HomeMy WebLinkAbout19 - Design Report - Jennifer Place - Water, SewerWATER & SEWER DESIGN REPORT
JENNIFER PLACE CONDOMINIUMS
PHASE 1-6 SITE PLAN
LOT 1, BLOCK 9
LAUREL GLEN SUBDIVISION PHASE 1
Prepared for:
Great Western Investment, LLC
15525 Horse Creek Road
Bozeman, MT 59715
Prepared by:
C&H Engineering and Surveying, Inc.
1091 Stoneridge Drive, Bozeman, MT 59718
(406) 587-1115
Project Number:190065.1
November 2019
INTRODUCTION
The Jennifer Place Condominium Master Site Plan proposes to develop Lot 1, Block 9, Laurel
Glen Subdivision Phase 1. The proposed development consists of ten 2-unit condominiums with a
proposed access road and associated utilities.This project will require connection to existing City
of Bozeman water and sanitary sewer systems.
WATER SYSTEM LAYOUT
The Jennifer Place Condominiums will tap into the existing 8” water mains running along Laurel
Parkways (east) and Annie Street (north)as shown on the plans included herein.All new water
mains are to be installed in the City standard location and will be located 10’ away from any
proposed sewer mains.All water mains will be looped and internal hydrants will be installed no
more than 400 feet apart.
A WaterCAD analysis is enclosed at the end of the report analyzing the 8-inch water main
extension installed with this project. The connection to the existing system was modeled as a pump
curve using data obtained from the City of Bozeman Water Department: static, residual and pitot
pressures were read at the hydrant located at the intersection of Annie Street/Rosa Way.This data
was used to develop the pump curve used at the connection point to model the existing system. The
following equation based off of the Hazen Williams method is used to generate the pump curve:
Q = Qf x ((Ps -P) / (Ps -Pr))0.54
Where: Q = flow predicted at desired residual pressure, Qf = total flow measured during test, Pr=
residual pressure during test, Ps = static pressure and P = residual pressure at the desired flow rate.
In the model, the pump is connected to a reservoir which acts as a source of water. The elevation of
the reservoir is fixed at the elevation of the pump, which is also equivalent to the elevation of the
tie-in point. The reservoir does not create any head on the system; the head is generated entirely by
the pumps. The input data and the pump curves are included at the end of the report. The pump
curve table includes all calculations and equations used in determining flow characteristics at the
connection point. A C-factor of 130 was chosen for ductile iron class 51 pipe.
WATER DISTRIBUTION SYSTEM SIZING
Residential Units:
Average Daily Residential Usage =170 gallons per capita per day
Average Population Density =2.17 persons/dwelling unit
Minimum Fire Hydrant Flow =1,500 gpm
Residual Pressure Required =20 psi for Fire Flow
Average Day Demand (Peaking Factor = 1)
Maximum Day Demand (Peaking Factor = 2.3)
Maximum Hour Demand (Peaking Factor = 3.0)
Residential Water Demands (Demand Junction 1)
Average Day Demand =20 d.u.x 2.17 persons/d.u. x 170 gpcpd =7,378 gpd =5.1 gpm
Maximum Day Demand =5.1 gpm x 2.3 =11.7 gpm
Peak Hour Demand =5.1 gpm x 3.0 =15.3 gpm
Available Pressure:8-inch class 51 ductile iron main Annie Street and Rosa Way
Static = 96 psi (Hydrant #2005)
Residual = 88 psi (Hydrant #2005)
Pitot (2.5” nozzle) = 80 (Hydrant #1985)
Flowing = 1,500 gpm (Hydrant #1985)
Water Demands (Demand Junction 1)
Average Day Demand = 8 d.u. x 2.17 persons/d.u. x 170 gpcpd = 2,951 gpd = 2.0 gpm
Maximum Day Demand = 2.0 gpm x 2.3 = 4.7 gpm
Peak Hour Demand = 2.0 gpm x 3.0 = 6.1 gpm
Water Demands (Demand Junction 2)
Design Report -Page 4 of 8
Average Day Demand = 12 d.u. x 2.17 persons/d.u. x 170 gpcpd = 4,427 gpd = 3.1 gpm
Maximum Day Demand = 3.1 gpm x 2.3 = 7.1 gpm
Peak Hour Demand = 3.1 gpm x 3.0 = 9.2 gpm
HYDRAULIC ANALYSIS
A water distribution model was created using WaterCAD Version 10.01.00.72 for demand
forecasting and describing domestic and fire protection requirements. In order to model the
system, each junction node of the water distribution system was assessed a demand based on its
service area. The table shown below quantifies the demands placed at the junction nodes and
calculates the demands for the Average Day,Maximum Day and Peak Hour within the
development. The peaking factor for each case is 1, 2.3 and 3.0 respectively.
Jenny Place Condominiums (Table 1):
DEMANDJUNCTIONNODE DWELLINGUNITS (D.U.)
POPULATION(RES.) 2.17PEOPLE PERD.U.
AVERAGE DAYGPM (170GALLONS PERDAY PERPERSON)
MAX.DAYGPM
PEAKHOURGPM
DJ 1 8 17 2.0 4.7 6.1
DJ 2 12 26 3.1 7.1 9.2
Total 20 43 5.12 11.78 15.37
*See Demand Junction Map for more information on which lots contribute to each DemandJunction.
CONCLUSION
The proposed 8-inch DIP water mains provide adequate capacity to serve the subdivision under the
Peak Hour Demand condition. The flows and pressures within the system for the Peak Hour
Demands were generated with the WaterCAD program and can be found in Appendix A.
The capacity of the system to meet fire flow requirements was tested by running a steady state fire
flow analysis for all junctions at fire hydrant locations. The model shows that all hydrant junctions
satisfy fire flow constraints (residual pressure >20 psi,flow rate > 1500 gpm), while providing
service to lots at peak hour.The results of the analysis at peak hourly flow are given in Appendix
A.
Design Report -Page 5 of 8
SANITARY SEWER SYSTEM
An 8-inch PVC sanitary sewer line will be installed within the 25-foot public access and utility
easement.The proposed main and will flow north and connect with the existing 8-inch main
located on Annie Street.
DESIGN REQUIREMENTS
The flow rates used herein are according to the City of Bozeman Design Standards and
Specifications Policy (DSSP)dated March,2004. The peaking factor for the design area is
determined by figuring the equivalent population and inserting the population into the Harmon
Formula.The population was calculated by applying 2.17 people per dwelling unit and 65 gallons
per day (gpd) per person.An 8-inch main is used because that is the minimum diameter allowed
within the City of Bozeman.
Using the wastewater flow rate by land use designation (Table V-1 in the City of Bozeman Design
Standards and Specifications Policy), the average daily flow for the subdivision is calculated.
The peaking factor is calculated by using the Harmon Formula.
Connection:
Equivalent Population =(20 dwelling units*2.17 people/unit) =44 persons
Harmon Formula:Peaking Factor = (18 + P0.5)/(4 + P0.5)
where:P = Population in thousands
Peaking Factor = (18 +0.0440.5)/(4 +0.0440.5)
Peaking Factor =4.33
Assumed infiltration rate = 150 gallons/acre/day = 150 (2.04 acres) =306 gal/day
The peak flow rate is calculated by multiplying the Average Daily Flow (Qave) by the Peaking
Factor and adding the assumed infiltration rate:
Design Flow Rate =(44 persons*65 gpd/person) = 2,860 gpd = 0.0044 cfs
Design Report -Page 6 of 8
Peak Flow Rate =2,860 gpd (4.33) +306 gpd gpd =12,690 gpd
=8.813 gpm
=0.0196 cfs
The capacity of an 8-inch main is checked using Manning’s Equation:
Qfull = (1.486/0.013)AR2/3S1/2
For an 8-inch PVC main:
Manning's n = 0.013 for PVC Pipe
Minimum Slope = 0.004 ft/ft
A =area =(3.14/4)d 2 = (3.14/4)(8/12)2 = 0.34907 ft2
P =perimeter =2(3.14)r = 2(3.14)(4/12) = 2.0944 ft
R =hydraulic radius =A/P = 0.34907/2.0944 = 0.16667 ft
R2/3 = 0.30105 ft
S = 0.004 ft/ft
S1/2 = 0.0632 ft/ft
Qfull = (1.486/0.013)(0.34907)(0.30105)(0.0632)= 0.7592 cfs
Connection:
Q/Qfull =0.0196 /0.7592 = 0.4775 or 2.58%
Based on these calculations,an 8-inch sewer line has adequate capacity to carry the design flows
for this development.Additionally, the Laurel Glen lift station has enough capacity to handle the
design flow based on a 2002 Lift Station Design Report done by Allied Engineering, and the 2018
Lift Station Analysis completed by C & H Engineering.
Design Report -Page 7 of 8
APPENDIX A
WATERCAD MODEL
Scenario: Base
P-5P-7
Page 1 of 127 Siemon Company Drive Suite 200 WWatertown, CT 06795 USA +1-203-755-166610/30/2019
WaterCAD[10.02.02.06]Bentley Systems, Inc. Haestad Methods SolutionCenter190065 water cad model.wtg
Scenario Summary Report
Scenario: Base
Scenario Summary
1ID
BaseLabel
Notes
Base Active TopologyActive Topology
Base PhysicalPhysical
Base DemandDemand
Base Initial SettingsInitial Settings
Base OperationalOperational
Base AgeAge
Base ConstituentConstituent
Base TraceTrace
Base Fire FlowFire Flow
Base Energy CostEnergy Cost
Base TransientTransient
Base Pressure Dependent DemandPressure Dependent Demand
Base Failure HistoryFailure History
Base SCADASCADA
Base User Data ExtensionsUser Data Extensions
Base Calculation OptionsSteady State/EPS Solver Calculation
Options
Base Calculation OptionsTransient Solver Calculation Options
Hydraulic Summary
Steady StateTime Analysis Type TrueUse simple controls during
steady state?
Hazen-WilliamsFriction Method FalseIs EPS Snapshot?
0.001Accuracy 12:00:00 AMStart Time
40Trials Fire FlowCalculation Type
Page 1 of 127 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]
Bentley Systems, Inc. Haestad Methods Solution
Center190065 water cad model.wtg
Fire Flow Node FlexTable: Fire Flow Report
Junction w/
Minimum
Pressure
(System)
Pressure
(Calculated Zone
Lower Limit)
(psi)
Pressure
(Zone Lower
Limit)
(psi)
Pressure
(Calculated
Residual)
(psi)
Pressure
(Residual
Lower Limit)
(psi)
Flow (Total
Available)
(gpm)
Flow (Total
Needed)
(gpm)
Fire Flow
(Available)
(gpm)
Fire Flow
(Needed)
(gpm)
Label
(N/A)(N/A)0(N/A)20(N/A)(N/A)(N/A)1,500J-5
(N/A)(N/A)0(N/A)20(N/A)(N/A)(N/A)1,500DJ 1
(N/A)(N/A)0(N/A)20(N/A)(N/A)(N/A)1,500DJ 2
DJ 134020202,7871,5002,7871,500Hyd. 1
Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA
+1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]Bentley Systems, Inc. Haestad Methods Solution Center190065 water cad model.wtg
FlexTable: Pipe Table
Headloss
Gradient
(ft/ft)
Hydraulic
Grade (Stop)
(ft)
Hydraulic
Grade (Start)
(ft)
Velocity
(ft/s)
Flow
(gpm)
Minor
Loss
Coefficie
nt
(Unified)
Hazen-
Williams
C
MaterialDiameter
(in)
Length (User
Defined)
(ft)
Label
0.000269.70269.700.10152.020130.0Ductile Iron8.0208P-3
0.000269.70269.700.0692.060130.0Ductile Iron8.0308P-4
0.00048.0048.000.00150.000150.0PVC999.01P-5
0.000269.70269.700.10150.000150.0PVC8.0500P-6
0.000269.70269.700.0001.280130.0Ductile Iron6.027P-7
Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA
+1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]Bentley Systems, Inc. Haestad Methods Solution Center190065 water cad model.wtg
FlexTable: Junction Table
Pressure
(psi)
Hydraulic Grade
(ft)
Demand
(gpm)
Demand CollectionElevation
(ft)
LabelID
96269.700<Collection: 0 items>48.00J-539
96269.706<Collection: 1 items>48.50DJ 140
97269.709<Collection: 1 items>44.50DJ 242
96269.700<Collection: 0 items>48.50Hyd. 148
Page 1 of 127 Siemon Company Drive Suite 200 W Watertown, CT 06795 USA
+1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]Bentley Systems, Inc. Haestad Methods Solution Center190065 water cad model.wtg
Pump Definition Detailed Report: Hydrant 1 (Annie St. X Rosa Way)
Element Details
91ID Notes
Hydrant 1
(Annie St. X
Rosa Way)
Label
Pump Curve
Head(ft)Flow(gpm)
221.540
208.001,284
196.001,781
185.002,181
173.002,526
162.002,835
150.003,117
138.003,379
127.003,625
115.003,857
104.004,079
92.004,290
81.004,493
69.004,688
58.004,876
46.005,059
35.005,236
23.005,408
11.545,576
0.005,739
Pump Efficiency Type
BestEfficiencyPointPump Efficiency Type %100.0Motor Efficiency
%100.0BEP Efficiency FalseIs Variable Speed Drive?
gpm0BEP Flow
Transient (Physical)
lb·ft²0.000Inertia (Pump and Motor)SI=25,
US=1280Specific Speed
rpm0Speed (Full)TrueReverse Spin Allowed?
Page 1 of 227 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]
Bentley Systems, Inc. Haestad Methods Solution
Center190065 water cad model.wtg
Pump Definition Detailed Report: Hydrant 1 (Annie St. X Rosa Way)
Page 2 of 227 Siemon Company Drive Suite 200 W
Watertown, CT 06795 USA +1-203-755-1666
10/30/2019
WaterCAD
[10.02.02.06]
Bentley Systems, Inc. Haestad Methods Solution
Center190065 water cad model.wtg
Design Report -Page 8 of 8
APPENDIX B
DEMAND JUNCTION MAP