HomeMy WebLinkAboutC030_Water-Details 11-13-20MJ GLAND MJ VALVE MJ GLAND D.I. PIPE D.I. PIPE MJ TEED.I. PIPE D.I. PIPE MJ GLAND CONCRETE THRUST BLOCK (TYP) UNDISTURBED EARTH (TYP) MJ GLAND MJ VALVE D.I. PIPE 3/4" MIN. CORROSION RESISTANT ALL THREAD RESTRAINING ROD, CONFORMING TO ASTM A242-81, INSTALLED IN HALF THE AVAILABLE MECHANICAL JOINT BOLT HOLES (TYP) WHERE NECESSARY, CLAMPING LUGS (ROMAC "DUCTILE LUG" OR EQUAL) DESIGNED TO FIT DUCTILE IRON (D.I.) PIPE, AND CONFORMING TO ASTM 536-80 MAY BE USED IN CONJUNCTION WITH THE RESTRAINING RODS. "C" "B""A" 6" "C" REBAR ANCHOR CONCRETE ANCHORS NOTE: COAT ROADS WITH "KOPPERS" BITUMASTIC NO. 50 COATING OR EQUAL. THRUST BLOCK DIMENSIONS ANCHOR ROD SIZE VALVE SIZE 100 PSI A B C 150 PSI A B C 200 PSI A B C 250 PSI A B C 300 PSI A B C 1/2"6" & 8"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-7" 1/2"10"2'-0"2'-0"2'-0"2'-6"2'-6"2'-0"2'-9"2'-6"2'-6"3'-0"3'-0"3'-0"3'-7"3'-0"3'-0" 1/2"12"2'-3"2'-0"2'-0"3'-0"3'-0"2'-8"3'-5"3'-0"3'-0"4'-3"3'-0"3'-0"5'-1"3'-0"3'-0" 1"14"2'-3"2'-0"2'-0"3'-5"3'-0"3'-0"4'-6"3'-0"3'-0"4'-0"4'-0"4'-0"4'-9"4'-0"4'-0" 1-1/8"16"3'-0"3'-0"3'-0"4'-4"3'-0"3'-0"4'-1"4'-0"4'-0"5'-1"4'-0"4'-0"6'-1"4'-0"4'-0" 1-1/4"18"3'-8"3'-0"3'-0"5'-5"3'-0"3'-0"5'-1"4'-0"4'-0"6'-4"4'-0"4'-0"5'-9"5'-0"5'-0" 1-3/8"24"4'-4"4'-0"4'-0"6'-5"4'-0"4'-0"6'-6"5'-0"5'-0"6'-5"6'-0"6'-0"7'-8"6'-0"6'-0" NOTE: PRESSURES SHOWN ABOVE ARE MAXIMUM WORKING PRESSURES IN THE SYSTEM. THRUST BLOCKING AND ANCHORS ARE REQUIRED ON ALL 6" VALVES AND LARGER UNLESS SPECIFIED BY THE ENGINEER. MEGA-LUG OR APPROVED EQUAL JOINT RESTRAINTS MAY BE USED IN LIEU OF CONCRETE THRUST BLOCKS. THRUST BLOCKS NOT REQUIRED ON TAPPING VALVES. *CONCRETE THRUST BLOCK MINIMUM OF 1/2 CUBIC YARD WASHED GRAVEL UNDISTURBED EARTH GROUND LINE ELEVATIONS AS SHOWN ON PLANS OR 0.2' ABOVE TOP OF CURB GRADE INSTALL PLUMB WITH PUMPER NOZZLE FACING STREET NEW HYDRANT TO BE MUELLER SUPER CENTURION 250 OR WATEROUS PACER MINIMUM 4'-0" CLEAR ALL AROUND (TREES, HEDGES, BUSHES, ETC.) ADJUSTABLE SCREW TYPE VALVE BOX WITH LID 8'-0" (MAX) 3'-0" (MIN) TO BACK OF CURB MINIMUM OF 6.5' COVER TO MAIN LINE JOINT AS REQUIRED FOR PIPE SPECIFIED NEW 6" AUXILIARY GATE VALVEFLANGE JOINT *MEGA-LUG OR APPROVED EQUAL JOINT RESTRAINTS MAY BE USED IN LIEU OF CONCRETE THRUST BLOCK 1' MIN TO 2' MAX ABOVE FINISHED FLOOR FLANGE TO BE THREADED ON STANDPIPE, MJ TO FLANGE ADAPTERS NOT ACCEPTABLE (TYPICAL FOR ALL RISER CONFIGURATIONS) 3/4" MIN. REDI ROD, INSTALLED IN EVERY OTHER AVAILABLE MJ BOLT HOLES (TYP) - 5/8" RODS ACCEPTABLE FOR 4" LINES FLOOR BACKFLOW PREVENTION ASSEMBLY REQUIRED BACKFLOW PREVENTION DEVICE TO BE DETERMINED BY WATER SUPERINTENDENT METER SIZED SAME AS INCOMING LINE, NO EXCEPTIONS 4" OR LARGER CLASS 51 DUCTILE IRON PIPE (TYP) MECHANICAL JOINTMAIN TAPPING TEE & VALVE, OR INSTALL VALVE AT PROPERTY LINE (TYPICAL FOR ALL RISER CONFIGURATIONS) THRUST BLOCK NO PRESSURE GAUGES OR PRESSURE GAUGE FITTINGS WILL BE ALLOWED ON THE TEST PORTS OF ANY BACKFLOW PREVENTION ASSEMBLY. ***A MINIMUM OF FOUR (4) PIPE DIAMETERS OF STRAIGHT RUN PIPE IS REQUIRED UPSTREAM AND DOWNSTREAM OF THE METER / STRAINER ASSEMBLY 90° BEND WITH THRUST BLOCK FLANGED OS&Y VALVE 1' MIN TO 2' MAX ABOVE FINISHED FLOOR FLANGED OS&Y VALVE PROVIDE FLEXIBLE, WATER-TIGHT CONNECTION FOR ALL WALL OR FLOOR PIPE PENETRATIONS. MECHANICAL JOINT 90° BEND WITH THRUST BLOCK FLOOR FLANGED OS&Y VALVE 1' MIN TO 2' MAX 2' MIN TO 3' MAX CLEARANCE ABOVE FINISHED FLOOR COATED STEEL WALL PLATE, 5/16" MINIMUM THICKNESS CITY OF BOZEMAN REQUIREMENTS FOR INSTALLATION OF BACKFLOW PREVENTION ASSEMBLY 1.THE FIRST FITTING INSIDE OF THE BUILDING SHALL BE A UL LISTED FLANGED KENNEDY OR MUELLER OS&Y VALVE THE SAME SIZE AS THE SERVICE LINE. COMBINATION STRAINER / METER IMMEDIATELY FOLLOWING OS&Y VALVE - METER MUST SET HORIZONTAL. 2.ALL BACKFLOW PREVENTION ASSEMBLIES SHALL BE: A.UL OR FM LISTED. B.APPROVED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA FOUNDATION FOR CROSS CONNECTION CONTROL AND HYDRAULIC RESEARCH (USCFCCCHR) FOR OPERATION IN THE PROPOSED POSITION (VERTICAL OR HORIZONTAL) AS SHOWN ON APPROVED PLANS. C.INSTALLED AS SHOWN ON THE APPROVED PLANS. 3.HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF TWO FEET (2') AND MAXIMUM OF THREE FEET (3') ABOVE THE FINISHED FLOOR. 4.THE SERVICE RISER MUST BE A MINIMUM OF TWO FEET (2') FROM ANY OUTSIDE WALL. 5.THE INCOMING SERVICE LINE SHALL BE A MINIMUM OF 6.5' AND A MAXIMUM OF 7.5' BELOW THE FINISHED GRADE. 6.ALL SERVICE LINE APPURTENANCES SHALL HAVE A MINIMUM PRESSURE RATING OF 175 PSI. 7.ALL SERVICE LINES FOUR INCHES (4") AND LARGER SHALL BE CLASS 51 DUCTILE IRON PIPE. 8.LINE SIZING: THE BACKFLOW PREVENTION ASSEMBLY AND METER SHALL BE EQUAL IN SIZE TO BOTH THE INCOMING PIPE DIAMETER (UPSTREAM) AND OUTGOING PIPE DIAMETER (DOWNSTREAM). FOR EXAMPLE, A FOUR INCH (4") SERVICE LINE SHALL HAVE A FOUR INCH (4") METER AND BACKFLOW PREVENTION ASSEMBLY. 9.A MINIMUM OF FOUR (4) PIPE DIAMETERS OF STRAIGHT RUN PIPE IS REQUIRED UPSTREAM AND DOWNSTREAM OF THE METER / STRAINER ASSEMBLY. 1 1 METER & STRAINERSPOOL SPOOL BACKFLOW PREVENTION ASSEMBLY PRESSURE REDUCING VALVE NO FITTINGS BETWEEN METER AND BACKFLOW PREVENTION ASSEMBLY 2' MIN CLEAR TO OTHER MECHANICAL LINESINSTALL VALVE WITH STEM PARALLEL TO WALL OS&Y VALVE 90° BEND PLAN VIEW 2 23 4 NOTES: 1.STANDPIPE FLANGE TO BE ONE FOOT (1') MINIMUM TO INTERIOR WALL AND TWO FOOT (2') MAXIMUM TO EXTERIOR WALL. 2.A MINIMUM OF FOUR (4) PIPE DIAMETERS OF STRAIGHT RUN PIPE IS REQUIRED UPSTREAM AND DOWNSTREAM OF THE METER / STRAINER ASSEMBLY. 3.METER MUST BE INSTALLED HORIZONTAL. STRAINER IS REQUIRED. 4.BACKFLOW PREVENTION ASSEMBLIES MUST BE UL OR FM LISTED AND APPROVED BY USCFCCCHR. 5.ALL PIPE SHALL BE DUCTILE IRON UP TO PRESSURE REDUCING VALVE.Know what's below. before you dig.Call R NOT TO SCALE TYPICAL VALVE / TEE RESTRAINT DETAIL02660-10 NOT TO SCALE THRUST BLOCKING FOR WATER MAIN VALVES DETAIL02660-3 NOT TO SCALE FIRE HYDRANT DETAIL 02660-4 NOT TO SCALE WATER SERVICE LINE DETAIL - FOR SIZES 4" AND LARGER02660-12 NOT TO SCALE TYPICAL RISER CONFIGURATION - 4" AND LARGER DOMESTIC SERVICE02660-12A REVIEWSUBMITTALDEVELOPMENTAPARTMENT UNITS IN BOZEMAN, MONTANAFARRAN REALTY PARTNERSBOZEMAN EAST MIXED-USE4202 BELTWAY DRIVE ADDISON, TX 75001hedk.com214.520.8878Engineering1800 RIVER DR. NO. • GREAT FALLS, MONTANA 59401406.761.3010 • tdhengineering.com