OR EQUAL
WALL MOUNTED SHALL BE AT +96", UNO
PROVIDE WITH BZ-50 POWER PACKS AS NEEDED.
TOGGLE SWITCH (MOUNT AT +48", UNO)
"X" INDICATES TYPE:
BLANK -SINGLE POLE
3 - INDICATES THREE-WAY
4 - INDICATES FOUR-WAY
D - INDICATES DIMMER SWITCH
PHILIPS SUNRISE - ON/OFF
K - INDICATES KEYED SWITCH
T - INDICATES TIMER
P - INDICATES PILOT LIGHT
OS - INDICATES WALL SWITCH OCC SENSOR
WATTSTOPPER DW100 (SINGLE OR DUAL
DW-200 SWITCH)
OSD - INDICATES WALL SWITCH OCC SENSOR
WITH 0-10V DIMMING - WATTSTOPPER PW-311
a - INDICATES SINGLE POLE LIGHTING SWITCH
ZONE FOR ZONE a
b - INDICATES SINGLE POLE LIGHTING SWITCH
ZONE FOR ZONE b
ab - INDICATES LIGHTING SWITCHES WITH
MULTIPLE ZONES
PHOTOCELL - EXTERIOR
STANDARD LIGHTING CONTROLS:
SWITCHES AND LINE VOLTAGE DIMMERS
ELECTRICAL ONE-LINE LEGEND
MOTOR
CT AND CUSTOMER POWER METER
UTILITY ELECTRIC METER AND BASE (BASE BY
CUSTOMER)
SURGE PROTECTION DEVICE
LIGHTNING ARRESTER, TYPE 1 SPD, MOUNTED ON
EXTERIOR OF MAIN SWITCHGEAR (SQUARE D NO.
SDSA3650, OAE)
STRESS RELIEF CONE
POWER FACTOR CORRECTION CAPACITOR
EQUIPMENT TOGGLE DISCONNECT SWITCH
"X" INDICATES TYPE:
F - FUSTAT
M - MOTOR STARTER SWITCH W/ THERMAL
OVERLOADS
CONTACTOR NORMALLY OPEN, NORMALLY CLOSED
TRANSFORMER, 3-PH, 3-WIRE DELTA CONNECTION
TRANSFORMER, 3-PH, 4-WIRE GROUNDED WYE
CONNECTION
AUTOMATIC TRANSFER SWITCH
VARIABLE FREQUENCY DRIVE
FIXED MOUNT LV BREAKER
FUSED SWITCH ("XXAS/XXAF" - SW AND FUSE AMP
RATING)
GENERATOR
WALL MOUNTED BREAKER
THERMAL OVERLOAD ELEMENT
DISCONNECT SWITCH ("XXAS" = SWITCH AMP RATING)
FUSED DISCONNECT SWITCH ("XXAS/XXAF" = SW AND
FUSE AMP RATING)
COMBINATION MOTOR STARTER (STR SIZE, TYP, AS,
AF, SEE MEP COORDINATION SCHEDULE)
SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE,
PHASE, NUMBER OF WIRES WHEN INDICATED
ELECTRICAL POWER LEGEND
PANEL AND CIRCUIT DESIGNATION ARE SHOWN NEXT
TO EACH DEVICE (PANEL NAME - CIRCUIT NUMBER).
BRANCH CIRCUIT WIRE SIZE IS #12, UNO. A SINGLE
INSULATED GREEN GROUND CONDUCTOR SHALL BE
PROVIDED WITH EACH HOME RUN. PROVIDE A
SEPARATE NEUTRAL FOR EACH CIRCUIT. HOME RUNS
SHALL HAVE NO MORE THAN THREE CIRCUITS. LINE
VOLTAGE AND LOW VOLTAGE WIRING IS NOT SHOWN
ON PLANS. FOR EQUIPMENT CIRCUITING, SEE MEP
COORDINATION SCHEDULE.
"X" INDICATES TYPE:
GFI - GROUND FAULT INTERRUPTER
WP - WEATHERPROOF WHILE-IN-USE COVER
U - PROVIDE WITH (2) USB PORTS
TR - TAMPER RESISTANT
PANELBOARD OR LOAD CENTER
JUNCTION BOX
SIMPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
DUPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
QUADRUPLEX RECEPTACLE - CEILING MOUNT, WALL
MOUNT (+18", UNO)
SPECIAL PURPOSE RECEPTACLE (MOUNT AT
+18", UNO)
"X" INDICATES TYPE:
A - NEMA 5-20R, #12 CU; B -NEMA 5-30R, #10 CU;
C -NEMA 5-50R, #8 CU; D - NEMA 6-20R, #12 CU;
E - NEMA 6-30R, #10 CU; F -NEMA 6-50R, #8 CU;
G -NEMA 14-20R, #12 CU; H - NEMA 14-30R, #10 CU;
I - NEMA 14-50R, #8 CU*
* +4" AFF FOR RANGE
SURFACE MOUNTED RACEWAY
RACEWAY CONCEALED IN WALL, FLOOR, OR CEILING
IN FINISHED SPACES, EXPOSED IN UNFINISHED
SPACES
RACEWAY BELOW FLOOR OR BELOW GRADE
RACEWAY STUB-OUT WITH CAPPED END
RACEWAY STUB-OUT WITH BRUSHED END
GROUNDING BUS
PUSHBUTTON (MOUNT AT +48", UNO)
"X" INDICATES TYPE:
EPO -EMERGENCY POWER OFF
ADA -HANDICAPPED ACCESSIBLE DOOR
(DEVICE BY OTHERS)
ODO - OVERHEAD DOOR OPERATOR
(DEVICE BY OTHERS)
ABOVE COUNTER RECEPTACLE - MOUNT AT
+4" ABOVE BACKSPLASH
ELECTRICAL PROJECT GENERAL NOTES
A. PRIOR TO BID CONTRACTOR SHALL VISIT THE SITE. NOT ALL WORK REQUIRED TO COMPLETE THE PROJECT IS SHOWN ON THE DRAWINGS.
THE CONTRACTOR SHALL BECOME THOROUGHLY FAMILIAR WITH ALL THE WORK REQUIRED TO COMPLETE THE PROJECT IN ADDITION TO
THE LOCAL CONDITIONS AND INCLUDE SAID WORK IN THE BID.
B. MONTANA STATE UNIVERSITY OWNS THE PRIMARY ELECTRICAL MEDIUM VOLTAGE DISTRIBUTION SYSTEM ON PROPERTY, RATED AT
7.2/12.47KV. CONTRACTOR SHALL PROVIDE ALL REQUIRED MEDIUM VOLTAGE WORK SHOWN ON PLANS AS PART OF PROJECT SCOPE. IT IS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ALL SCHEDULES ARE MET.
C. GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION SHALL BE IN ACCORDANCE WITH NECA 1, "STANDARD PRACTICES FOR GOOD
WORKMANSHIP IN ELECTRICAL CONTRACTING." THIS PUBLICATION IS AVAILABLE FROM NECA BY TELEPHONE AT 301-657-3110 OR ON-LINE AT
WWW.NECANET.ORG.
D. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE WITH MECHANICAL FOR PLENUM SPACES AND PROVIDE PLENUM RATED CABLES
WHERE REQUIRED FOR LIGHTING CONTROL, DATA, FIRE ALARM AND ALL OTHER L.V. SYSTEMS NOT INSTALLED IN CONDUIT. VERIFY CONDUIT
REQUIREMENTS ON DRAWINGS AND SPECIFICATIONS.
E. FIRE-RESISTANCE: PROVIDE A MINIMUM HORIZONTAL DISTANCE OF 24" BETWEEN OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE-
RESISTANCE RATED WALLS. WHERE THIS IS NOT POSSIBLE INSTALL UL LISTED PUTTY PADS ON ALL OUTLET BOXES NOT MEETING THE 24"
SEPARATION. PROVIDE A UL LISTED THROUGH -PENETRATION FIRESTOP FOR PENETRATIONS OF FIRE-RESISTANCE RATED ASSEMBLIES.
F. CONDUCTORS ARE SIZED PER THE 75 DEGREE C RATING COLUMN OF NEC TABLE 310.16. IF THE TERMINAL USED FOR A TERMINATION OF A
PARTICULAR CONDUCTOR IS NOT MARKED, OR THE TERMINAL IS MARKED FOR 60 DEGREE C CONDUCTORS, IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO EITHER ADJUST THE AMPACITY OF THE CONDUCTOR TO MATCH THE 60 DEGREE COLUMN OF TABLE 310.16, OR
REPLACE THE TERMINAL WITH ONE RATED FOR AT LEAST 75 DEGREES C.
G. BASED ON ACTUAL HOMERUN LENGTHS REQUIRED IN THE FIELD, THE CONTRACTOR SHALL CALCULATE AND INCREASE THE WIRE SIZES AS
REQUIRED TO LIMIT BRANCH CIRCUIT VOLTAGE DROP TO 3%. FOR 20A BRANCH CIRCUITS THE MINIMUM CONDUCTOR SIZES SHALL BE AS
FOLLOWS: #10 AWG CU FOR RUNS BETWEEN 100 AND 200 LINEAR FEET, #8 AWG CU FOR RUNS BETWEEN 200 AND 325 LINEAR FEET, AND AS
CALCULATED BY THE CONTRACTOR FOR CIRCUITS EXTENDING BEYOND 325 LINEAR FEET. IN ALL CASES WHERE WIRE SIZES INCREASE, THE
CONTRACTOR SHALL PROVIDE LARGER CONDUITS AS REQUIRED.
H. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH 120V BRANCH CIRCUIT.
REV. DESCRIPTION DATE
REVIEWED BY:
DRAWN BY:
SHEET
DATE
SHEET TITLEMONTANASTATE UNIVERSITYMSU-CPDC
MONTANA STATE UNIVERSITY
BOZEMAN, MONTANA
PHONE: 406.994.5413
FAX: 406.994.5665
MMI#0747.075AES BART FARMCITY WATER SERVICE95% CONSTRUCTION DOCUMENTSRPM
MJS
ELECTRICAL LEGENDS
E0.1
11-11-2021
PPA#20-0116
02/01/22
21450 MSU AES
Bart Farm Water
Service Bldg.
MOD