HomeMy WebLinkAbout5_HouseBracedWallLines_08-20-21House 2nd Braced Wall Lines
c
Date:mobile #:phone #:Project No.Drawn by:Date:Scale:GENERAL CONTRACTOR:Revised by:
Drafting & Design, Inc.B19-0109-1-3McLay Project - SummerHome330 NO. ROUSEBOZEMAN, MONTANACHRIS MCLAY608-774-2678Tract 2D. Johnston 28 Jan 19
D. Johnston 04 Feb 19
These drawings are licensed for
ONE USE ONLY.
D. Johnston 16 Jan 19
D. Johnston 25 Jan 19
D. Johnston 08 Mar 19IMPACTDRAFTING & DESIGN, incwww.impactdrafting.com2021 Brentwood Professional Center1195 Stoneridge Dr., Suite 3DBozeman, MT. 59718406-522-5382All rights reserved. All designs, drawings, ideas, and
written material contained or described herein are
the sole property of IMPACT Drafting & Design Inc.
and as such may not be altered, duplicated, used or
disclosed without written consent from IMPACT
Drafting & Design Inc.scale is correct ifprinted on D-Size paperby IMPACT DraftingNote: IMPACT Drafting & Design Inc. is not responsible for engineering orconstruction. Individual contractors are responsible for meeting codes.IMPACT
D. Johnston 03 Apr 19
D. Johnston 16 Sep 20CONTACT/OWNER5 133/16" = 1'Braced Wall Line
scale: 3/16" = 1'
PRODUCT TYP.
BASE PLATE
MANUFACTURER
SIMPSON USP
AB66 PB66
HANGER ITT THO
SIMPSON TO USP CONNECTOR CONVERSION
JB28 JL28
STRAP MSTA 24 MSTA24
MSTA 48 MSTA 49
LTP4 MP4F
HURRICANE TIES A35 MPA1
H1 RT15
H2.5 RT7
House 1st Braced Wall Lines
scale: 3/16" = 1'
TABLE R602.10.4 - BRACING METHODS
MATERIAL MIN.
THICKNESS
FASTENERS
WSP
Wood Structural
Panel (R604)
3/8″Ext. sheathing per Table
R602.3(3). Interior
sheathing per Table
R602.3(1) or R602.3(2)
6″ edges 12″
field
Varies by
fastener
BV-WSP
Wood Structural
Panels w. Stone
or Masonry
Veneer
(R602.10.6.5)
7/16″8d common
(2 1/2″ × 0.131)
nails
4″ at panel edges
12″at
intermediate
supports 4″at
braced wall panel
end posts
GB
Gypsum Board
*for intermittent
bracing my not mix
within BWL
1/2″Nails or screws per Table
R602.3(1) for exterior
locations. Nails or screws
per Table R702.3.5 for
interior locations
All braced wall
panel locations:
7″ edges (inc.
top and bottom
plates) 7″ field
ABW
Alternate
Braced Wall
3/8″See Section
R602.10.6.1
See
Section
R602.10.6.1
PFH
Portal Frame w.
Hold-downs
3/8″See Section
R602.10.6.2
See Section
R602.10.6.2
PFG
Portal Frame at
Garage
7/16″See Section
R602.10.6.3
See Section
R602.10.6.3
Braced Wall Lines (BWL) and Braced Wall Panels (BWP)
Bracing is required in accordance with R602.10. All exterior and interior
walls parallel to a Braced Wall Line shall be offset not more than 4 feet and
Braced Wall Panels shall be full-height sections with no vertical or
horizontal offsets (R602.10.2).
BWP shall begin within 10 feet from each end of a braced wall line.
Distance between Braced Wall Panels in a Braced Wall Line shall be no
greater than 20 feet. (R602.10.2.2).
Per R602.10.2.3 a BWL with a length of 16' or less shall have a minimum
of two braced wall panels of any length or one BWP equal to or greater
than 48”. BWL greater than 16' shall have a minimum of two BWP.
The end of a BWL shall be the intersection with a perpendicular BWL
(R602.10.1.1). For additional spacing information see Tables R602.10.3
CONTINUOUS SHEATHING METHOD (R602.10.4.2) require structural panel
sheathing to be used on ALL sheathable surfaces ON ONE SIDE of a Braced
Wall Line, including ares above and below openings and gable end walls
(R602.10.7). See Figure R602.10.7 for the five acceptable End Conditions.
There are 16 Bracing Methods in addition to Continuous Sheathing allowed
(R602.10.4); the most common ones are listed below.
SPACING
MIN. 3" X 11-1/4" NET HEADER
STEEL HEADER PROHIBITED
12' MAX TOTAL WALL HEIGHT10' MAX HEIGHTPONYWALL
HEIGHT
EXTENT OF HEADER WITH DOUBLE PORTAL FRAMES (TWO BRACED WALL PANELS)
EXTENT OF HEADER WITH SINGLE PORTAL FRAME
(ONE BRACED WALL PANEL)
2' - 18' FINISHED WIDTH OF OPENING
FOR SINGLE OR DOUBLE PORTAL
FASTEN SHEATHING TO HEADER WITH 8D
COMMON OR GALVANIZED BOX NAIL IN 3" GRID
PATTERN AS SHOWN
HEADER TO JACK-STUD STRAP PER TABLE
R602 10.6.4 ON BOTH SIDES OF OPENINGOPPOSITE SIDE OF SHEATHING
MIN DOUBLE 2X4 FRAMING COVERED WITH MIN.
3/8" THICK WOOD STRUCTURAL PANEL SHEATHING
WITH 8D COMMON OR GALVANIZED BOX NAILS AT
3" O.C. IN ALL FRAMING (STUDS, BLOCKING, AND
SILLS) TYP.
MIN. LENGTH OF PANEL PER TABLE R602.10.5
MIN. (2)4200 LB STRAP - TYPE HOLD - DOWNS
(EMBEDDED INTO CONCRETE AND NAILED INTO
FRAMING)
MIN. REINFORCING OF FOUNDATION, ONE #4 BAR
TOP AND BOTTOM OF FOOTING LAP BARS 15"
MINIM
MIN. FOOTING SIZE UNDER OPENING IS 12" X 12" A TURNED-
DOWN SLAB SHALL BE PERMITTED AT DOOR OPENINGS.
MIN. (1) 5/8" DIAMETER ANCHOR BOLT INSTALLED
PER R403.1.6 - WITH 2" x 2" x 3/16" PLATE WASHER
TENSION STRAP PER
TABLE R602 10.6.4 (ONOPPOSITE SIDE OF
SHEATHING)
IF NEEDED, PANEL
SPLICE EDGES SHALL
OCCUR OVER AND BE
NAILED TO COMMON
BLOCKING WITHIN
MIDDLE 24" OF WALL
MID. HEIGHT. ONEROW OF 3" O.C.NAILING IS REQUIREDIN EACH PANEL EDGE.
TYPICAL PORTALFRAME CONSTRUCTION
MIN. DOUBLE 2x4 POST
(KING AND JACK STUD)NUMBER OF JACK STUDS
PER TABLES R502 5(1) &
(2)
MIN. 1000 LB HOLD-DOWN
DEVICE (EMBEDDED INTO
CONCRETE AND NAILED
INTO FRAMING)
FASTEN TOP
PLATE TO
HEADER WITH
TWO ROWS OF
160 SINKER
NAILS AT 3"
O.C. TYP.
MIN 3/8"
WOODSTRUCTURALPANELSHEATHING
FRONT ELEVATION
SECTION
METHOD PFH - PORTAL FRAME WITH STRAP- STYLE HOLD-DOWNS
(c) 2018 iddi - trj
*Note: When exterior wall shear wall lines or Braced Wall Panels are
not in one plane vertically from the foundation to uppermost story,
the following conditions must be met:
1.Floor joists must be 16" o.c. or closer
2.Ratio of back span of a cantilever is no greater than 2:1
3.Floor joists at the ends of the Braced Wall Panels are doubled
4.A continuous rim joist is used
5.Gravity loads are uniform.
(IRC 301.2.2.2.5)
FIGURE R602.10.8.2(2)
BRACED WALL PANEL CONNECTION OPTION TO PERPENDICULAR RAFTERS OR
ROOF TRUSSES
MIN. 24 INCH WOOD
STRUCTURAL PANEL
SHEATHING OR 32 INCH
STRUCTURAL FIBERBOARD
CORNER RETURN
160 NAIL (3-1/2" x0.131")
AT 12 INCH O.C.
CONTINUOUS WOOD
STRUCTURAL PANEL
OR WALL LINE
SEE TABLE R602.3(1) FOR
FASTENING
OPTIONAL NONSTRUCTURAL
FILLER PANEL
GYPSUM WALLBOARD AND
INSTALLED IN ACCORDANCE
WITH CHAPTER 7
ORIENTATION OF STUDS MAY VARY
SEE FIGURE R602.3(2)
SEE TABLE R602.3(1) FOR
FASTENING
2 METHOD PFH (PORTAL FRAME WITH HOLDDOWNS)
FIGURE R602.10.6.2 - 2018 IRC
SEE TABLE R602.3(1) FOR
FASTENING
ORIENTATION OF STUDS MAY VARY
SEE FIGURE R602.3(2)
160 NAIL (3-1/2" x 0.131")
AT 12 INCH O.C.
GYPSUM WALLBOARD AND
INSTALLED IN ACCORDANCE
WITH CHAPTER 7
MIN. 24 INCH WOODSTRUCTURAL PANELSHEATHING OR 32 INCHSTRUCTURAL FIBERBOARD
CORNER RETURN
CONTINUOUS WOOD STRUCTURALPANEL OR STRUCTURAL FIBER
BOARD WALL LINE
4 TYP.(a) OUTSIDE CORNER DETAIL 5 TYP.(b) INSIDE CORNER DETAIL
160 NAIL (3 1/2" x0.131")
2 ROWS AT 24 INCH O.C.
GYPSUM WALLBOARD AS
REQUIRED AND INSTALLED IN
ACCORDANCE WITH CHAPTER 7
OPTIONAL BLOCKING FOR
GYPSUM WALL BOARD
SEE TABLE R602.3(1)
FOR FASTENING
MIN. 24 INCH WOOD
STRUCTURAL PANEL OR 32 INCH
STRUCTURAL FIBERBOARD
SHEATHING (BOTH EDGES AT
CORNER)
SEE TABLE R602.3(1) FOR
FASTENING
OPTIONAL NONSTRUCTURALFILLER PANEL
FASTENERS ON BOTH STUDS
AT EACH PANEL EDGE
CONTINUOUS WOOD STRUCTURAL
PANEL OR STRUCTURAL FIBER
BOARD WALL LINE
CONTINUOUS RIM
OR END JOIST
8d @ 6" O.C. ALONG
BRACED WALL PANEL
BRACED WALL PANEL
3-16d @16" O.C. ALONG
BRACED WALL PANEL
CONTINUOUS RIM OR
BAND JOIST
PERPENDICULAR FRAMING
PERPENDICULAR FRAMING
8d @ 6" O.C. ALONG
BRACED WALL PANEL
BRACED WALL PANEL
3-16d @16" O.C. ALONG
BRACED WALL PANEL
FULL HEIGHT BLOCKING CONTINUOUS
ALONG LENGTH OF BRACED WALL
PANEL
FULL HEIGHT BLOCKING CONTINUOUS
ALONG LENGTH OF BRACED WALL
PANEL
CONTINUOUS RIM
OR END JOIST
8d @ 6" O.C. ALONG
BRACED WALL PANEL
BRACED WALL PANEL
FIGURE R602.10.6(1)
BRACED WALL PANEL WHEN PERPENDICULAR TO FLOOR/CEILING FRAMING
3-16d @16" O.C. ALONG
BRACED WALL PANEL
CONTINUOUS RIM OR
BAND JOIST
8d @ 6" O.C. ALONG
BRACED WALL PANEL
ADDITIONAL FRAMING MEMBER
DIRECTLY ABOVE BRACED WALL
PANEL
BRACED WALL PANEL
3-16d @16" O.C. ALONG
BRACED WALL PANEL
ADDITIONAL FRAMING MEMBER
DIRECTLY BELOW BRACED WALLPANEL
FULL HEIGHT BLOCKING @ 16" O.C.
ALONG BRACED WALL PANEL
FULL HEIGHT BLOCKING @ 16" O.C.
ALONG BRACED WALL PANEL
3-16d @16" O.C. AT EACH
BLOCKING MEMBER
BRACED WALL PANEL
TOE NAIL 3-8d NAILS
AT EACH BLOCKING
MEMBER
3-16d NAILS EACH SIDE
FIGURE R602.10.6(2)
BRACED WALL PANEL WHEN PARALLEL TO FLOOR/CEILING FRAMING
= BRACED WALL PANEL= Hold-down per R602.10.6.4&5
Label indicates side of bracing. Double sides will have double labels
Interior Braced Wall Panels to be connected to solid framing (blocking or
double joists as required) w. (3) 16d nails 16" O.C.