HomeMy WebLinkAbout5.j_ FireProtectionPlan_04162021P A R K V I E W C R O S S I N G S U B D I V I S I O N P R E L I M I N A R Y P L A T A P P L I C A T I O N A P R I L 2 0 2 1 F I R E P R O T E C T I O N P L A N Fire Protection Plan The Parkview Crossing development group is working with the City of Bozeman Fire Department to provide fire flows within the proposed water distribution system extension. No changes are proposed from that which has already been completed in the previous surrounding subdivisions. Street Hydrants conforming to IFC spacing requirements shall provide flow minimums of at least 1,000 gallons per minute (gpm) at 20 psi for two hours for all residential structures equal to or less than 3,600 sq. ft. Note: If a residential structure exceeds 3,600 sq. ft., the minimum flow and duration shall meet the requirements set forth in Appendix B of the IFC, or as adopted by the State of Montana, or utilize an approved automatic sprinkler system, unless an alternate method for fire suppression is approved by the Fire Authority having jurisdiction. All hydrant spacing, hydrant type and location is based on the City of Bozeman Design Standards, as approved by the City of Bozeman Fire Department. The City of Bozeman water system is capable of providing greater than 1,500 gpm hydrant flows within the project area.