Loading...
HomeMy WebLinkAboutWastewater Generation Estimates 06-10-2020# of Dwelling Units (DUs)138 DU # of people per dwelling**2.17 persons/DU** population 299 people peaking factor*4.08 assumed infiltration rate**150 gallons/acre/day lot area 8.78 acres infiltration rate 1317 gpd wastewater generation rate**65 gal/day/person Average Wastewater Flow Rate 14.4 gpm Average Wastewater Flow Rate 20752 gallons per day Peak Wastewater Flow Rate 56.0 gpm Peak Wastewater Flow Rate 3360 gallons per hour *Calculated Per Harmon Formula **Based on City of Bozeman Design Standards and Specifications Policy Westside Flats Master Site Plan  Sewer Flow Calculations 06/04/2020