HomeMy WebLinkAbout18 - Design Report - Flanders Mill Ph 7 - Stormwater DESIGN REPORT STORMWATER MANAGEMENT FLANDERS MILL SUBDIVISION, PHASE 7 Prepared for: Flanders Mill, LLC 235 Greenhills Ranch Road, Bozeman, MT 59718 Prepared by: C&H Engineering and Surveying, Inc. 1091 Stoneridge Drive, Bozeman, MT 59718 (406) 587-1115 Project Number: 14500 January 2018 INTRODUCTION The proposed Flanders Mill Subdivision— Phase 7 infrastructure improvements will include the construction of Oak Street from the Flanders Mill Road (FMR) intersection, east to the Phase 4 limit of paving, the construction of Windrow Drive, from Oak Street north to Broken Spur Drive, the construction of Broken Spur Drive,and the construction of Harvest Parkway from Broken Spur Drive west to FMR. Stormwater runoff from these improvements will be conveyed via curb and gutter channel flow to a series of curb chases and storm sewer inlets. It will then be routed through storm drainage pipes to 3 detention ponds, and the existing pond in the Phase 4 Park, before being released into the relocated tributary stream flowing through the subdivision, or the relocated irrigation overflow ditch west of Flanders Mill Road. A Drainage Area Map is included in Appendix A, and calculations for each individual drainage area (total area, weighted C factor, and time of concentration) are included in Appendix B. In addition to the various drainage areas contributing to these ponds, the multi-family lot west of Windrow Drive is anticipated to contribute to these infrastructure improvements as well. The multi-family lot site plan is being designed by Madison Engineering, Inc, and although it has not undergone site plan review by the City of Bozeman, Madison Eng. has provided preliminary drainage design for the lot so that it can be incorporated into the Phase 7 infrastructure design. Currently, Madison Eng. plans to retain the first 0.5" of rainfall to all impervious areas of the multi-family lot on the lot itself, and release volumes that exceed this 0.5" to the Phase 7 infrastructure. Currently, the portion of the multi-family lot that releases to the Phase 7 infrastructure is broken into 2 basins (Basin A and B). Basin A will connect to ST Inlet 7G in Harvest Parkway via an 18" pvc pipe, and Basin B will connect to ST Inlet 7B in Windrow Drive via a 12"pvc pipe. Madison Eng. provided the contributing areas and weighted C values for each basin as well as the pre and post-development time of concentrations and peak runoff rates. These values were used to size the Phase 7 pipes and detention ponds to accommodate flows from the multi-family lot. The calculations provided by Madison Eng. for both of these basins can be found in Appendix B. STORM SEWER FACILITIES DESIGN Storm sewer facilities were sized for the 25-yr storm using Manning's Equation. For each inlet,the contributing area,weighted C factor,and time of concentration were calculated.These values were input into Manning's Equation to check capacity and flow characteristics for inlets, storm drain pipes, and curb gutters. All curbs are designed to maintain 0.15' freeboard per C.O.B. Design Manual Section IV.C.5. For the purposes of this report, each pipe section was named to match the associated upstream structure. Pipe sizing calculations are included in Appendix C. RETENTION/DETENTION POND DESIGN All ponds have been sized according to City of Bozeman Design Standards. The proposed Detention Ponds are sized to limit discharge to pre-development rates for the 10-year storm event. Calculations used for sizing each pond can be found in Appendix D. Design pond capacities were calculated using volume surfaces in AutoCAD Civil 3D. Proposed Detention Pond #7E Detention Pond#7E is located in Open Space V,southeast of Broken Spur Drive.It receives runoff from Drainage Areas 713, 7C, 7F, 7E, and Basin B of the multi-family lot.Runoff in the westbound lane of Oak Street between Ryun Sun Way and FMR will be collected in the northern curb gutter of the street and flow toward the center of the subdivision to a low point in Oak Street at the Windrow Drive Intersection. From here, runoff will be directed north along Windrow Drive via gutter flow until reaching a series of curb inlets (713 and 7C) on either side of Windrow Drive. These inlets will direct the runoff via an 18" pvc pipe across Block 24 and into Detention Pond #7E. Runoff on Windrow Drive north of inlets 7B and 7C will flow north via curb gutters to the double gutter across the Windrow Drive/Broken Spur Drive intersection. From here it will be directed east along the south side of Broken Spur Drive to curb chase 717,which drains directly into Detention Pond#7E. The pre-development time to concentration for the pond was calculated to be 26 minutes and the pre-development runoff rate for the 10-yr storm event was calculated to be 1.83 cfs. In order to limit discharge from the detention pond to pre-development runoff rates the proposed outlet structure for the pond will have a 3.6" weir installed. The outlet pipe (Pipe 7E) was sized for the 25-yr storm event using the maximum time of concentration of the contributing drainage areas (13.6 minutes for DA#7C). The pipe will discharge into the adjacent stream channel, which is an unnamed tributary of Baxter Creek. The required pond volume was calculated to be 4,698 cubic feet. The provided pond volume is 5,334 cubic feet at a water depth of 1.5'. In the case of a storm exceeding the 10-yr design storm, runoff will overflow the pond banks and flow east across open space into the stream channel. Supporting calculations for the pond sizing can be found in Appendix D. In addition to Drainage Areas 713, 7C, 7E, and 7F, Basin B from the multi-family lot will also contribute to Detention Pond#7E.Based on the information provided by Madison Eng.,Basin B is a 1.35-acre portion of the multi-family lot with a weighted C value of 0.69. The calculated post development time of concentration for Basin B is 15 minutes and the peak runoff rate that was accounted for in sizing pipes 713, 7C, and 7E is 1.77 cfs. This basin area was also incorporated into sizing the required storage capacity of Detention Pond#7E. Proposed Detention Pond 97I Detention Pond #7I is located in the northern portion of Park 2, within Broken Spur Drive and receives runoff from Drainage Area 7I. The proposed park is currently graded with a "dome" shape, shedding water to the outside of the park into Broken Spur Drive. From here, runoff is captured in the gutter on the inside of Broken Spur Drive and channeled north to a low point adjacent to the intersection with the future portion of Windrow Drive. A curb chase (7I) will be installed at this low-point to direct water into the pond. The pre-development time to concentration was calculated to be 37 minutes and the pre-development runoff rate for the 10-yr storm was calculated to be 0.44 cfs. In order to limit discharge from the detention pond to pre-development runoff rates the proposed outlet structure for the pond will have a 0.9"weir installed. The outlet pipe(Pipe 7I)was sized for the 25-yr storm event using the maximum time of concentration of the contributing drainage area(15.8 minutes for DA#71), and will discharge the pond across Broken Spur Drive into the adjacent stream channel, which is an unnamed tributary of Baxter Creek. The required pond volume was calculated to be 1,382 cubic feet. The provided pond volume is 2,141 cubic feet at a water depth of 1.5'. In the case of a storm exceeding the 10-yr design storm, the pond was designed to be slightly oversized, and will contain an additional 9"of freeboard between the outlet structure top of weir and overflow rim elevation to accommodate larger flow events. Supporting calculations for the pond sizing can be found in Appendix D. Existing Detention Pond FMR The existing detention pond east of Flanders Mill Road was constructed to capture runoff from Flanders Mill Road north of Oak Street, and was conservatively sized to capture a portion of Phases 6 and 7 of the subdivision. For this phase of work a new series of manholes and pipes will be installed to drain the southwest portion of Broken Spur Drive,Harvest Parkway and a portion of Ryun Sun Way to the pond.Drainage Areas 7G, 7H, 6A, 613, and the multi-family lot Basin A will all contribute to the existing detention pond. Inlets 7G and 7H will be installed in Harvest Parkway, while inlets 6A, 613, and manhole 6C will be installed in the gravel subgrade of Ryun Sun Way and Forage Drive and tied into the proposed curb, gutter and pavement when Phase 6 is completed in the future. From ST MH 6C in(future) Forage Drive, runoff will be conveyed to the existing detention pond via a 21"pvc pipe. In addition to Drainage Areas 7G, 7H, 6A, and 613, Basin A from the multi-family lot will also contribute to the existing detention pond. Based on the information provided by Madison Eng., Basin A is a 7.62-acre portion of the multi-family lot with a weighted C value of 0.61. The calculated post development time of concentration for Basin A is 18 minutes and the peak runoff rate that was accounted for in sizing pipes 7G, 7H, 6A, and 6B is 7.93 cfs. Madison Eng. currently plans to hold the first 0.5" of rainfall to impervious areas of Basin A on the multi-family lot, and discharge excess flows via an 18" pipe to Inlet 7G in Harvest Parkway. In order to calculate the design capacity for the existing detention pond and account for the first 0.5" of rainfall to Basin A being contained on site, a detention scenario was designed for Basin A using the pre-development criteria provided by Madison Eng. The pre-development time of concentration of 31 minutes was used to calculate the rainfall intensity in a 10-year storm event and determine a pre-development runoff rate for the 10-year event. It was then assumed that runoff from Basin A would be held on the multi-family lot until the volume of 0.5" of rainfall to the impervious areas (8,154 cf) was retained. At this point (minute 28 of the storm event) runoff exceeding the 8,154 cf retention capacity would be released to Inlet 7G. This runoff volume was used in addition to the runoff volume calculated for the rest of the contributing area to the existing detention pond to calculate the required storage volume for the entire contributing area to the existing detention pond (including Basin A) The pre-development time to concentration for the pond was calculated to be 90 minutes (from Flanders Mill Road stormwater design report) and the pre-development runoff rate for the 10-yr storm was calculated to be 1.50 cfs. Since the contributing area to this existing pond was originally conservatively estimated to be larger with the Flanders Mill Road design report than it will be with this updated design report,the original pre-development runoff rate was also larger(1.78 cfs). The weir for the existing outlet structure was sized at this larger runoff rate, so the existing weir slot width of 3.5"will remain, although the newly calculated weir slot width is 2.9". This existing weir controls the pond discharge rate, so for this pond capacity calculation, the newly calculated pond contributing area and the existing 1.78 cfs pre-development runoff rate were used. The existing outlet pipe was re-evaluated for the 25-yr storm event with the new contributing area and has adequate capacity convey the pond runoff. The required pond capacity was calculated to be 6,142 cf, and the existing pond capacity is 14,502 cf at 1.5' water depth. Supporting calculations for the pond sizing can be found in Appendix D. The excess pond capacity and excess pipe capacities will provide room for changes to the multi-family lot design as it undergoes the site plan process, and may provide additional capacity for Phase 6 of the subdivision, if necessary. ADDITIONAL FLOW Drainage Area 7A Drainage area 7A captures runoff from Ryun Sun Way and the eastbound lane of Oak Street that were constructed with Phase 4 as well as the proposed Phase 7 eastbound lane of Oak Street. Runoff from these streets will be conveyed via curb and gutter to a low point in Oak Street adjacent to the Windrow Drive intersection.A curb chase will be installed at this point to channel water into the Phase 4 Park. The chase will discharge south of the Oak Street ROW into a meandering 4-wide swale which will allow sediment and debris to settle out of the runoff before entering the existing ponds within the park. The contributing area to this chase/swale system is 4.41 acres,and the chase and swale were both sized to handle the 25-year runoff rate of 3.74 cfs. Open Space V Open Space V runs between Phases 4 and 7 and is primarily composed of a 130-foot-wide stream channel and open space buffer. This open space will be landscaped with a meandering gravel trail and is generally sloped to drain into the stream channel. Open Space U Open Space U, labeled Drainage Area#EX1 on the attached drainage area map, is similar to Open Space V in that it will be primarily landscaped and contains a stream corridor. Since the original tributary stream flowing through the subdivision was relocated to OS V, the existing stream corridor in OS U now primarily drains groundwater from the surrounding open space,north across Harvest Parkway and beneath Flanders Mill Road via a recently relocated culvert. A 24" equivalent RCP culvert will be installed across Harvest Parkway from OS U to OS R with this phase of work in order to continue to allow groundwater from OS U to drain. Based on the contributing area to DA #EX 1 (OS U and potentially the NWE Transfer Station) the required capacity of this culvert for the 25-year storm event would be 2.53 cfs. As it is currently unknown if the development of the multi-family lot will discharge stormwater to OS U, the pipe was conservatively sized to match the downstream culvert crossing Flanders Mill Road with a flow rate of 15.38 cfs. Broken Spur Drive—North (Drainage Areas 6F1 and 6G) The northern portion of the outside lane of Broken Spur Drive(and a portion of Harvest Parkway) is designed to drain to a low point at the (future) Windrow Drive intersection at the northernmost point of Broken Spur Drive, and then drain north to future storm inlets in Windrow Drive. These storm inlets will be installed with Phase 6 of the subdivision. Until then, it is anticipated that the small amount of runoff from this area will drain north to the limit of paving at the Windrow intersection and dissipate onto the existing pit run gravel subgrade of future Windrow Drive. APPENDIX A DRAINAGE AREA MAP 8 a °I - -' •/ z m II F ( rn J I r---.� � _ n � � LL _ ox o U., aO o. . '�' m� �� 11 �om �" �; 9m .. �� o� o o� . �, � _•d?'o�: s ih, � _ �� �a�I ( �'i v, k 0 n � o Ni IA vie v a _ _ 15 nu N J - N n t EM 08 r a ; A n N r� r Awe/ I —I O r d- _ j o 0 �a n LLI ^ ^ N E— / L L, �h ���� n'c i �zw �.,�3+..� n��n `•' a r- o n ._� ♦ �Iil o� � � i + �,� o�n� vaia � � amm ,- _ Y x _o�— > n—x—"x.—, lY ({ • II \ \ OR i • a N o r � o 3h m3�1a � r J (n Jm � o bmna p o 3 M LL � 3 — A Vi y� y o _ O 0 W n¢m �n i r a \� Ak o m �i Z H 1 LL < /E W Q AdM S Nf1Al - �I i IAI m — ofl — _ — — —_ _ _ - — - — �o m N N II �� wM3 0� oo-: oo oumi_ o 'so N vao e—aal--aai—aa—am—aal---aa1-- amUnm p>U> V1N GN oT Z, _ VzM U my I/ rry r- Z Q ��aaII F ? OLL U m ?U w m arl 3 e o O m w m o w ~ a0 GG Q a Q O w x a o o �w w ¢ r}}r z a w N F O a s z a w N w O a s o 3 x w N 0 Z w w I Q w w m N W@ 0 � m w Q Cs a f N o o z o d o o v U).. ts r oti ov C cn Z TI c LLI o M Ci �gg J T T mOaf W APPENDIX B DRAINAGE AREA CALULATIONS DRAINAGE AREA# 7A1 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C"Area ROW-Tanzanite 0.76 5993 4570 ROW-Ryun Sun 0.71 28807 20525 ROW -Oak 0.68 33283 22633 Low-Med Density Residential 0.35 88507 30978 Total 156591 78705 A =Area(acres) 3.59 C=Weighted C Factor 0.50 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 0.1-CC1)D1/2/S1/3 -------- ;Storm S = Slope of Basin (%) 1.50 Return (yrs) Cf C= Rational Method Runoff Coefficient 0.35 2 to 10 1 Cf= Frequency Adjustment Factor 1.1 ;11 to 25 1.1 D= Length of Basin (ft) 160 :26 to 50 1.2 51 to 100 1.25 !----------------------------- Tc Overland Flow(minutes) 14.77 Tc Gutter Flow Tc= LN/60 V= (1.486/n)R213 S112 n = Mannings Coefficient 0.013 R = Hydraulic Radius A/P(ft) 0.13 (0.15' below top of curb) S = slope (ft/ft) 0.0075 L=length of gutter(ft) 784 V= mean velocity(ft/s) 2.60 Tc Gutter Flow(minutes) = 5.03 Tc Total= ltl 3. Calculate Flow(Rational Formula) Q =CIA C =Weighted C Factor 0.50 (calculated above) I =0.78 Tc-0.64(in/hr) 1.59 (25-yr storm) A= area(acres) 3.59 (calculated above) Q = REQUIRED GUTTER CAPACITY(cfs) 2.86 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR"'Sin n= Mannings Coefficient 0.013 A=Area(ft) 1.24 (0.15'below top of curb) P=Wetted perimeter(ft) 9.23 (0.15'below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S= slope(ft/ft) i_IU Q= PROVIDED GUTTER CAPACITY(cfs) 3.22 DRAINAGE AREA# 7A2 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C*Area ROW-Oak 0.68 35329 24024 Total 35329 24024 A =Area(acres) sm C=Weighted C Factor ads 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CCf)D'/2/Sl/3 Storm S= Slope of Basin (%) 3 :Return (yrs) Cf C= Rational Method Runoff Coefficient 0.68 ;2 to 10 1 Cf= Frequency Adjustment Factor 1.1 111 to 25 1.1 D = Length of Basin (ft) 44 :26 to 50 1.2 51 to 100 1.25 :----------------- Tc Overland Flow(minutes) 3.03 ------------ Tc Gutter Flow Tc = LN/60 V= (1.486/n)R213 SI12 n= Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S= slope(ft/ft) 0.0045 L= length of gutter(ft) 588 V= mean velocity(ft/s) 2.01 Tc Gutter Flow(minutes) = 4.87 Tc Total= Fie 3. Calculate Flow(Rational Formula) Q =CIA C =Weighted C Factor O.E)S (calculated above) I = 0.78 Tc'-"(in/hr) 2.86 (25-yr storm) A= area (acres) 0.81 (calculated above) Q=REQUIRED GUTTER CAPACITY(cfs) 1.67 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR213 S112 n= Mannings Coefficient 0.013 A =Area(ft) 1,24 (0.15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15'below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S =slope(ft/ft) Q =PROVIDED GUTTER CAPACITY (cfs) 2.49 DRAINAGE AREA# 713 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C `Area ROW-Oak 0.68 38310 26051 ROW-Windrow 0.71 26338 18766 Low-Med Density Residential 0.35 37009 12953 Total 101658 57770 A =Area(acres) 2.33 C=Weighted C Factor 0.57 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CC)D'/2/Sf/3 ;Storm S= Slope of Basin (%) 3.00 ;Return(yrs) Cf C = Rational Method Runoff Coefficient 0.71 12 to 10 1 C,= Frequency Adjustment Factor 1.1 ;11 to 25 1.1 D = Length of Basin (ft) 44 126 to 50 1.2 51 to 100 1.25 Tc Overland Flow(minutes) 2.74 Tc Gutter Flow Tc= L/V/60 V= (1.486/n)R2/3 Stn n= Mannings Coefficient 0.013 R.= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S= slope (ft/ft) 0.0092 L= length of gutter(ft) 1466 V= mean velocity(ft/s) 2.88 Tc Gutter Flow(minutes) = 8.49 Tc Total= 11.23 3. Calculate Flow(Rational Formula) O =CIA C =Weighted C Factor 0.57 (calculated above) = 0.78 Tc-0.64(in/hr) 2.28 (25-yr storm) A=area(acres) 2.33 (calculated above) Q= REQUIRED GUTTER CAPACITY(cfs) 3.02 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR2.a S"' n = Mannings Coefficient 0.013 A=Area (ft) 1.24 (0.15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S= slope (ft/ft) 0.0092 Q= PROVIDED GUTTER CAPACITY(cfs) 3.57 DRAINAGE AREA# 7C 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft`) C *Area ROW-Oak 0.68 23249 15809 ROW-Windrow 0.71 26082 18583 Low-Med Density Residential 0.35 95504 33427 Total 144836 67819 A =Area(acres) 3.32 C= Weighted C Factor 0.47 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CiC)D1/2/S1/3 Storm S= Slope of Basin (%) 2.00 Return (yrs) Cf C= Rational Method Runoff Coefficient 0.35 :2 to 10 1 Cf= Frequency Adjustment Factor 1.1 ;11 to 25 1.1 D= Length of Basin (ft) 81 126 to 50 1.2 51 to 100 1.25 •---------------------- Tc Overland Flow(minutes) 9.55 ' ----- Tc Gutter Flow Tc= LN/60 V= (1.486/n)R213 S1/2 n = Mannings Coefficient 0,013 R = Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S =slope(ft/ft) 0.0115 L=length of gutter(ft) 788 V= mean velocity(ft/s) 3.22 Tc Gutter Flow(minutes) = 4.08 Tc Total= 13.63 3. Calculate Flow(Rational Formula) Q =CIA C =Weighted C Factor 0.-1 (calculated above) =0.78 Tc-0.64(in/hr) 2.01 (25-yr storm) A = area(acres) 3.12 (calculated above) Q= REQUIRED GUTTER CAPACITY(cfs) 3.14 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR"3 Sv2 n= Mannings Coefficient 13 A=Area(ft) ro-oj�� 4 (0.15' below top of curb) P=Wetted perimeter(ft) 23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) i 3 (0.15' below top of curb) S= slope(ft/ft) 15 Q= PROVIDED GUTTER CAPACITY(cfs) DRAINAGE AREA# 7F 1. Calculate Area and Weighted C Factor Contributing Area C Area (It 2) C "Area ROW-Windrow 0.71 12485 8895 ROW-Broken Spur 0.78 5718 4432 Low-Med Density Residential 0.35 14442 5055 Total 32645 18382 A =Area(acres) 0.75 C= Weighted C Factor 0.56 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CC)D1/2/S'/3 Storm S = Slope of Basin (%) 2.00 :Return (yrs) Cf C= Rational Method Runoff Coefficient 0.45 :2 to 10 1 Cf= Frequency Adjustment Factor 1.1 :11 to 25 1.1 D= Length of Basin (ft) 17 26 to 50 1.2 51 to 100 1.25 Tc Overland Flow(minutes) 3.70 Tc Gutter Flow Tc = L/V/60 V= (1.486/n)R213 S1i2 n = Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S = slope(ft/ft) 0.0088 L= length of gutter(ft) 382 V= mean velocity(ft/s) 2.82 Tc Gutter Flow(minutes) = 2.26 Tc Total= 5.96 3. Calculate Flow(Rational Formula) Q =CIA C =Weighted C Factor 0.56 (calculated above) =0.78 Tc-0.64(in/hr) 3.42 (25-yr storm) A = area(acres) 0.75 (calculated above) Q = REQUIRED GUTTER CAPACITY(cfs) 1.44 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q= (1.486/n)ARzia S112 n = Mannings Coefficient 0.013 A =Area (ft) 1.24 (0.15'below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S= slope (ft/ft) 0.0088 Q = PROVIDED GUTTER CAPACITY(cfs) 3.50 DRAINAGE AREA# 7G 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C *Area ROW-Broken Spur 0.78 7180 5564 ROW-Harvest Parkway 0.73 10447 7595 Total 17627 13160 A =Area(acres) 0.40 C=Weighted C Factor 0.75 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CCf)D1/2/Sf/3 Storm S= Slope of Basin (%) 2.00 Return (yrs) Cf C= Rational Method Runoff Coefficient 0.50 ;2 to 10 1 Cf= Frequency Adjustment Factor 1.1 ill to 25 1.1 D= Length of Basin (ft) 12.6 -26 to 50 1.2 51 to 100 1.25 T -•----------------------------- c Overland Flow(minutes) 2.90 Tc Gutter Flow Tc= L/V/60 V= (1.486/n)R213 S112 n= Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S =slope (ft/ft) 0.0092 L=length of gutter(ft) 432 V= mean velocity(ft/s) 2.88 Tc Gutter Flow(minutes) = 2.50 Tc Total= 5.40 3. Calculate Flow(Rational Formula) O =CIA C =Weighted C Factor 0.75 (calculated above) =0.78 Tc-0.64(in/hr) 3.64 (25-yr storm) A=area (acres) 0.40 (calculated above) Q= REQUIRED GUTTER CAPACITY(cfs) 1.10 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR213 Sv2 n= Mannings Coefficient 0.013 A=Area (ft) 1.24 (0.15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S= slope (ft/ft) 0.0092 Q= PROVIDED GUTTER CAPACITY(cfs) 3.57 DRAINAGE AREA# 7H 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 2) C *Area ROW-Broken Spur 0.78 1061 822 ROW-Harvest Parkway 0.73 8742 6356 Total 9804 7178 A =Area(acres) 0.23 C= Weighted C Factor 0.73 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CC)D'/2/S13 ------------------------ ;Storm S= Slope of Basin (%) 2.00 :Return (yrs) Cf C= Rational Method Runoff Coefficient 0.50 ;2 to 10 1 Cf= Frequency Adjustment Factor 1.1 ;11 to 25 1.1 D = Length of Basin (ft) 12.3 '-26 to 50 1.2 51 to 100 1.25 1.---------------------------- Tc Overland Flow(minutes) 2.86 Tc Gutter Flow Tc= LN/60 V= (1.486/n)R211 S112 n = Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S =slope (ft/ft) 0.0067 L= length of gutter(ft) 222 V= mean velocity(ft/s) 2.46 Tc Gutter Flow(minutes) = 1.51 Tc Total= 4.37 3. Calculate Flow(Rational Formula) 0 =CIA C =Weighted C Factor 0.7 3 (calculated above) = 0.78 Tc-0.64(in/hr) 4.17 (25-yr storm) A=area(acres) 0.23 (calculated above) Q=REQUIRED GUTTER CAPACITY(cfs) 0.69 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR113 Sv2 n = Mannings Coefficient 0.013 A=Area (ft) 1.24 (0.15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15'below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15'below top of curb) S= slope (ft/ft) 0.0067 Q= PROVIDED GUTTER CAPACITY(cfs) 3.05 DRAINAGE AREA# 6A 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C*Area ROW-Ryun Sun 0.71 9500 6769 Low-Med Density Residential 0.35 35256 12340 Total 44756 19108 A =Area(acres) C= Weighted C Factor 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CCf)D1/2/Sli3 --- ----------------------- torm S = Slope of Basin (%) 2 i Return (yrs) Cf C= Rational Method Runoff Coefficient 0.50:2 to 10 1 Cf= Frequency Adjustment Factor 1.1111 to 25 1.1 D= Length of Basin (ft) 17'-26 to 50 1.2 151 to 100 1.25 ------------ Tc Overland Flow(minutes) 3.37 ----------------- Tc Gutter Flow Tc= LN/60 V= (1.486/n)R213 S112 n = Mannings Coefficient 0.013 R = Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S= slope (ft/ft) 0.0123 L = length of gutter(ft) 310 V= mean velocity(ft/s) 3.32 Tc Gutter Flow(minutes) = 1.55 Tc Total= 4.92 3. Calculate Flow(Rational Formula) Q = CIA C =Weighted C Factor : -1 (calculated above) = 0.78 Tc-0.sa(in/hr) (25-yr storm) A = area(acres) 1 (calculated above) Q = REQUIRED GUTTER CAPACITY(cfs) 1.70 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR"3 S'n n = Mannings Coefficient 0.013 A =Area(ft) 1.24 (0.15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S=slope (ft/ft) 0.0123 Q=PROVIDED GUTTER CAPACITY(cfs) 4.12 DRAINAGE AREA# 613 1. Calculate Area and Weighted C Factor Contributing Area C Area (f,2 1 C *Area ROW-Harvest Parkway 073 1790 1301 ROW-Ryun Sun 0.71 9891 7048 Low-Med Density Residential 0.35 35256 12340 Total 46938 20689 A =Area(acres) 1.08 C= Weighted C Factor 0.44 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CCf)D1/2/S'►3 ;Storm S = Slope of Basin (%) 2;Return (yrs) Cf C = Rational Method Runoff Coefficient 0.4612 to 10 1 Cf= Frequency Adjustment Factor 1.1;11 to 25 1.1 D= Length of Basin (ft) 12.726 to 50 1.2 ;51-- to-100------------- - -- Tc Overland Flow(minutes) 3.14 Tc Gutter Flow Tc= LN/60 V= (1.486/n)R213 S112 n = Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S= slope (ft/ft) 0.0130 L= length of gutter(ft) 388 V= mean velocity(ft/s) 3.41 Tc Gutter Flow(minutes) = 1.89 Tc Total= 5.04 3. Calculate Flow(Rational Formula) Q = CIA C =Weighted C Factor 0.44 (calculated above) =0.78 Tc-0.64(in/hr) 3.81 (25-yr storm) A= area(acres) 1.08 (calculated above) Q= REQUIRED GUTTER CAPACITY(cfs) 1.81 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q = (1.486/n)AR"' S"' n= Mannings Coefficient 0.013 A =Area (ft) '1.24 A15' below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S=slope(ft/ft) 0.0130 Q= PROVIDED GUTTER CAPACITY(cfs) 4.23 DRAINAGE AREA# 71 9. Calculate Area and Weighted C Factor Contributing Area C Area(ft2 C "Area ROW-Broken Spur 0.78 32586 25254 Park 0.35 77537 27138 Total 110123 52392 A =Area(acres) 2.53 C=Weighted C Factor 0.48 2. Calculate Tc(Time to Concentration) Tc Overland Flow Tc= 1.87 (1.1-CC)D'/2/Sl/3 Storm S=Slope of Basin (%) 1.98 :Return (yrs) Cf C = Rational Method Runoff Coefficient 0.20 ;2 to 10 1 Cf= Frequency Adjustment Factor 1.1 ;11 to 25 1.1 D= Length of Basin (ft) 96 26 to 50 1.2 51 to 100 1.25 Tc Overland Flow(minutes) 12.84 Tc Gutter Flow Tc= LN/60 V= (1.486/n)R213 S112 n= Mannings Coefficient 0.013 R= Hydraulic Radius A/P (ft) 0.13 (0.15' below top of curb) S =slope(ft/ft) 0.0095 L=length of gutter(ft) 519 V= mean velocity(ft/s) 2.93 Tc Gutter Flow(minutes) = 2.95 Tc Total= 1179 3. Calculate Flow(Rational Formula) Q=CIA C=Weighted C Factor 0.-tt (calculated above) I =0.78 Tc-0.64(in/hr) 1.83 (25-yr storm) A=area(acres) 2.53 (calculated above) Q= REQUIRED GUTTER CAPACITY(cfs) 2.20 (assuming no carry flow) PROVIDED GUTTER CAPACITY 1. Calculate Gutter Capacity @ 0.15'Below Top of Curb Q =(1.486/n)AR113 Sv2 n= Mannings Coefficient 0.013 A=Area (ft) 1.24 (0.15'below top of curb) P=Wetted perimeter(ft) 9.23 (0.15' below top of curb) R= Hydraulic Radius A/P(ft) 0.13 (0.15' below top of curb) S=slope(ft/ft) 0.0095 Q= PROVIDED GUTTER CAPACITY(cfs) 3.63 DRAINAGE AREA# EX1 Contributing Area C Area(ft 2) C * Area Park/Open Space, 0.2 132360 26472 Transfer Station 0.5 185715 92858 Total 318075 119330 C=Weighted C Factor 0.38 A =Area(acres) 7.30 Required Gutter/Pipe Capacity (25-yr Storm) Tc Overland Flow Tc= 1.87 (1.1-CCf)D"/S1/3 Storm C S = Slope of Basin (%) 1.29 Return f C =Rational Method Runoff Coefficient 0.35 2 to 10 1 Cf=Frequency Adjustment Factor 1.1 11 to 25 1.1 D =Length of Basin (ft) 1415 26 to 50 1.2 51 to 100 1.25 Tc Overland Flow(minutes)= 46.20 Q =CIA C =Weighted C Factor 0.38 (calculated above) I= 0.78 Tc-0 64(in/hr) 0.92 n =area(acres) 7.30 Qreyuired (Cfs)= 2.53 Provied Pipe Capacity Pipe Material Concrete Arch Pipe Mannings (n) 0.013 Size (24" equiv.) 18" x 28.5" Area (ft) 2.8 Hydraulic Radius (ft) 0.45 Slope (ft/ft) 0.0067 Q=(1.486/n)ARh2/3S1/2 Flow cfs 15.38 Drainage Area#DA EX1 Multi-Family Lot Provided by Madison Engineering, Inc. Flanders Mill Basin A 25 Year Storm Event Calculation of Required Volume for Storm Detention Pond (Reference: Bozeman Stormwater Master Plan-1982) Design Rainfall Freq. 25 year(see page III-5 of master plan) IDF coefficient a 0.78 IDF coefficient b IDF coefficient n 0.64 Pre-development Calculations Post-development Calculations C C Areas(fe):open space 331,735 0.20 Areas(fe): Landscape 136,028 0.20 0.35 Pavement/SW 116,153 0.90 0.50 Roof 79,554 0.90 Total: 331,735 Total: 331,735 total area: 7.62 acres total area: 7.62 acres composite C: 0.20 composite C: 0.61 Overland t. Overland t. average slope: 1.75 percent average slope: 1.5 percent travel distance: 500 feet travel distance: 500 feet t�: 31 minutes t�: 18 minutes Channel t. Channel t. channel t„ minutes channel t.; minutes Total t.: 31 minutes Total t.: 18 minutes intensity at tc(fig 23): 1.18 in/hr intensity at t (fig 23): 1.70 in/hr pre-devel peak runoff: 1.80 cfs post-devel peak runoff: 7.93 cfs Basin A-Stormwater Calc Provided by Madison Engineering, Inc. Multi-Family Lot Flanders Mill Basin B-SE Corner 25 Year Storm Event Calculation of Required Volume for Storm Detention Pond (Reference: Bozeman Stormwater Master Plan-1982) Design Rainfall Freq. 25 year(see page III-5 of master plan) IDF coefficient a 0.78 IDF coefficient b IDF coefficient n 0.64 Pre-development Calculations Post-development Calculations C C Areas(fe):open space 58,680 0.20 Areas(fe): Landscape 17,425 0.20 0.35 Pavement/SW 35,988 0.90 0.50 Roof 5,267 0.90 Total: 58,680 Total: .58.680 total area: 1.35 acres total area: 1.35 acres composite C: 0.20 composite C: 0.69 Overland t. Overland t. average slope: 1.75 percent average slope: 1.5 percent travel distance: 500 feet travel distance: 500 feet tc: 31 minutes t�: 15 minutes Channel t. Channel t. channel t�: minutes channel t.: minutes Total t.: 31 minutes Total t�: 15 minutes intensity at t (fig 23): 1.18 in/hr intensity at t (fig 23): 1.90 in/hr pre-devel peak runoff: 0.32 cfs post-devel peak runoff: 1.77 cfs Basin B-Stormwater Calc APPENDIX C STORM SEWER FACILITIES CALCULATIONS CHASE 7A 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (f,2) C *Area ROW-Tanzanite 0.76 5993 4570 ROW-Ryun Sun 0.71 28807 20525 ROW-Oak 0.68 33283 22633 Low-Med Density Residential 0.35 88507 30978 ROW-Oak 0.68 35329 24024 Total 191920 102729 A =Area(acres) 4.41 C=Weighted C Factor 0.54 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i= 0.78x 0.64(25-yr Storm, Fig. 1-3, COB Design Standards) x= storm duration (hrs) 0.33 (DA#7A1) i=rainfall intensity(in.1hr.) 1.59 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0.54 (calculated above) i= rainfall intensity(in./hr.) 1.59 (calculated above) A=Area(acres) 4.41 (calculated above) Q=25-yr Pipe Flow Rate(cfs) 3.74 Stormwater Chase 7A Sizing Determine slope of stormwater chase slope (ft/ft) 0.015 Calculate chase capacity chase depth (feet) 0.50 Chase width (feet) 1.50 Mannings#, n (for concrete) 0.013 X-sect. area (ft) 0.750 Perimeter(ft) 2.500 Hydr. Radius, R(ft) 0.3000 slope(ft/ft) 0.015 iQf.11 WS) 4.71 PIPE VA 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 7A Location: SWALE 7A CULVERT 0 INPUT D= 15 inches _____ d= 14.07 inches Mannings Formula d ► n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213SI12 S= 0.005 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh213sii2 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values z Wetted Hydraulic Area,ft Perimeter,ft Radius,ft velocity ft/s flow,cfs PVC 0.013 1.20 3.30 0.36 4.11 4.91 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 PIPE # 713 (ST Inlet 713 Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C *Area ROW-Oak 0 6.1 38310 26051 ROW-Windrow O.71 26838 18766 Low-Med Density Residential a 3r i-009 12953 Total 1016.58 Fi 7 770 A =Area(acres) 2.33 C=Weighted C Factor 0.57 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i = 0.78x 0.64(25-yr Storm, Fig. 1-3, COB Design Standards) x= storm duration (hrs) 0.19 I=rainfall intensity(in.1hr.) 2.28 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0.57 (calculated above) i = rainfall intensity(in./hr.) 2.28 (calculated above) A=Area(acres) 2.33 (calculated above) Q(25-yr Pipe Flow Rate) (cfs)= 3.02 Q 25- r Pipe Flow Rate(cfs)) from Multi-Family Basin B = 1.77 Q(total) (cfs)= 4.79 PIPE # 7B (ST Inlet 7B Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 4B Location: ST Inlet 4B Outlet Pipe � e INPUT D= 18 inches________ d= 16.88 inches Mannings Formula d7 n= 0.013 mannings p 0= 57.7 degrees Q=(1.486/n)ARh213SI12 S= 0.005 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh2i3S112 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity ft/s flow,cfs Perimeter,ft Radius,ft PVC 0.013 1.72 3.96 0.44 1 4.64 7.99 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 PIPE # 7C (ST Inlet 7C Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 1) C*Area ROW-Oak 0.68 38310 26051 ROW-Windrow 0.71 26338 18766 Low-Med Density Residential 0.35 37009 12953 ROW-Oak 0.68 23249 15809 ROW-Windrow 0.71 26082 18583 Low-Med Density Residential 0.35 95504 33427 Total 246493 125590 A =Area(acres) 5.66 C= Weighted C Factor 0.51 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i= 0.78z o.s4(25-yr Storm, Fig. 1-3, COB Design Standards) x = storm duration (hrs) 0.23 (DA#7C) i=rainfall intensity(in.1hr.) 2.01 3. Calculate 25-yr Pond Outflow Rate Q = CiA C = Rational Method Runoff Coefficient 0.51 (calculated above) i= rainfall intensity(in./hr.) 2.01 (calculated above) A =Area (acres) 5.66 (calculated above) Q 25-yr Pipe Flow Rate(cfs)= 5.81 Q(25- r Pipe Flow Rate(cfs)) from Multi-Family Basin B = 1.77 Q(total) (cfs)= 7.58 PIPE # 7C (ST Inlet 7C Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 7C Location: ST Inlet 7C Outlet Pipe � e INPUT D= 18 inches d= 16.88 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213S112 S= 0.005 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh213S'i2 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity fUs flow,cfs Perimeter,ft Radius,ft PVC 0.013 1.72 3.96 0.44 4.64 7.99 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 CHASE 7F 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 2) C *Area ROW-Windrow 0.71 12485 8895 ROW-Broken Spur 0.78 5718 4432 Low-Med Density Residential 0.35 14442 5055 Total 32645 18382 A =Area(acres) 0.75 C= Weighted C Factor 0.56 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i = 0.78x o.s4 (25-yr Storm, Fig. 1-3, COB Design Standards) x = storm duration (hrs) 0.10 (DA#7F) i=rainfall intensity(in.1hr.) 3.42 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0.56 (calculated above) i= rainfall intensity(in./hr.) 3.42 (calculated above) A =Area(acres) 0.75 (calculated above) Q=25-yr Pipe Flow Rate(cfs) 1.44 Stormwater Chase 7F Sizing Determine slope of stormwater chase slope (ft/ft) 0.015 Calculate chase capacity chase depth (feet) 0.50 Chase width (feet) 1.00 Mannings#, n (for concrete) 0.013 X-sect. area(ft) 0.500 Perimeter(ft) 2.000 Hydr. Radius, R(ft) 0.2500 slope(ft/ft) 0.015 Qf„u(cfs) 2.78 PIPE # 7E (ST OUTLET 7E Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft Z) C*Area ROW-Oak -0.68 38310 2t5C1.,1 ROW-Windrow 0.7,1 25338 16766 Low-Med Density Residential 0.-`5 37009 12953 ROW-Oak C.68 232449 16609 ROW-Windrow 0.71 26082 18583 Low-Med Density Residential 0.35 95504 33427 ROW-Windrow 0.71 12485 8895 ROW-Broken Spur ,+ 7 8 5718 4432 Low-Med Density Residential 0 35 14442 5055 Low-Med Density Residential 0.35 9767 3418 OS 0.20 16207 3241 Total 305112 150631 A =Area(acres) 7.00 C= Weighted C Factor 0.49 2. Calculate Rainfall Intensity(Duration =Max Tc from Contributing Drainage Areas) i= 0.78x o.64(25-yr Storm, Fig. 1-3, COB Design Standards) x= storm duration (hrs) 0.23 (DA VC) I=rainfall intensity(in.1hr.) 2.01 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0491(calculated above) i= rainfall intensity(in./hr.) 2.01 (calculated above) A=Area(acres) 70'0'.(calculated above) Q 25-yr Pipe Flow Rate(cfs)= 6.96 Q(25- r Pipe Flow Rate cfs from Multi-Family Basin B= 1.77 Q(total) (cfs)= 8.73 PIPE # 7E (ST OUTLET 7E Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 7E Location: ST OUTLET 7E Outlet Pipe � e INPUT D= 18 inches d= 16.88 inches Mannings Formula d 4 n= 0.013 mannings D 0= 57.7 degrees 0=(1.486/n)ARh213S112 S= 0.0064 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh2i3S'12 S=slope of channel Q=V x A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity fUs flow,cfs Perimeter,ft Radius,ft PVC 0.013 1.72 3.96 0.44 5.25 9.04 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 PIPE # 7G (ST INLET 7G Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 2) C "Area ROW - Broken Spur 0.78 7180 5564 ROW-Harvest Parkway 0.73 10447 7595 Total 17627 13160 A =Area(acres) 0.40 C=Weighted C Factor 0.75 2. Calculate Rainfall Intensity(Duration =Max Tc from Contributing Drainage Areas) i=0.78x o.64 (25-yr Storm, Fig. 1-3, COB Design Standards) x =storm duration (hrs) 0.30 (DA#MF 2) i=rainfall intensity(in.1hr.) 1.69 3. Calculate 25-yr Pond Outflow Rate Q=CiA C= Rational Method Runoff Coefficient 0.75 (calculated above) i= rainfall intensity(in./hr.) 1.69 (calculated above) A =Area(acres) 0.40 (calculated above) Q 25-yr Pipe Flow Rate(cfs)= 0.51 Q (25-yr Pipe Flow Rate(cfs)) from Multi-Family Basin A = 7.93 Q(total) (cfs)= 8.44 PIPE # 7G (ST INLET 7G Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 7G Location: ST INLET 7G Outlet Pipe - - e \� INPUT D= 18 inches d= 16.88 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213S112 IF S= 0.01 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh213S1i2 S=slope of channel Q=V x A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity ft/s flow,cfs Perimeter,ft Radius,ft PVC 0.013 1.72 3.96 0.44 1 6.56 11.30 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CN1P 0.025 ADS N12 0.012 HCMP 0.023 Colic 0.013 PIPE # 7H (ST INLET 7H Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area(ft 2) C *Area ROW-Broken Spur 0.78 7180 5564 ROW-Harvest Parkway 0.73 10447 7595 ROW-Broken Spur 0.78 1061 822 ROW-Harvest Parkway 0.73 8742 6356 Total 27430 20338 A =Area(acres) 0.63 C= Weighted C Factor 0.74 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i = 0.78x o.s4(25-yr Storm, Fig. 1-3, COB Design Standards) x=storm duration (hrs) 0.30 (DA#7G) I=rainfall intensity(in.1hr.) 1.69 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0.74 (calculated above) i = rainfall intensity(in./hr.) 1.69 (calculated above) A=Area (acres) 0.63 (calculated above) Q 25-yr Pipe Flow Rate(cfs)= 0.79 Q(25-yr Pipe Flow Rate(cfs))from Multi-Family Basin A = 7.93 Q(total) (cfs)= 8.72 PIPE # 7H (ST INLET 7H Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 7H Location: ST INLET 7H Outlet Pipe 00 INPUT D= 18 inches d= 16.88 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh2i3S'n S= 0.0119 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh2/3S'i2 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values z Wetted Hydraulic Area,ft Perimeter,ft Radius,ft velocity ft/s flow,cfs PVC 0.013 1.72 3.96 0.44 7.16 12.33 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 PIPE # 6A (ST Inlet 6A Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (It 2) C "Area ROW-Ryun Sun (6A) 0.71 9500 6769 Low-Med Density Residential (6A) 0.35 35256 12340 ROW-Broken Spur (7G) 0.78 7180 5564 ROW-Harvest Parkway 7G 0.73 10447 7595 ROW - Broken Spur (7H) 0.78 1061 822 ROW-Harvest Parkway (7H) 0.73 8742 6356 Total 72186 39446 A =Area(acres) 1.66 C= Weighted C Factor 0.55 2. Calculate Rainfall Intensity(Duration=Max Tc from Contributing Drainage Areas) i= 0.78x o.s4 (25-yr Storm, Fig. 1-3, COB Design Standards) x= storm duration (hrs) 0.09 i=rainfall intensity(in.1hr.) 3.64 3. Calculate 25-yr Pond Outflow Rate Q =CiA C = Rational Method Runoff Coefficient 0.55 (calculated above) i = rainfall intensity(in./hr.) 3.64 (calculated above) A =Area(acres) 1.66 (calculated above) Q 25-yr Pipe Flow Rate(cfs)= 3.30 Q(25-yr Pipe Flow Rate(cfs)) from Multi-Family Basin A = 7.93 Q(total) (cfs)= 11.23 PIPE # 6A (ST Inlet 6A Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 6A Location: ST Inlet 6A Outlet Pipe INPUT D= 21 inches d= 19.70 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213S112 S= 0.0111 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh2i3S1n S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values z Wetted Hydraulic Area,ft Perimeter,ft Radius,ft velocity ft/s flow,cfs PVC 0.013 2.34 4.62 0.51 7.66 1T:96 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 PIPE # 613 (ST Inlet 613 Outlet Pipe) 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 2) C *Area ROW-Harvest Parkway (613) 0.73 1790 1301 ROW- Ryun Sun (6B) 0.71 9891 7048 Low-Med Density Residential 613 0.35 35256 12340 ROW-Ryun Sun (6A) 0.71 9500 6769 Low-Med Density Residential (6A) 0.35 35256 12340 ROW-Broken Spur (7G) 0.78 7180 5564 ROW-Harvest Parkway (7G) 0.73 10447 7595 ROW-Broken Spur (71-1) 0.78 1061 822 ROW-Harvest Parkway (7H) 0.73 8742 6356 Total 119124 60135 A =Area(acres) 2.73 C= Weighted C Factor 0.50 2. Calculate Rainfall Intensity(Duration =Max Tc from Contributing Drainage Areas) i = 0.78x o.64 (25-yr Storm, Fig. 1-3, COB Design Standards) x = storm duration (hrs) 0.09 i=rainfall intensity(in.1hr.) 3.64 3. Calculate 25-yr Pond Outflow Rate Q = CiA C = Rational Method Runoff Coefficient 0.50 (calculated above) i = rainfall intensity(in./hr.) 3.64 (calculated above) A=Area(acres) 2.73 (calculated above) Q 25-yr Pipe Flow Rate(cfs)= 5.03 Q 25- r Pipe Flow Rate(cfs)) from Multi-Family Basin A = 7.93 Q(total)(cfs)= 12.96 PIPE # 6B (ST Inlet 6B Outlet Pipe) 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 6B Location: ST Inlet 6B Outlet Pipe f0 INPUT D= 21 inches d= 19.70 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213S112 S= 0.0099 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh213SI12 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity ft/s flow,cfs Perimeter,ft Radius,ft PVC 0.013 2.34 4.62 0.51 1 7.24 16.96 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Conc 0.013 CHASE 71 & PIPE #71 25-YR OUTFLOW RATE REQUIRED CAPACITY 1. Calculate Area and Weighted C Factor Contributing Area C Area (ft 2) C"Area ROW-Broken Spur 0.78 32586 25254 Park 0.35 77537 27138 Total 110123 52392 A =Area(acres) 2.53 C= Weighted C Factor 0.48 2. Calculate Rainfall Intensity(Duration =Max Tc from Contributing Drainage Areas) i=0.78z o.s4(25-yr Storm, Fig. 1-3, COB Design Standards) x =storm duration (hrs) 0.26 (DA#71) i=rainfall intensity(in.1hr.) 1.83 3. Calculate 25-yr Pond Outflow Rate Q = CiA C= Rational Method Runoff Coefficient 0.48 (calculated above) i= rainfall intensity(in./hr.) 1.83 (calculated above) A=Area(acres) 2.53 (calculated above) Q=25-yr Pipe Flow Rate(cfs) 2.20 Stormwater Chase 71 Sizing Determine slope of stormwater chase slope (ft/ft) 0.015 Calculate chase capacity chase depth (feet) 0.50 Chase width (feet) 1.00 Mannings#, n (for concrete) 0.013 X-sect. area(ft) 0.500 Perimeter(ft) 2.000 Hydr. Radius, R (ft) 0.2500 slope (ft/ft) 0.015 iQf.11(cfS) 2.78 PIPE #71 25-YR OUTFLOW RATE MANNING'S EQUATION FOR PIPE FLOW (PROVIDED CAPACITY) Pipe: 71 Location: OUTLET STRUCTURE 71 Outlet Pipe 0 / INPUT D= 15 inches____ d= 14.07 inches Mannings Formula d n= 0.013 mannings D 0= 57.7 degrees Q=(1.486/n)ARh213S112 S= 0.005 slope in/in R=A/P A=cross sectional area P=wetted perimeter V=(1.49/n)Rh2i3st i2 S=slope of channel Q=V X A n=Manning's roughness coefficient Solution to Mannings Equation Manning's n-values Area,ft2 Wetted Hydraulic velocity ft/s flow,cfs Perimeter,ft Radius,ft PVC 0.013 1.20 3.30 0.36 1 4.11 4.91 PE(<9"dia) 0.015 PE(>12"dia) 0.02 PE(9-12"dia) 0.017 CMP 0.025 ADS N12 0.012 HCMP 0.023 Cone 0.013 PIPE # E1 (Culvert Draining DA# EX1) 25-YR OUTFLOW RATE Contributing Area C Area(fe) C * Area Park/Open Space (EX 1) 0.20 132360 26472 Transfer Station (EX 1) 0.5 185715 92858 Total 318075 119330 C =Weighted C Factor 0.38 A=Area (acres) 7.30 2. Calculate Rainfall Intensity (Duration =Max Tc from Contributing Drainage Areas) i = 0.78x 0"' (25-yr Storm, Fig. 1-3, COB Design Standards) x = storm duration (hrs) 0.77 (DA EX1) i = rainfall intensity(in./hr.) 0.92 3. Calculate 25-yr Pipe Flow Rate Q = CiA C = Rational Method Runoff Coefficient 0.38 (calculated above) i = rainfall intensity (in./hr.) 0.92 (calculated above) A = Area (acres) 7.30 (calculated above) Q = 25-yr Pipe Flow Rate (cfs) 2.53 PROVIDED PIPE CAPACITY Pipe Material Concrete Arch Pipe Mannings (n) 0.013 Size (24" equiv.) 18" x 28.5" Area (ft) 2.8 Hydraulic Radius (ft) 0.45 Slope (ft/ft) 0.0067 Q=(1.486/n)ARh213SI12 Flow cfs 15.38 Drainage Area#PIPE E1 APPENDIX D POND SIZING CALCULATIONS DETENTION POND # 7E REQUIRED VOLUME 1. Calculate Area and Weighted C Factor(Post-Development) Contributing Area C Area ft2) C *Area ROW-Oak (7B) 0.68 38310 26051 ROW-Windrow (7B) 0.71 26338 18766 Low-Med Density Residential 713 0.35 37009 12953 ROW-Oak (7C) 0.68 23249 15809 ROW-Windrow (7C) 0.71 26082 18583 Low-Med Density Residential (7C) 0.35 95504 33427 ROW-Windrow (7F) 0.71 12485 8895 ROW-Broken Spur (7F) 0.78 5718 4432 Low-Med Density Residential (7F) 0.35 14442 5055 Low-Med Density Residential (7E) 0.35 9767 3418 OS 7E) 0.20 16207 3241 Dense Residential(Basin B) 0.69 58680 40489 Total 363792 191121 --------------------------------- A =Area(acres) 8.35 Storm C=Weighted C Factor 0.53 Return (yrs) Cf 12 to 10 1 2. Calculate T°(Pre-Development) ;11 to 25 1.1 Tc Overland Flow 26 to 50 1.2 Tc= 1.87 (1.1-CCf)D'/2/S1i3 :51 to 100 1.25 .------------------------------- S= Slope of Basin (%) 1.30 C = Rational Method Runoff Coefficient 0.2 Cf= Frequency Adjustment Factor 1 D= Length of Basin (ft) 288 Tc(Pre-Development)(minutes) 26 3. Calculate Rainfall Intensity(Duration=Pre-Development Tc) i = 0.64-o.65 (10-yr Storm, Fig. 1-3, COB Design Standards) x=storm duration (hrs) 0.44 (Tc Pre-Development) i=rainfall intensity(in.1hr.) 1.10 4. Calculate Runoff Rate(Pre-Development) Q= CiA C = Rational Method Runoff Coefficient 0.2 (open land) i= rainfall intensity(in./hr.) 1.10 (calculated above) A=Area (acres) 8.35 (calculated above) Q=Runoff Rate (Pre-Development) (cfs) 1.83 5. Calculate Required Pond Volume Total Area (acres) = 8.35 acres Weighted C = 0.53 Discharge Rate (cfs) = 1.83 cfs (Equal to Pre-Development Runoff Rate) Duration(min) Duratio Intensity Q.� (cfs) Runoff Release Required 3 n(hrs) (in/hr) Volume Volume Storage(ft) ) 18 0.30 1.40 6.14 6633 1979 4653 19 0.32 1.35 5.93 6759 2089 4670 20 0.33 1.31 5.73 6882 2199 4683 21 0.35 1.27 5.56 7000 2309 4691 22 0.37 1.23 5.39 7115 2419 4696 23 0.38 1.19 5.24 7227 2529 4698 24 0.40 1.16 5.09 7335 2639 4696 25 0.42 1.13 4.96 7441 2749 4692 26 0.43 1.10 4.84 7544 2859 4685 27 0.45 1.08 4.72 7644 2969 4675 PROVIDED VOLUME (ft') 5334 OUTLET STRUCTURE SLOT Q=CLH l Q = Discharge(cfs) 1.83 C = Weir Coefficient 3.33 (per COB Design Standards) H = Head (ft) 1.5 L= Horizontal Length (ft) 0.30 L=Slot Width(inches) 3.6 Multi-Family Lot (Basin A) - Flow to FMR Det. Pond **Contributing Area, C Factor,and Time of Concentration provided by Madison Engineering REQUIRED VOLUME 1. Calculate Area and Weighted C Factor(Post-Development) Contributing Area C Area(ft 2) C *Area Dense Residential Landscape 0.20 136028 27206 Pavement/SW 0.90 116153 104538 Roof 0.90 79554 71599 Total 331735 203342 ------------------------------- A =Area(acres) 7.62 Storm C=Weighted C Factor 0.61 Return (yrs) Cf ;2 to 10 1 2. Calculate T, (Pre-Development) 11 to 25 1.1 Tc Overland Flow 126 to 50 1.2 Tc= 1.87 (1.1-CCf)D'/2/S1i3 :51 to 100 1.25 :-------------------------------- S= Slope of Basin (%) 1.75 C = Rational Method Runoff Coefficient 0.2 Cf= Frequency Adjustment Factor 1 D= Length of Basin (ft) 500 Tc(Pre-Development) (minutes) 31 3. Calculate Rainfall Intensity(Duration=Pre-Development Tc) i = 0.64x o.s5(10-yr Storm, Fig. 1-3, COB Design Standards) x=storm duration (hrs) 0.52 (Tc Pre-Development) i=rainfall intensity(in.1hr.) 0.98 4. Calculate Runoff Rate(Pre-Development) Q = CiA C = Rational Method Runoff Coefficient 0.2 (open land) i = rainfall intensity(in./hr.) 0.98 (calculated above) A =Area (acres) 7.62 (calculated above) Q=Runoff Rate (Pre-Development) (cfs) 1.49 5. Calculate Required Pond Volume Total Area (acres) = 7.62 acres Weighted C = 0.61 Discharge Rate (cfs) = 1.49 cfs (Equal to Pre-Development Runoff Rate) Retained Volume (0.5" Impervious) = 8154 cf Time of Release to ST Inlet 7G = 28 min Runoff Release Duration Intensity Volume Duration(min) Q;� (cfs) Volume(to (hrs) (in/hr) (within ST Inlet 7G) Basin A) 1 0.02 9.16 42.77 2566 0 2 0.03 5.84 27.26 3271 0 3 0.05 4.49 20.94 3769 0 4 0.07 3.72 17.37 4169 0 5 0.08 3.22 15.02 4507 0 6 0.10 2.86 13.35 4804 0 7 0.12 2.59 12.07 5071 0 8 0.13 2.37 11.07 5313 0 9 0.15 2.20 10.25 5537 0 10 0.17 2.05 9.57 5745 0 11 0.18 1.93 9.00 5940 0 12 0.20 1.82 8.50 6123 0 13 0.22 1.73 8.07 6297 0 14 0.23 1.65 7.69 6463 0 15 0.25 1.58 7.36 6621 0 16 0.27 1.51 7.05 6772 0 17 0.28 1.45 6.78 6917 0 18 0.30 1.40 6.53 7057 0 19 0.32 1.35 6.31 7192 0 20 0.33 1.31 6.10 7322 0 21 0.35 1.27 5.91 7448 0 22 0.37 1.23 5.74 7570 0 23 0.38 1.19 5.57 7689 0 24 0.40 1.16 5.42 7804 0 25 0.42 1.13 5.28 7917 0 26 0.43 1.10 5.14 8026 0 27 0.45 1.08 5.02 8133 0 28 0.47 1.05 4.90 8237 83 29 0.48 1.03 4.79 8339 184 30 0.50 1.00 4.69 8438 284 31 0.52 0.98 4.59 8536 381 32 0.53 0.96 4.50 8631 477 33 0.55 0.94 4.41 8725 570 34 0.57 0.93 4.32 8816 662 35 0.58 0.91 4.24 8906 752 36 0.60 0.89 4.16 8994 840 37 0.62 0.88 4.09 9081 927 38 0.63 0.86 4.02 9166 1012 39 0.65 0.85 3.95 9250 1096 40 0.67 0.83 3.89 9332 1178 41 0.68 0.82 3.83 9413 1259 42 0.70 0.81 3.77 9493 1339 43 0.72 0.79 3.71 9572 1417 44 0.73 0.78 3.65 9649 1494 45 0.75 0.77 3.60 9725 1571 46 0.77 0.76 3.55 9800 1646 47 0.78 0.75 3.50 9874 1720 48 0.80 0.74 3.45 9947 1793 49 0.82 0.73 3.41 10019 1865 50 0.83 0.72 3.36 10090 1936 51 0.85 0.71 3.32 10161 2006 52 0.87 0.70 3.28 10230 2075 53 0.88 0.69 3.24 10298 2144 54 0.90 0.69 3.20 10366 2211 55 0.92 0.68 3.16 10433 2278 56 0.93 0.67 3.12 10499 2344 57 0.95 0.66 3.09 10564 2409 58 0.97 0.65 3.05 10628 2474 59 0.98 0.65 3.02 10692 2538 60 1.00 0.64 2.99 10755 2601 61 1.02 0.63 2.96 10818 2663 62 1.03 0.63 2.92 10879 2725 63 1.05 0.62 2.89 10941 2786 64 1.07 0.61 2.86 11001 2847 65 1.08 0.61 2.84 11061 2906 66 1.10 0.60 2.81 11120 2966 67 1.12 0.60 2.78 11179 3024 68 1.13 0.59 2.75 11237 3082 69 1.15 0.58 2.73 11294 3140 70 1.17 0.58 2.70 11351 3197 71 1.18 0.57 2.68 11408 3254 72 1.20 0.57 2.65 11464 3310 73 1.22 0.56 2.63 11519 3365 74 1.23 0.56 2.61 11574 3420 75 1.25 0.55 2.58 11629 3474 76 1.27 0.55 2.56 11683 3529 77 1.28 0.54 2.54 11737 3582 78 1.30 0.54 2.52 11790 3635 79 1.32 0.54 2.50 11842 3688 80 1.33 0.53 2.48 11895 3740 81 1.35 0.53 2.46 11946 3792 82 1.37 0.52 2.44 11998 3843 83 1.38 0.52 2.42 12049 3894 84 1.40 0.51 2.40 12099 3945 85 1.42 0.51 2.38 12150 3995 86 1.43 0.51 2.36 12200 4045 87 1.45 0.50 2.35 12249 4095 88 1.47 0.50 2.33 12298 4144 89 1.48 0.50 2.31 12347 4192 90 1 1.501 0.491 2.301 123951 4241 EXISTING DETENTION POND (FMR) REQUIRED VOLUME 1. Calculate Area and Weighted C Factor(Post-Development) Contributing Area C Area(ft 2) C *Area ROW-Ryun Sun (6A) 0.71 9500 6769 Low-Med Density Residential (6A) 0.35 35256 12340 ROW- Harvest Parkway (6B) 0.73 1790 1301 ROW- Ryun Sun (6B) 0.71 9891 7048 Low-Med Density Residential 66 0.35 35256 12340 Dense Residential Basin A 0.61 331735 202358 ROW-Broken Spur (7G) 0.78 7180 5600 ROW-Harvest Parkway (7G) 0.73 10447 7626 ROW- Broken Spur (7H) 0.78 1061 828 ROW- Harvest Parkway (7H) 0.73 8742 6382 Flanders Mill Road ROW (F1) 0.76 59011 44996 Flanders Mill Road ROW (F2) 0.70 59025 41318 Harvest Pkwy ROW (F2) 0.73 11137 8097 Forage Drive ROW (F2) 0.71 10550 7517 Oak Street ROW (F1+F2) 0 Hardscape 0.95 8326 7910 Landscape 0.20 2823 565 Open Space/Park (F3) 0.20 39438 7888 Low-Med Density Residential (F3) 0.35 23177 8112 Total 664346 388992 Including Multi-Family Basin A A =Area(acres) 15.25 Storm C=Weighted C Factor 0.59 ; Return (yrs) Cf ;2 to 10 1 Excluding Multi-Family Basin A 11 to 25 1.1 A =Area(acres) 7.64 126 to 50 1.2 C=Weighted C Factor 0.56 151 to 100 1.25 - - - ----------------- 2. Calculate Tc (Pre-Development) Tc Overland Flow Tc= 1.87 (1.1-CCf)D'/2/S'/3 S= Slope of Basin (%) 1.19 C = Rational Method Runoff Coefficient 0.2 Cf= Frequency Adjustment Factor 1 D= Length of Basin (ft) 3189 Tc(Pre-Development) (minutes) 90 3. Calculate Rainfall Intensity(Duration =Pre-Development Tc) i =0.64x o.s5 (10-yr Storm, Fig. 1-3, COB Design Standards) x =storm duration (hrs) 1.49 (Tc Pre-Development) i=rainfall intensity(in.1hr.) 0.49 4. Calculate Runoff Rate(Pre-Development) Q = CiA C= Rational Method Runoff Coefficient 0.2 (open land) i = rainfall intensity(in./hr.) 0.49 (calculated above) A=Area (acres) 15.25 (calculated above) Q=Runoff Rate (Pre-Development) (cfs) 1.50 Runoff Rate (Pre-Development) (cfs) FMR Design 1.78 5. Calculate Required Pond Volume Total Area (acres) = 15.25 acres Weighted C = 0.59 Discharge Rate(cfs) = 1.78 cfs (Equal to Pre-Development Runoff Rate) Required Pond Volume(W) = 6142 (See attached table) Provided Pond Volume(ft9) F 14502 OUTLET STRUCTURE SLOT Q=CLH 312 Q = Discharge(cfs) 1.50 C=Weir Coefficient 3.33 (per COB Design Standards) H= Head (ft) 1.5 L= Horizontal Length (ft) 0.25 L =Slot Width(inches) Current Design 2.9 Ex. Slot Width (inches) FMR Design 3.5 Storage Table Runoff Runoff Duration Intensity Volume Release Required Duration(min) (hrs) (in/hr) Qin(cfs) (Excluding Volume Volume Storage (ft) Basin A) (Basin A) 1 0.02 9.16 39.25 2355 0 107 2248.43 2 0.03 5.84 25.02 3002 0 214 2788.28 3 0.05 4.49 19.22 3460 0 320 3139.19 4 0.07 3.72 15.94 3826 0 427 3398.88 5 0.08 3.22 13.79 4137 0 534 3602.87 6 0.10 2.86 12.25 4409 0 641 3768.66 7 0.12 2.59 11.08 4654 0 748 3906.30 8 0.13 2.37 10.16 4877 0 854 4022.17 9 0.15 2.20 9.41 5082 0 961 4120.60 10 0.17 2.05 8.79 5273 0 1068 4204.69 11 0.18 1.93 8.26 5452 0 1175 4276.75 12 0.20 1.82 7.81 5620 0 1282 4338.53 13 0.22 1.73 7.41 5780 0 1388 4391.40 14 0.23 1.65 7.06 5932 0 1495 4436.48 15 0.25 1.58 6.75 6077 0 1602 4474.66 16 0.27 1.51 6.47 6215 0 1709 4506.68 17 0.28 1.45 6.22 6349 0 1816 4533.17 18 0.30 1.40 6.00 6477 0 1922 4554.66 19 0.32 1.35 5.79 6601 0 2029 4571.60 20 0.33 1.31 5.60 6720 0 2136 4584.37 21 0.35 1.27 5.43 6836 0 2243 4593.32 22 0.37 1.23 5.26 6948 0 2350 4598.73 23 0.38 1.19 5.11 7057 0 2456 4600.88 24 0.40 1.16 4.97 7163 0 2563 4599.99 25 0.42 1.13 4.84 7266 0 2670 4596.27 26 0.43 1.10 4.72 7367 0 2777 4589.91 27 0.45 1.08 4.61 7465 0 2884 4581.06 28 0.47 1.05 4.50 7560 83 2990 4652.51 29 0.48 1.03 4.40 7654 184 3097 4740.93 30 0.50 1.00 4.30 7745 284 3204 4825.02 31 0.52 0.98 4.21 7834 381 3311 4905.02 32 0.53 0.96 4.13 7922 477 3418 4981.14 33 0.55 0.94 4.04 8008 570 3524 5053.59 34 0.57 0.93 3.97 8092 662 3631 5122.53 35 0.58 0.91 3.89 8174 752 3738 5188.15 36 0.60 0.89 3.82 8255 840 3845 5250.60 37 0.62 0.88 3.75 8335 927 3952 5310.01 38 0.63 0.86 3.69 8413 1012 4058 5366.53 39 0.65 0.85 3.63 8490 1096 4165 5420.28 40 0.67 0.83 3.57 8566 1178 4272 5471.38 41 0.68 0.82 3.51 8640 1259 4379 5519.93 42 0.70 0.81 3.46 8713 1339 4486 5566.04 43 0.72 0.79 3.41 8785 1417 4592 5609.79 44 0.73 0.78 3.35 8856 1494 4699 5651.29 45 0.75 0.77 3.31 8926 1571 4806 5690.62 46 0.77 0.76 3.26 8995 1646 4913 5727.85 47 0.78 0.75 3.21 9063 1720 5020 5763.06 48 0.80 0.74 3.17 9130 1793 5126 5796.31 49 0.82 0.73 3.13 9196 1865 5233 5827.69 50 0.83 0.72 3.09 9261 1936 5340 5857.24 51 0.85 0.71 3.05 9326 2006 5447 5885.03 52 0.87 0.70 3.01 9389 2075 5554 5911.12 53 0.88 0.69 2.97 9452 2144 5660 5935.55 54 0.90 0.69 2.94 9514 2211 5767 5958.39 55 0.92 0.68 2.90 9575 2278 5874 5979.67 56 0.93 0.67 2.87 9636 2344 5981 5999.45 57 0.95 0.66 2.84 9696 2409 6088 6017.77 58 0.97 0.65 2.80 9755 2474 6194 6034.67 59 0.98 0.65 2.77 9814 2538 6301 6050.19 60 1.00 0.64 2.74 9872 2601 6408 6064.37 61 1.02 0.63 2.71 9929 2663 6515 6077.25 62 1.03 0.63 2.68 9985 2725 6622 6088.86 63 1.05 0.62 2.66 10042 2786 6728 6099.23 64 1.07 0.61 2.63 10097 2847 6835 6108.40 65 1.08 0.61 2.60 10152 2906 6942 6116.40 66 1.10 0.60 2.58 10206 2966 7049 6123.26 67 1.12 0.60 2.55 10260 3024 7156 6129.00 68 1.13 0.59 2.53 10314 3082 7262 6133.66 69 1.15 0.58 2.50 10366 3140 7369 6137.25 70 1.17 0.58 2.48 10419 3197 7476 6139.81 71 1.18 0.57 2.46 10471 3254 7583 6141.36 72 1.20 0.57 2.44 10522 3310 7690 6141.93 73 1.22 0.56 2.41 10573 3365 7796 6141.52 74 1.23 0.56 2.39 10623 3420 7903 6140.18 75 1.25 0.55 2.37 10673 3474 8010 6137.91 76 1.27 0.55 2.35 10723 3529 8117 6134.74 77 1.28 0.54 2.33 10772 3582 8224 6130.69 78 1.30 0.54 2.31 10821 3635 8330 6125.77 79 1.32 0.54 2.29 10869 3688 8437 6120.01 80 1.33 0.53 2.27 10917 3740 8544 6113.42 81 1.35 0.53 2.26 10965 3792 8651 6106.02 82 1.37 0.52 2.24 11012 3843 8758 6097.82 83 1.38 0.52 2.22 11059 3894 8864 6088.85 84 1.40 0.51 2.20 11105 3945 8971 6079.11 85 1.42 0.51 2.19 11151 3995 9078 6068.63 86 1.43 0.51 2.17 11197 4045 9185 6057.41 87 1.45 0.50 2.15 11243 4095 9292 6045.47 88 1.47 0.50 2.14 11288 4144 9398 6032.83 89 1.48 0.50 2.12 11332 4192 9505 6019.49 90 1 1.501 0.491 2.111 113771 42411 9612 6005.47 DETENTION POND # 71 REQUIRED VOLUME 1. Calculate Area and Weighted C Factor(Post-Development) Contributing Area C Area(It 2 C *Area ROW- Broken Spur 0.78 32586 25254 Park 0.35 77537 27138 Total 110123 52392 A =Area(acres) 2.53 Storm C= Weighted C Factor 0.48 Return (yrs) Cf 12 to 10 1 2. Calculate T°(Pre-Development) ;11 to 25 1.1 Tc Overland Flow :26 to 50 1.2 Tc= 1.87 (1.1-CC)D1f2/S1/3 :51 to 100 1.25 1------------------------------ S = Slope of Basin (%) 1.21 C = Rational Method Runoff Coefficient 0.2 Cf = Frequency Adjustment Factor 1 D= Length of Basin (ft) 558 Tc(Pre-Development) (minutes) 37 3. Calculate Rainfall Intensity(Duration =Pre-Development Tc) i = 0.64z o.65 (10-yr Storm, Fig. 1-3, COB Design Standards) x =storm duration (hrs) 0.62 (Tc Pre-Development) i=rainfall intensity(in./hr.) 0.87 4. Calculate Runoff Rate(Pre-Development) Q = CiA C = Rational Method Runoff Coefficient 0.2 (open land) i = rainfall intensity(in./hr.) 0.87 (calculated above) A=Area (acres) 2.53 (calculated above) Q=Runoff Rate (Pre-Development) (cfs) 0.44 5. Calculate Required Pond Volume Total Area (acres) = 2.53 acres Weighted C = 0.48 Discharge Rate (cfs) = 0.44 cfs(Equal to Pre-Development Runoff Rate) uur IntensityRunoff Release Required Duration(min) atio (in/hr) Qin (cfs) Volume Volume Storage(ft) 24 0.40 1.16 1.40 2011 635 1376 25 0.42 1.13 1.36 2040 661 1379 26 0.43 1.10 1.33 2068 687 1381 27 0.45 1.08 1.29 2095 714 1382 28 0.47 1.05 1.26 2122 740 1382 29 0.48 1.03 1.23 2149 767 1382 30 0.50 1.00 1.21 2174 793 1381 31 0.52 0.98 1.18 2199 820 1380 32 0.53 0.96 1.16 2224 846 1378 33 0.55 0.94 1.14 2248 872 1375 PROVIDED VOLUME (ft") 2,141 OUTLET STRUCTURE SLOT Q=CL.f-{3111 Q = Discharge (cfs) 0.44 C =Weir Coefficient 3.33 (per COB Design Standards) H = Head (ft) 1.5 L = Horizontal Length (ft) 0.07 L =Slot Width(inches) 0.9