HYALITE Brett Megaard <bmegaard@hyaliteeng.com>
Gallatin Subaru-Bozeman-Proposed Utility Locations
Dooley, Cammy <Cammy.Dooley@northwestern.com> Tue, Feb 25, 2020 at 12:04 PM
To: Brett Megaard <bmegaard@hyaliteeng.com>
Cc: Darwin Lindahl <darwin@lindahlarchitects.com>
Brett,
Thank you for the reminder call on this. As per our conversation today, one of my questions is regarding the service
requirement. Currently the building is being served by 120/240V 3 phase, is there a chance that it will upgrade to
120/208V? If so,then the transformer pad will likely be a 6'x6' and if the wall is combustible, there will need to be
10' of separation from the building. If the wall is made of non-combustible material, then the distance can be
reduced to 2'. Depending upon the service amperage,there is a possibility that the existing electric transformers can
be used and a service wire run to the west side of the building. I measured the distance at about 135', but that was
to where the gas meter is proposed at so it would need to be relocated. So if we can re-use the existing transformer,
the additional utility easement needed to go across the parking lot can be removed. IF, we need to keep it in its
proposed location, the easement width will only need to be 10'. If we determine that it needs to stay in the proposed
location, please submit a site plan to Dylan Swanson with NWE to get an easement document that meets NWE
standards. His email is Dylan.Swanson@northwestern.com.
Additionally, if we could get the gas and electric meter nearer to each other that would be ideal.
If it hasn't been completed, please submit an application to NWE to discuss with the design engineer in the area. The
following is a link to the application. Please let the engineer know that we have talked.
https://northwesternenergy.com/account-services/new-construction/new-construction-form-v2?State=MT
Thanks,
Cammy
https://mail.google.com/mail/u/0?ik=381 ad69777&view=pt&search=all&permmsgid=msg-f%3Al659536668135403152&simpl=msg-f%3Al6595366681... 1/3
3/3/2020 Hyalite Engineers, PLLC Mail-Gallatin Subaru_Bozeman_Proposed Utility Locations
Cammy Dooley, P.E.
Engineer
cammy.dooley@northwestern.com
O (406) 582-4680
C (406) 539-2359
F (406) 585-9634
121 E Griffin Dr I Bozeman, MT 59771
Nord iWstern
Delivering o Bright FvWn
From: Brett Megaard <bmegaard@hyaliteeng.com>
Sent:Tuesday, February 18, 2020 3:33 PM
To: Dooley, Cammy<Cammy.Dooley@northwestern.com>
Cc: Darwin Lindahl <darwin@lindahlarchitects.com>
Subject: Re: Gallatin Subaru_Bozeman_Proposed Utility Locations
NOTICE: This message has been sent by an EXTERNAL sender outside of
NorthWestern Energy. Please use caution when clicking on links, opening attachments,
or replying to this email.
[Quoted text hidden]
This message is for the named person's use only. It may contain confidential, proprietary
or legally privileged information. No confidentiality or privilege is waived or lost by any
mistransmission. If you receive this message in error, please immediately delete it and
all copies of it from your system, destroy any hard copies of it and notify the sender. You
must not, directly or indirectly, use, disclose, distribute, print, or copy any part of this
message if you are not the intended recipient. NorthWestern Corporation and its
https://mail.google.com/mail/u/0?ik=381 ad69777&view=pt&search=all&permmsgid=msg-f%3Al659536668135403152&simpl=msg-f%3Al6595366681... 2/3
3/3/2020 Hyalite Engineers, PLLC Mail-Gallatin Subaru_Bozeman_Proposed Utility Locations
subsidiaries each reserve the right to monitor all e-mail communications through its
network.
https://mail.google.com/mail/u/0?ik=381 ad69777&view=pt&search=all&permmsgid=msg-f%3Al659536668135403152&simpl=msg-f%3Al6595366681... 3/3