HomeMy WebLinkAbout2021-03-30_E5-2 - EXTERIOR LUMINAIRE SCHEDULE & DETAILSBase Cap
Rotation lock set screws
180 degress apart, quantity
two (2).
Dual O-Ring Seal. Make sure
sealing surface is kept clean.
Grease o-rings with silicone
grease. To allow for easy rotation
and extended life of o-ring.Stability Plate Attachment Method
Driver Slope surface to allow for run off
Pea gravel back fill below and
around sides of direct burial
junction box for drainage.
Recommended re-enterable potting
seal material - 3M High Gel 4442
Recessed Direct Burial
Junction Box
Stability Plate Conduit plug. Recommed
using gray duct sealing
compund to completely
seal wires inside conduit
and conduit entries
P
CKT PER LTG PLAN
CKT PER LTG PLAN
ZONE 1
EMERGENCY LIGHTING
EM
INVERTER
OUTDOOR
NOTE:
PROGRAM LIGHTING CONTACT FOR ALL EXTERIOR
LUMINAIRES TO SWITCH ON/OFF VIA PHOTOCELL AND
TIMECLOCK. COORDINATE TIMECLOCK SCHDULE WITH
OWNER.
LIGHTING CONTROL PANEL
WITH PHOTOCELL AND
INTEGRAL SYSTEM CLOCK
WATTSTOPPER LC8-120/277V, OAE
ZONE 2
ZONE 3
ZONE 4
BASE SIZE
SEE SCHED.2'-6"HEIGHT AFGSEE SCHED.DEPTH *** - SEE SCHED.
CONCRETE BASE SCHEDULE *****
POLE HT.BASE
SIZE
VERT.
REINF.
HORIZ.
REINF.
DEPTH
***
HEIGHT
AFG
0' TO 14'
15" SQ.(4) #6 *#3@10"O.C. 4'-0" 0'-6"
18" RND.(6) #5 **** #3@10"O.C. 4'-0" 0'-6"
14' TO 30'
20" SQ. (4) #7 * #3@12"O.C. 7'-0" 2'-6"
24" RND. (6) #6 **** #3@12" O.C. 7'-0" 2'-6"
35' TO 40'24" RND. (6) #6**** #3@12" O.C. 8'-6" 2'-6"
ANCHOR BOLTS
FROM POLE MANF.
NOTE:
HORIZ. REINF.
SEE SCHEDULE
HANDHOLE - 4" X 6" (NOMINAL)
THWN CONDUCTOR AS SHOWN ON PLANS
PROVIDE 1' OF COILED SLACK ON
CONDUCTOR FEED THRU
PROJECT ANCHOR BOLTS 3" MIN. ABOVE TOP
OF BASE. PROVIDE DOUBLE NUTS FOR
LEVELING UNIT (ONE ABOVE AND ONE BELOW
BASE FLANGE). PROVIDE NON-SHRINK GROUT
IN VOID BETWEEN BASE FLANGE AND TOP OF
CONCRETE, LEAVING DRAIN HOLE. HAND FINISH.
CONNECT GROUND TO POLE
BASE W/ BOUNDRY #GB4C
PROVIDE FUSE(S) IN CKT. TO
BALLAST. FUSE(S) SHALL BE
BUSS TYP. BBS. FUSE
HOLDERS SHALL BE BUSS
"TRON" HEB WATERPROOF.
SIZE OF FUSE SHALL BE AS
REQUIRED BY LUMINAIRE
MANUFACTURER.
BASE COVER
BUSH CONDUITS
REINFORCED CONC.
BASE BY ELECTRICAL
CONTRACTOR
1" CHAMFER
SEE SITE PLAN
FOR CONDUIT SIZE
FINISH GRADE. COMPACT SOIL IN 6" MAX
LIFTS IN EXCAVATED AREA AROUND POLE
FOUNDATION
VERT. REINF.
SEE SCHEDULE
NOTE:
• CONTRACTOR SHALL GRIND EXPOSED CONCRETE SMOOTH. EXPOSED CONCRETE SHALL HAVE NO
SONOTUBE MARKINGS.
• CONTRACTOR SHALL PREP EXPOSED BASE FOR EUCLID VERTICOAT. APPLY PER MANUFACTURER
INSTRUCTIONS TO PROVIDE A FINSIHED APPEARANCE
* PROVIDE VERTICAL BARS AT EACH CORNER OF SQ. PIER.
** PROVIDE SPACING OF S/3 AT TOP 1'-0" OF PIER.
*** DEPTH BELOW FINISHED GRADE.
**** SPACE VERTICAL BARS EVENLY AROUND PERIMETER.
*****PROVIDE REINF. CLEARANCE PER ACI 318.
40' TO 55' 36" RND. (8) #6**** #3@12" O.C. 9'-0" 2'-6"20' - 0"E2
REVISIONS
NOTES
REVISIONS
NOTES
STAMP + SIGNATURE
KEY PLAN
Building A
Building B
SP1
03/30/2021
Energy 1
2042 Stadium Dr Suite 2
Bozeman, MT 59715
+1 406 587 2917
As indicated EXTERIOR LUMINAIRE
SCHEDULE & DETAILS E5.2HAVENPond Row
Lot 3A, Van Horn Subdivision
Bozeman, MT 59715
E5.2 SCALE: 12" = 1'-0"
EXTERIOR LIGHTING CONTROL DIAGRAM - LCP WITH INVERTER1
E5.2 SCALE: 1/2" = 1'-0"
LIGHTED BOLLARD BASE DETAIL3
E5.2 SCALE: 1/8" = 1'-0"
POLE LIGHT BASE DETAIL4
1. ALL EXTERIOR FIXTURES ARE REQUIRED TO BE FULL CUTOFF. B.U.G - U LEVEL TO BE 0.
2. ALL EXTERIOR FIXTURES TO BE 0-10V DIMMABLE AND HAVE A COLOR TEMP. OF 4000K....
EXTERIOR LUMINAIRE SCHEDULE
Type Mark Wattage DESCRIPTION MANUFACTURER & MODEL
E1 9 W EXTERIOR 2FT TALL PATHWAY LIGHT COOPER-303-P1-LEDB1-4000K-UNV-T2-DIM10-BZ-24-EDGE
E2 54 W EXTERIOR POLE MOUNT AREA LIGHT COOPER - PRV-PA1-A-740-U-T3--BK-HSS
E2H 54 W SAME AS E2 WITH HOUSE SIDE SHEILD LITHONIA-DSX1 LED -P1-40K-T3M-MVOLT-SPA-DMG-HS-DDBXD
E4 8 W EXTERIOR LANDSCAPE ACCENT LIGHT COOPER-203-FL-8LED-40K-45-12-KZ-LVR
EM1 EMERGENCY BATTERY INVERTER SURE-LITE - INV-600-SD-CA
EX1 25 W EXTERIOR RECESSED DOWN LIGHT COOPER-LDSQ4B-30-D010
EX1E 25 W SAME AS EX1 TIED TO EMERGENCY BATTERY INVERTER COOPER-LDSQ4B-30-D010
EX2 12 W WALL MOUNTED CYLINDER UP/DOWN LIGHT (TO BE LOCATED UNDER
EAVES ONLY)
COOPER-9003-W1-RW-LED4080-W-BZ-L1-UNV-WRR-DIM10
EX2E 12 W SAME AS EX2 TIED TO EMERGENCY BATTERY INVERTER COOPER-9003-W1-RW-LED4080-W-BZ-L1-UNV-WRR-DIM10
EX3 12 W WALL MOUNTED CYLINDER DOWN LIGHT COOPER-9003-W2-RW-LED4080-W-M-BZ-L1-UNV-WRR-DIM10
E5.2 SCALE: 1/4" = 1'-0"
POLE HEIGHT DETAIL2
No. Description Date