HomeMy WebLinkAboutA00-41 - ACCESSIBILITY ANALYSIS AND DETAILSA."CODE TYPE A" AND "CODE TYPE B" DETAILS APPLY TO ALL RESIDENTIAL UNITS AND ARE BASED ON IBC,
ANSI 117.1, AND FHA REQUIREMENTS.
B. "PUBLIC" DETAILS APPLY TO PUBLICLY ACCESSIBLE SPACES INCLUDING LEASING, AMENITY, COURTYARD,
AND RETAIL SPACES AND ARE BASED ON IBC AND 2010 ADA.
Specification AIf Specification A is used it applies to all bathrooms, and all fixtures in those bathrooms must be usable.
Specification B
If Specification B is used, it applies to one bathroom, and only one of each type of fixture must be usable; additional bathrooms
in the unit are exempt only from maneuvering and clear floor space requirements at fixtures.
Usable bathroom specifications include:
1. an accessible route to and into the bathroom with a nominal 32-inch clear door opening (Requirements 3 and 4),
2. switches, outlets, and controls in accessible locations (Requirement 5),
3. reinforced walls to allow for the later installation of grab bars around the toilet, tub, and shower stall; under certain conditions
provisions for reinforcing must be made in shower stalls to permit the installation of a wall-hung bench seat (Requirement 6),
4. maneuvering space within the bathroom to permit a person using a mobility aid to enter the room, close and reopen the door,
and exit (Requirement 7), and5. maneuvering and clear floor space within the bathroom to permit a person using a mobility aid to approach and use fixtures;
fixture dimensions and placement are specified only under certain conditions (Requirement 7).
Bathroom Requirements for Covered Dwelling Units
All bathrooms as defined in the Guidelines must:
1. be on an accessible route (Requirement 4),
2. have 32-inch nominal clear width doorways (Requirement 3),
3. have switches, outlets, and controls in accessible locations (Requirement 5),
4. have reinforcing around toilets, tubs, and showers (Requirement 6), and
5. meet Requirement 7, Specification A or B:
Specification A
If Specification A is used it applies to all bathrooms, and all fixtures in those bathrooms must be usable.
Specification BIf Specification B is used, it applies to one bathroom, and only one of each type of fixture must be usable; additional
bathrooms in the unit are exempt only from maneuvering and clear floor space requirements at fixtures.
Powder Room Requirements for Covered Dwelling Units
Powder rooms must:
1. be on an accessible route (Requirement 4),
2. have 32-inch nominal clear width doorways (Requirement 3), and
3. have switches, outlets, and controls in accessible locations (Requirement 5).
Exception
When the powder room is the only toilet facility on the entry level of a multi-story unit in a building with one or more
elevators, it must, in addition to Requirements 3, 4, and 5, meet the reinforcing specifications of Requirement 6 and
the maneuvering and clear floor specifications of Requirement 7.
Maximum Allowable Height Difference Between Interior Floor Level and Exterior Floor Level
level difference at primary entry door:
0'' pervious construction (e.g., wood decking with spaces)
1/2'' impervious construction (e.g., concrete, brick, or flagstone)
level difference at secondary door:
1/2'' pervious construction
4'' impervious construction
Walks on Accessible Routes
Walks that are part of accessible routes become ramps when their slope exceeds 5% (1 in 20). Handrails are not required on
walks with slopes between 0% and 5%, but they are required on those steeper than 5% and up to 8.33% (1 in 12). Slopes
steeper than 8.33% are not usable by most people with disabilities and cannot be considered part of an accessible route.Handrail requirements for walks differ, depending upon which buildings the walks connect. This is addressed in the following
sections.
FAUCET CONTROLS SHALL
COMPLY WITH ANSI SEC. 309.4,
PROVIDE FORWARD APPROACH
WITH REMOVABLE BASE
CABINET PER ANSI SEC.
1003.12.4.1, PROVIDE KNEE
SPACE COMPLIANT WITH SEC.306, PLUMBING PIPING AND
DISPOSAL ARE NOT PERMITTED
TO ENCROACH ON KNEE SPACE
SINK 33 1/2" MAX. A.F.F. TO TOP
OF SINK RIM OR COUNTERTOP
AND ONE BOWL SHALL HAVE A
MAX. DEPTH OF 6 1/2" FROM
TOP OF COUNTERTOP
REFRIGERATOR SIDE BY SIDE
CONFIGURATION, SHALL
COMPLY WITH ANSI SEC.
1003.12.6.6
WORK SURFACE 34" MAX. A.F.F.
WITH REMOVABLE BASE
CABINET, FINISH WALL, FLOOR
AND END PANELS OF SIDE
CABINETS
RANGE WITH FRONT
ACCESSIBLE CONTROLS,
RANGE HOOD ABOVE SHALL
HAVE CONTROLS FOR LIGHT
AND EXHAUST FAN WITHIN
ACCESSIBLE REACH RANGE
NOTE: DESIGN BASED ON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH
NOTE: ALL 30"X48" CLEARANCES SHALL BE CENTERED ON THE APPLIANCE
FOR PARALLEL APPROACH, UNLESS NOTED OTHERWISE
REFRIGERATOR
RANGE WITH RANGE
HOOD ABOVE
30"X48"
30"X48"
30"X48"
30"X48"
30"X48"40" MIN.54".30" MIN.
30" MIN.
SHOWER SPRAY UNIT
WITH 59" LONG MIN. HOSE
THAT CAN BE USED AS A
FIXED OR HAND-HELD
SHOWER HEAD. THE
HAND-HELD PORTION
MUST BE MOUNTED NO
HIGHER THAN 48" PER ANSI
SEC. 607.6
CONTROL LOCATION,
EXCLUDING
DRAIN STOPPERS18" MIN.6" MAX.3" MIN.3'-0" MAX.CL
1' - 6"1' - 6"
3' - 0"NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
3' - 0"2' - 6"6"4' - 0"6"4' - 0"GRAB BAR REINFORCEMENT
REQUIRED. REFER TO TUB/SHOWER
BLOCKING DETAIL
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT IS
INSTALLED
30" X 48" CLEARANCE FOR
PARALLEL APPROACH PER ANSI
SEC. 1004.11.3.1.3.1
30 "X 48"
30" X 48"
REFRIGERATOR
DISH
WASHER
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH
NOTE: ALL 30 X 48 CLEARANCES SHALL BE CENTERED ON THE
APPLIANCE OR PLUMBING FIXTURE FOR PARALLEL APPROACH
30 "X 48"
30 "X 48"4' - 6"40" MIN. CLR.40" MIN. CLR.GRAB BAR REINFORCEMENT
REQUIRED
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT
IS INSTALLED
LAVATORY COMPLYING WITH
ANSI SEC. 1003.11.5 ARE
PERMITTED TO ENCROACH
ON CLEARANCE
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT
IS INSTALLED
TOILET FLUSH CONTROLS
BETWEEN 15" AND 36" A.F.F.
AND OPERABLE WITH 5 LBS OF
PRESSURE OR LESS. LOCATE
FLUSH CONTROL ON THE OPEN
SIDE OF WATER CLOSET PER
ANSI 117.1 SEC 309 AND 604.6
4'-2"NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH5' - 6"5' - 0"8"4' - 2"3' - 6"1' - 0"3' - 8"2"
3' - 0"6"
1' - 6" MIN.1' - 6"
FAUCET CONTROLS SHALLCOMPLY WITH ANSI SEC. 309.4
AT LEAST 1 SINK BOWL SHALL
HAVE A MAX. DEPTH OF 6 1/2"
FROM TOP OF COUNTERTOP
TOP OF COUNTERTOP OR SINK
SHALL BE 33 1/2" A.F.F. MAX.
EXPOSED PLUMBING PIPES
SHALL BE INSULATED AND
COMPLY WITH ANSI SEC. 306.4
REMOVABLE SINK BASE
CABINET - AFTER BASE IS
REMOVED, REMAINING CABINET
SHALL PROVIDE CLEAR KNEE
SPACE PER ANSI SEC. 306.4
FINISH WALL, END PANELS OF
CABINETS AND EXTEND FLOOR
FINISH BENEATH REMOVABLE
BASE CABINET
NOTE: DESIGN BASED ON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH3' - 0"2' - 9 1/2" MAX.2' - 3" MIN.33" MIN.6 1/2"30" X 48" CLEARANCE FOR
PARALLEL APPROACH
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT IS
INSTALLED
GRAB BAR REINFORCEMENT
REQUIRED. REFER TO
TUB/SHOWER BLOCKING
DETAIL
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
2' - 8"2' - 6"6"4' - 0"6"2' - 8"4' - 0"TOILET TISSUE DISPENSER
SHALL NOT BE WITHIN 1 1/2"
OF ANY GRAB BAR OR
OTHER OBSTRUCTION
TOILET, FLUSH CONTROLS
BETWEEN 15" AND 36" A.F.F.
AND OPERABLE WITH 5 LBS.
OF PRESSURE OR LESS.
LOCATE FLUSH CONTROLS
ON THE OPEN SIDE OF
WATER CLOSETS PER ANSI
117.1 SEC. 309 AND 604.6
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS.
7"-9"19" MAX.15" MIN.48" MAX.15" MIN.REMOVABLE BASE CABINET -
AFTER CABINET IS REMOVED,
REMAINING BASE CABINET
SHALL PROVIDE CLEAR KNEE
SPACE PER ANSI SEC. 306.4
FINISH WALL, END PANELS OF
SIDE CABINETS AND EXTEND
FLOOR FINISH BENEATH
REMOVABLE BASE CABINET
TOP OF COUNTER SHALL
BE 33 1/2" A.F.F. MAX.
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS.3' - 0"33 1/2" MAX.27" MIN.33" MIN.
30" X WIDTH OF TUB REQUIRED
CLEARANCE FOR PARALLEL
APPROACH
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT IS
INSTALLED
GRAB BAR REINFORCEMENT
REQUIRED. REFER TO
TUB/SHOWER BLOCKING
DETAIL
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH
2' - 8"2' - 6"6"4' - 0"6"2' - 8"LENGTH OF TUB48" X 60" CLEARANCE FOR
FORWARD APPROACH PER ANSI
SEC. 1004.11.3.1.3.2
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
3' - 0"5' - 0"6"4' - 0"6"4' - 0"GRAB BAR REINFORCEMENT
REQUIRED. REFER TO TUB/SHOWER
BLOCKING DETAIL
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT IS
INSTALLED
FAUCET CONTROLS SHALL
COMPLY WITH ANSI SEC. 309.4,
PROVIDE FORWARD APPROACHWITH REMOVABLE BASE
CABINET PER ANSI SEC.
1003.12.4.1, PROVIDE KNEE
SPACE COMPLIANT WITH SEC.
306, PLUMBING PIPING AND
DISPOSAL ARE NOT PERMITTED
TO ENCROACH ON KNEE SPACE
SINK 33 1/2" MAX. A.F.F. TO TOP
OF SINK RIM OR COUNTERTOP
AND ONE BOWL SHALL HAVE A
MAX. DEPTH OF 6 1/2" FROM
TOP OF COUNTERTOP
REFRIGERATOR SIDE BY SIDE
CONFIGURATION, SHALL
COMPLY WITH ANSI SEC.
1003.12.6.6
WORK SURFACE 34" MAX. A.F.F.
WITH REMOVABLE BASE
CABINET, FINISH WALL, FLOOR
AND END PANELS OF SIDE
CABINETS
RANGE WITH FRONT
ACCESSIBLE CONTROLS,
RANGE HOOD ABOVE SHALL
HAVE CONTROLS FOR LIGHT
AND EXHAUST FAN WITHIN
ACCESSIBLE REACH RANGE
NOTE: DESIGN BASED ON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH
NOTE: ALL 30"X48" CLEARANCES SHALL BE CENTERED ON THE APPLIANCE
FOR PARALLEL APPROACH, UNLESS NOTED OTHERWISE
30"X48"
30"X48"
30"X48"
30"X48"
30"X48"
30" MIN.60" MIN. CLR.74".30" MIN.
30"X48"
REFRIGERATOR
DISH
WASHER
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH
NOTE: ALL 30 X 48 CLEARANCES SHALL BE CENTERED ON THE
APPLIANCE OR PLUMBING FIXTURE FOR PARALLEL APPROACH6' - 2"60" MIN. CLR.30"X48"
30"X48"
30"X48"
GRAB BAR NOT REQUIRED
WHEN REINFORCEMENT IS
INSTALLED
GRAB BAR REINFORCEMENT
REQUIRED. REFER TO
TUB/SHOWER BLOCKINGDETAIL
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 2009 ANSI A117.1 REQUIREMENTS6"4' - 0"6"2' - 8"4' - 0"2' - 6"1' - 6"5' - 0" MIN.Accessibility Analysis
Black & Olive is an apartment building with 5 stories above grade with a parking garage at the 1st floor. The building is equipped
with one elevator providing accessible access to all floors. Of the 56 units, 16 are studio units, 24 are one bedroom units and 16
are two bedroom units. Level 1 of the buildng contains accessible parking, leasing office, fitness, mailroom, and 943 SF of
Retail space. Floors two - five each contain 14 residential units each. All required parking will be contained on site in the parking
garage and on street parking.
Applicable Codes2012 International Building Code (Chapter 11)
2009 ICC/ANSI A117.1, as referenced by the 2009 IBC
1998 Fair Housing Act Design Manual
1986 ANSI A117.1, as referenced by the FHA Design Manual
2010 ADA Standards for Accessible Design
Safe Harbor for Compliance
The Fair Housing Act Design Manual (1998)
Scoping
2012 IBC Section 1107.6.2.1.1 requires that 2% of the total unit count be Type A accessible dwelling units. The remaining units
shall be Type B accessible units. 2% of 56 units = 1.12 units (2 units)
Type A dwelling units 6 pts each 6 pts x 2 Type A units = 12 pts
Type B dwelling units 4 pts each 4 pts x 54 Type B units =216 pts
Total points provided 228 pts
2 Type A dwelling units will be provided per 2012 IBC Section 1107.6.2.1.1
Total 1 bedroom Type A units 1 (1 required)
Total 2 bedroom Type A units 1 (1 required)
Total Type A units 2
Refer to the Accessibility Plans for locations of Type A dwelling units.
2012 IBC Analysis
Accessible Route Accessible routes within the site shall be provided from public transportation stops, accessible
1104 parking, accessible passenger loading, and public streets or sidewalks to the accessible
building entrance served.
At least one accessible route shall connect accessible buildings, accessible facilities, accessible
elements and accessible spaces that are on the same site.
An accessible path of travel has been provided throughout the building and site. Refer to the
accessibility plans for travel within the building and to Civil drawings for accessible paths of
travel throughout the site.
Employee Work Areas Common use circulation paths within employee work areas shall be accessible routes. A 36"
1104.3.1 wide accessible path of travel has been provided to all employee work areas.---
Multilevel Buildings At least one accessible route shall connect each accessible level. One accessible elevators have
1104.4 been provided within the building.
Accessible Entrances At least 60% of all public entrances shall be accessible.
1105
Accessible Parking Two percent of each type of parking space shall be accessible. Per IBC Table 1106.1, 2 total
accessible parking stalls shall be provided including 1 Van parking stall. There are (1) van spaces, (1)
accessible space and (1) accessible car share space being provided for a total of (2) accessible
spaces provided. Accessible parking is provided at the shortest accessible route to the accessible
building entrances and Type A dwelling units. Refer to Accessibility drawings on A00.40 for quantityand location of accessible parking stalls at each level.
Dwelling Units Dwelling units that are required to be accessible Type A or Type B units shall
1107.2 comply with the applicable portions of the ICC/ANSI 117.1. Refer to the scoping information stated
earlier in this analysis for quantity and type of accessible units.
Storage Facilities Self-service storage facilities shall provide accessible individual self-storage spaces in accordance
1108.3 with Table 1108.3. 41 storage lockers are provided. Per Table 1108.3, 5% of storage spaces are
required to be accessible (1 lockers). 1 accessible storage lockers are provided.
Public Toilet and Toilet and bathing facilities shall be accessible. At least one of each type of
Bathing Facilities fixture, element, control, or dispenser in each accessible toilet room shall be
1109.2 accessible.
Water Closet Where water closet compartments are provided, at least one wheelchair
Compartment accessible compartment shall be provided. Accessible compartments shall comply
1109.2.2 with ICC/ANSI 117.1.
Sinks Where sinks are provided, at least 5% shall comply with ICC/ANSI 117.1.
1109.3
Kitchens Where kitchens are provided in accessible spaces, they shall comply with ICC/ANSI 117.1.
1109.4
Drinking Fountains One drinking fountain shall be provided per exception at wheelchair elevation.
1109.5
Elevators Elevators shall comply with ICC/ANSI 117.1 per Section 3001.3.
1109.7
Lifts Platform (wheelchair) lifts are permitted to be a part of a required accessible route to spaces
1109.8 that are not open to the general public with an occupant load of not more than 5 [residential units].
Storage Where fixed or built-in storage elements are provided, at least one of each type
1109.9 shall comply with ICC/ANSI 117.1.
Work Surface Heights Where counters or work surfaces are provided, at least 5% of the seating and
1109.11 standing spaces, but not less than one, shall be accessible.
Controls Controls, mechanisms, and hardware intended for operation by the occupant
1109.13 shall be accessible.
Exceptions:
1.Operable parts intended for use only by maintenance personnel.
2.Electrical or communication receptacles serving a dedicated use.
3.Floor electrical receptacles.
4.HVAC diffusers.
Operable Windows Where operable windows are provided within accessible spaces, at least one
1009.13.1 operable window shall be accessible.
Exception: Accessible windows are not required in kitchens or bathrooms.
Recreational Fac.Recreational facilities shall be provided with accessible features per Section
1109.15 1109.14.1 through 1109.14.4.
Signage Accessible signage shall be provided per Section 1110 and IIC/ANSI 117.1.
1110
Fire Extinguisher Where provided along accessible routes, surface mounted extinguishers / cabinets projecting more
Cabinets\than 4" from wall must have bottom of cylinder / cabinet not exceeding maximum 27" AFF or cane
detection device must be provided. If cabinets are partially recessed, cabinet must not project more
than 4" from wall or cabinet base must not exceed max. 27" AFF or cane detection device must be
provided.
WATER CLOSET
FRONT OF LAVATORY AND SINK
SHALL BE 34" MAX. ABOVE THE
FINISHED FLOOR SURFACE
MEASURED TO THE HIGHER OF
THE FIXTURE RIM OR THE
COUNTER SURFACE, OPERABLE
FAUCET SHALL COMPLY WITH
SECTION 309
LAVATORY SHALL COMPLY WITH
ANSI SEC. 606 AND 306. A
REMOVABLE BASE CABINET IS
PERMITTED PER ANSI 1003.11.5
EXCEPTION
30" X 48" REQUIRED CLEARANCE
FOR PARALLEL AND FORWARD
APPROACH WITH KNEE SPACE
NOTE: ALL DIMENSIONS ARE TO FACE OF FINISH.
NOTE: DESIGN BASED UPON 1998 ANSI REQUIREMENTS.
ACCESSIBLE LAVATORIES AND SINKS SHALL COMPLY WITH SECTION 608.4' - 0"2' - 6"1' - 3"1' - 3"
2' - 0"2' - 0"
1'-6" MIN.
MIRROR SHALL BE INSTALLED AT
40" MAX. ABOVE THE FLOOR TO THE
BOTTOM EDGE OF THE REFLECTING
SURFACE
PROJECT
COPYRIGHT BY JOHNSON
NATHAN STROHE (JNS). ALL
DRAWN AND WRITTEN
INFORMATION APPEARING
HEREIN SHALL NOT BE
MODIFIED, DUPLICATED,
DISCLOSED, USED FOR
ANOTHER PROJECT, OR
OTHERWISE USED WITHOUT
THE WRITTEN CONSENT AND
INDEMNIFICATION OF JNS
SHEET TITLE
ISSUES/REVISIONS
STAMP
SHEET NUMBER
PRINTED ON1600 Wynkoop St., Suite 100 | Denver, CO 80202303.892.7062WWW.JNS.DESIGN12/28/2016 8:53:05 AMP:\1611\05-Design Drawings\08-Local Workstation\Kevin\1611_Black Olive_KEVIN.rvtA00.41BLACK & OLIVE, LLCBLACK OLIVE #1611
ACCESSIBILITY
ANALYSIS AND
DETAILS 110 E. OLIVE STREET, BOZEMAN, MONTANA 59715ACCESSIBILITY ANALYSIS
GENERAL ACCESSIBILITY NOTES
1/2" = 1'-0"2 CODE TYPE A - GALLEY KITCHEN1
1/2" = 1'-0"6 CODE TYPE A - TUB/SHOWER1
1/2" = 1'-0"14 CODE TYPE B / OPTION A - TUB
1/2" = 1'-0"11 CODE TYPE B - GALLEY KITCHEN1
1/2" = 1'-0"7 CODE TYPE A - WATER CLOSET
1/2" = 1'-0"3 CODE TYPE A - KITCHEN SINK1
1/2" = 1'-0"12 CODE TYPE B / OPTION B - TUB
1/2" = 1'-0"8 CODE TYPE A -WATER CLOSET1
1/2" = 1'-0"4 CODE TYPE A - WORK SURFACE1
1/2" = 1'-0"5 CODE TYPE A - TUB
1/2" = 1'-0"13 CODE TYPE B / OPTION A - TUB
1/2" = 1'-0"1 CODE TYPE A - U SHAPED KITCHEN1
1/2" = 1'-0"10 CODE TYPE B - U SHAPED KITCHEN1
1/2" = 1'-0"15 CODE TYPE B / OPTION C - TUB
1/2" = 1'-0"9 CODE TYPE A - LAVATORY1
1/4" = 1'-0"16 IBC STRETCHER COMPLIANCE
# Date Description
09/12/2016 100% SCHEMATIC
DESIGN
10/04/2016 SITE PLAN
1 11/30/2016 SITE PLAN - REV 1
2 01/04/2017 REV 2