HomeMy WebLinkAbout4_Stormwater Management Report_02-04-2020 STORMWATER MANAGEMENT DESIGN REPORT FOR: COLLINS APARTMENTS LOTS 2 & 3, BLOCK 1 CATTAIL CREEK SUBDIVISION, PH. 3 BOZEMAN, MT Prepared By: M MADISON ENGINEERING Madison Engineering 895 Technology Drive, Suite 203 Bozeman, MT 59718 (406) 586-0262 FEBRUARY 2020 M STORMWATER MANAGEMENT DESIGN REPORT FOR: COLLINS APARTMENTS LOTS 2 & 3, BLOCK I CATTAIL CREEK SUBDIVISION, PH. 3 BOZEMAN, MT ' e-i!IS, C re //rrtlit Madison Engineering 895 Technology Blvd Ste 203 Bozeman, MT 59718 (406) 586-0262 FEBRUARY 2020 COLLINS APARTMENTS SITE PLAN LOT 2 & 3, BLOCK 1, CATTAIL CREEK SUBDIVISION, PHASE 3 STORMWATER DESIGN REPORT A. Introduction The proposed development for the Collins Apartments will be constructed on Lots 2 and 3, Block 1, of Cattail Creek Subdivision Phase 3. The site will have four buildings, each with four apartments, for a total of 16 dwelling units. The site will contain stormwater onsite and allow infiltration/retention through underground infiltration chambers consisting of 36-inch diameter perforated corrugated metal pipe(CMP) that capture runoff via stormwater inlets in the parking lot and drive lanes. The following references were used in the preparation of this report: a. COB Design Standards and Specifications Policy, 2004. Addendum #6 b. COB Modifications to Montana Public Works Standard Specifications (MPWSS) B. Stormwater Management The infrastructure for Lots 2 and 3 will be constructed in one phase although the construction of the buildings may be phased. Stormwater from Lot 2 flows in a northerly direction from the drive aisle and driveways into two storm inlets at the center of the lot. These flows are directed into an underground infiltration facility on the west side of the site (straddling Lots 2 and 3). The flows from Lot 3 flow in a northerly direction into an inlet at the northwest corner of the drive aisle, which directs flows into an underground infiltration facility along the west side of the site. All four buildings will tie their roof downspouts into an 8-inch ADS pipe that connects to the storm system and ultimately drains into the infiltration chambers. Storm water run-off is calculated based on the Rational Formula and infiltration/retention facilities are sized per the City of Bozeman's design standards for a storm intensity of 10-year frequency and a 2-hour duration. Table 1 below shows the required and proposed storage volumes for the two (Lot 2: southern; Lot 3: northern) infiltration basins. The calculations that produce these volumes can be found in Appendix A. Table 1:Facilih'.Storage Eolunres Facility ID Required Storage Volume cu ft Proposed Storage Volume cu ft) Northern 409 452.2 Southern 400 409.8 Collins Apartments Stonnwater Design Report Page 1 of 2 C. Curb inlet adequacy check The three curb inlets that received surface flow from the site were checked for capacity. All standard 24-inch by 36-inch curb inlets are adequate to handle the runoff from a 25-year storm event. See Appendix B for more information. Appendices A. Stormwater calculations B. Curb Inlet adequacy check C. Stormwater Maintenance Plan D. Drainage Exhibit Collins Apartments Stormwater Design Report Page 2 of 2 Appendices Appendix A — Stormwater Calculations Collins Apartments 1/9/2020 North Basin Stormwater Run-off and Infiltration Calculation Calculation of Required Volume for Storm Water Infitration System Design Rainfall Freq ?c aQ-•,;,year IDF coefficient a 064 IDF coefficient h IDF coefficient n 065 Post-development Calculations C Areas(ft): Impervious 17.455 090 Landscapec 7.942 0.20 Total: 25,397 total area: 0 58 acres composite C: 068 Overland tc average slope: 075 percent travel distance: >_•feet tc: 10 minutes intensity at t,(fig 23): 2.07 in/hr post-devel peak runoff: 082 cfs Infiltration Rate Calculation Trench Width= 40 Trench Length= 64.0 Total Infiltration Surface Area= ?56 ft2 Infitration Rate= 5 inch/min 0.00069 f/s Q= 0.18 cfs Storrs Duration Intensity Future Runoff Runoff Infiltration Required (minutes) (in/hr) Rate(cfs) Volume(cf) Volume(cf) Storage(cf) 10 2.07 0 82 486 105 381 12 1.84 0.73 518 126 392 14 1.66 0.66 547 148 400 16 152 0.60 574 169 405 18 141 0.56 598 190 408 20 131 0.52 621 212 409 22 123 0.49 642 233 409 24 117 0.46 662 254 408 26 111 0.44 681 276 406 28 105 0.42 699 297 402 30 101 0.40 716 318 398 32 0 97 0.38 733 340 393 34 0.93 0.37 749 361 388 36 0.89 0.36 764 382 382 38 086 0.34 779 404 375 40 0.84 0.33 793 425 368 42 0.81 0.32 806 446 360 REQ'D STORAGE(ft'): 409 Contech Corrugated Perforated CMP Pipe Storage Calculations Pipe Area A=314xR2 Diameter ft Radius(ft) 3 1.5 3.14 = 7.07 ft2 Infiltration Surface Area Length = 64 ft Pipe Diameter = 3 ft Additional Trench Width = 1 ft Infiltration Surface Width = 4 ft Infiltration Surface Area = 256 ft2 Pipe Volume A=3.14xR2 Diameter(ft) Radius(ft) 3 1.5 3.14 = 707 ft2 Length 64 ft PROPOSED STORAGE: = 452.2 ft Infiltration Calc-Corrugated CMP-North As Collins Apartments 1/9/2020 South Basin Stormwater Run-off and Infiltration Calculation Calculation of Required Volume for Storm Water Infitration System Design Rainfall Freq E'..i._ 14;:; ; year IDF coefficient a 0.64 IDF coefficient b IDF coefficient n 065 Post-development Calculations Areas(ft): Impervious 16.965 090 Landscape( 5,951 0.20 Total: 22,916 total area: 053 acres composite C: 072 Overland t. average slope: 075 percent travel distance: 145 feet tc: 9 minutes intensity at tc(fig 23): 2.13 in/hr post-devel peak runoff: 0 80 cfs Infiltration Rate Calculation Trench Width= 4,0 Trench Length= 58.0 Total Infiltration Surface Area= 232 ftZ Infitration Rate= 0.50 Inch/min 0.00069 f/s Q= 0.16 cis Storm Duration Intensity Future Runoff Runoff Infiltration Required (minutes) (in/hr) Rate(cfs) Volume(cf) Volume(cf) Storage(cf) 9 2.13 0.80 456 91 365 11 188 0.71 488 111 377 13 1,69 0.64 516 130 386 15 1.55 0.58 542 149 392 17 1.43 0.54 565 169 396 19 1.33 0.50 587 188 399 21 1.25 047 607 207 400 23 1.18 045 627 227 400 25 1.12 0.42 645 246 399 27 1.06 0-40 662 265 397 29 1.02 0.38 679 285 394 31 0.97 0.37 694 304 390 33 0.94 0.35 710 323 386 35 0.90 0.34 724 343 381 37 0.87 0.33 738 362 376 39 0,84 0.32 752 381 370 41 0.81 0.31 765 401 364 REQ'D STORAGE(ft):1 400 Contech Corrugated Perforated CMP Pipe Storage Calculations Pipe Area A=3.14xR2 Diameter(ft Radius(ft) 3 15 314 = 7.07 ftZ Infiltration Surface Area Length = 58 ft Pipe Diameter = 3 ft Additional Trench Width = 1 it Infiltration Surface Width = 4 it Infiltration Surface Area = 232 ftz Pipe Volume A=3.14xR2 Diameter(ft) Radius(it) 3 15 3.14 = 7.07 ftZ Ln_ngih = 58 ft PROPOSED STORAGE: = 409.8 ft Infiltration Calc-Corrugated CMP-South As Appendix B — Curb Inlet adequacy check I Collins Apartments Peak flow calculations Curb Inlet Drainage Basins-Post Development Peak Flow Summary(cfs) Area Drainage Area No. Area(Ac.) Weighted C 100 Yr 25 Yi i o Yr S.drive aisle DA 1 0.420 0.72 1.62 1.22 1.06 E.drive aisle DA 2 0.110 0.72 0.81 0.61 0.53 N.drive aisle DA 3 0.580 0.68 2.00 1.59 1.41 OF Equations from Bozeman Stormwater Master Plan for City of Bozeman,March 1982 General Equation i=a/(b+D)"where D is duration in hours,i=intensity in inches/hour Storm Information Design Rainfall Freq. 100 25 10 OF coefficient a 1.01 0.78 0.64 OF coefficient b 0 0 0 OF coefficient n 0.67 0.64 0.65 Adjustment Factor Cf: 1.25 1.1 1 Peak Q Values Drainage Area 1 Area 0.420 acres Weighted C 0.72 Average slope 0.75 percent Travel Distance 145 feet Design Rainfall Freq. 100 25 10 years C`Cf 0.90 0.79 0.72 (Shall not exceed 1.00) Total tc: 4.96 7.63 9.42 minutes intensity at t. 5.37 4.02 3.49 in/hr peak runoff: 1.62 1.22 1.06 cfs Drainage Area 2 Area 0.110 acres Weighted C 0.72 Average slope 2.72 percent Travel Distance 50 feet Design Rainfall Freq. 100 25 10 years C'Cf 0.90 0.79 0.72 (Shall not exceed 1.00) Total t�: 1.89 2.92 3.60 minutes intensity at tc 10.23 7.66 6.65 in/hr peak runoff: 0.81 0.61 0.53 cfs Drainage Area 3 Area 0.580 acres Weighted C 0.68 Average slope 0.75 percent Travel Distance 130 feet Design Rainfall Freq. 100 25 10 years C'Cf 0.85 0.75 0.68 (Shall not exceed 1.00) Total tc: 5.87 8.26 9.86 minutes intensity at tc 4.80 3.81 3.39 in/hr peak runoff: 2.00 1.59 1.41 cfs Page 1 of 1 Collins Apartments Gutter Capacity Calculations Allowable Pavement Encroachment Given: T= 9 feet(max per city) T W= 1.5 feet -W--Ts - Ts= 7.5 feet Sw= 0.0625 ft/ft Sx= 0.03 ft/ft a a= 0.59 inches a S• d= 3.24 inches ° n= 0.015 S. Sw/Sx= TM= Capacity for Gutter equations: Q=QW +Qs Where Q W =EoQ Qs.= Discharge within the Roadway above the depressed section(cfs) QS Qw= Discharge within the depressed Q= I—E (gutter)section(cfs) ° Cf= 0.56 for English units QS =Cr SX 5TS8S�,1 Sx= Pavement cross slope(ft/ft) n Ts= Width of flow in the roadway above depressed section So= Gutter longitudinal slope(ft/ft) S /S Sw= Gutter depression cross slope(ft/ft) E = 1+ W "Sx T= Spread (ft) ( �T/W 1+ S W/)—] —1 W= Width of gutter depression (ft) Capacity solution Gutter Capacity-Drainage Area 1 Gutter Capacity-Drainage Area 2 So= 0.0075 So= 0.0272 QS= 2.02 cfs Qs= 3.84 cfs Eo= 0.41 cfs Eo= 0.42 cfs Q= 3.50 cfs Q= 6.67 cfs Gutter Capacity-Drainage Area 3 So= 0.0075 QS= cfs Eo= cfs Q= cfs DA AREA 25 Yr Design Flow(cfs) 1 S.drive aisle 1.22 2 E.drive aisle 0.61 3 N.drive aisle 1.59 Summary The gutter capacity is adequate for all three proposed curb inlets Page 1 of 1 Collins Apartments Inlet Capacity Calculations Gutter Section Given T= 9.0 feet T W= 1.50 feet Ts= 7.50 feet W Ts SW= 0.06 ft/ft Sx= 0.03 fUft _ a = 0.59 inches d = 3.24 inches n = 0.015 d "� Where: So= 0.016 s. a Qs= Discharge within the Roadway above the depressed section (cfs) Qw= Discharge within the depressed (gutter) section (cfs) Capacity for Inlets on Grade Cf= 0.56 for English units (Standard 24x36 Curb inlet) Sx= Pavement cross slope (ft/ft) Ts= Width of flow in the roadway above Drainage Area 1 depressed section So= Gutter longitudinal slope(ft/ft) Qw= 1.48 cfs Sw= Gutter depression cross slope (ft/ft) Qs= 2.02 cfs T= Spread (ft) Cross-sectional area of flow W= Width of gutter depression (ft) A= 1.22 ft2 Gutter Velocity V= 2.88 ft/sec Fraction of side flow intercepted Rs= 0.27 Total flow capacity intercepted b the inlet Qint= 2.07 cfs Qbypass= 1 4' cfs Design Q for inlet#1 Q25= 1.22 cfs Single Inlet Sufficient Drainage Area 2 Qw= 2.83 cfs Qs= 3.84 cfs Cross-sectional area of flow A= 1.22 ft2 Gutter Velocity V= 5.49 ft/sec Fraction of side flow intercepted Rs= 0.10 Total flow capacity intercepted by the inlet Page 1 of 2 Qint= 3.32 cfs Qbypass= 3.34 cfs Design Q for inlet#2 Q25= 0.61 cfs Single Inlet Sufficient Drainage Area 3 Qw= 1.48 cfs Qs= 2.02 cfs Cross-sectional area of flow A= 1.22 ftz Gutter Velocity V= 2.88 ft/sec Fraction of side flow intercepted Rs= 0.27 Total flow capacity intercepted by the inlet Qint= 2.07 1 cfs Qbypass= 1.43 cfs Design Q for inlet#3 Q25= 1.59 cfs Single Inlet Sufficient Page 2 of 2 Appendix C — Stormwater Maintenance Plan a STORMWATER MAINTENANCE PLAN Collins Apartments Owner's responsibility for routine inspection and maintenance 1. Keep the inlets of the facilities free of leaves, rocks, and other debris. 2. Re-sod damaged or maintained areas immediately, or use grass plugs from the adjacent up-slope area. 3. See that litter and other debris are removed from inlets, swales, and vegetated and paved areas. 4. Maintenance of the underground systems are as follows: • Minimum required maintenance includes a quarterly inspection during the first year of operation and a yearly inspection thereafter. Utilize inspection ports for inspections. • The inspection ports can be used to pump water into the system and re- suspend accumulated sediment so that is may be pumped out. Flush and pump as inspections deem necessary. • Utilize the adjacent upstream storm sewer manhole or cleanout for removal (vacuuming) of debris from the end of the storm drain at the connection point with the underground chamber. 5. Owner to maintain and fund Operation and Maintenance of stormwater facilities. Shane Collins, Owner's Representative GAMADISON ENGINEERING\PROJECTS\2019\19-116 Springer-Collins\Stonn'.STORMWATER MAINTENANCE PLAN.doe Appendix D — Drainage Exhibit b � I / 'L99ti ' / �-4 I �® / p18991' td > __ • o tfi 4669.5 � 64 b L-- ——J L-- n all eo Tcr- td N — OL9V I\ 4668.5 69 loc N \a4 6 0` � � A 4670.0 � � m cc 8900 IX yam{ I �'699 yS•g � S , PN --- ---- O ----- ------ ----- ------- M S/ // / 3 M 104 M MIM WARBLERWAY zqtz IQ � ---------- o cc) y - - - - - - - - - - - - - - - - - - - - - - - - - T \ G:\ACAD\2019\19-116 Springer—Collin \dwg\Civil\Grading\Grading Plan.dwg I