Fire Protection Plan
The Parkview Crossing development group is working with the City of Bozeman Fire
Department to provide fire flows within the proposed water distribution system
extension. No changes are proposed from that which has already been completed in
the previous surrounding subdivisions.
Street Hydrants conforming to IFC spacing requirements shall provide flow minimums
of at least 1,000 gallons per minute (gpm) at 20 psi for two hours for all residential
structures equal to or less than 3,600 sq. ft.
Note: If a residential structure exceeds 3,600 sq. ft., the minimum flow and duration
shall meet the requirements set forth in Appendix B of the IFC, or as adopted by the
State of Montana, or utilize an approved automatic sprinkler system, unless an
alternate method for fire suppression is approved by the Fire Authority having
jurisdiction.
All hydrant spacing, hydrant type and location is based on the City of Bozeman Design
Standards, as approved by the City of Bozeman Fire Department.
The City of Bozeman water system is capable of providing greater than 1,500 gpm
hydrant flows within the project area.