HomeMy WebLinkAboutUn-Knotted Catering As-builts474547504755476047654745475047600+00.000+50.001+00.001+50.00ROUSE AVE.PROPERTY LINE
EXISTING BUILDINGFINISH FLOORAPPROX. ELEV. = 4759.51(VERIFY W/ ARCH)STA. 0+02.81CONNECT TO EXISTING 16" WATER MAINW/ 4" TAPPING SADDLE AND GATE VALVEINV. ELEV. = 4747.75 (VERIFY W/ CONTRACTOR)STA. 0+36.43,167$//%(1':7+5867%/2&.OR EQUIV. JOINT RESTRAINTINV. ELEV. = 4750.94 (VERIFY W/ CONTRACTOR)
STA. 0+56.25
,167$//9(57,&$/%(1':7+5867
BLOCK OR EQUIV. JOINT RESTRAINT
SEE DETAIL THIS PAGE
INV. ELEV. = 4752.54 (VERIFY W/ CONTRACTOR)EXISTING 16"WATER MAINEXTERIOR WALL
NOTE:PIPE PENETRATION TO BE INSTALLED 2.5' FROMINSIDE OF WEST WALL TO CENTER OF PIPEAND 1.5' FROM INSIDE NORTH WALL TO CENTEROF PIPE. FIRE SERVICE LINE CLASSIFICATION ISCLASS I.EXISTINGTELEPHONE LINESEXISTING 24"SEWER MAIN18" MINIMUM VERT. SEPARATIONBETWEEN WATER & SEWER MAINSSEE DETAIL THIS PAGEFOR FIRE RISER SPEC.EXISTING 16"WATER MAINEXISTINGGAS MAINS4" CL 51 DUCTILE IRON FIRE SERVICE LINE2" BLUEBOARDINSULATION PROVIDEFOR EXTRA FROSTPROTECTIONSTA. -0+02.19CONNECT TO EXISTING 16" WATER MAINW/ 4" TAPPING SADDLE AND GATE VALVEINV. ELEV. = 4749.98
EL. = 4759.51'TOP of ADAPT./SPOOL (4")THRUST BLOCKEL. = 4761.004" F.S. LINEEL. = +/-4752.50'&/',%(1'THRUST BLOCKINGw/ MJ FITTINGSFIRE SERVICE LINE GENERAL NOTES:1. THE FIRST FITTING INSIDE THE BUILDING SHALL BE A ULLISTED FLANGED OS&Y VALVE THE SAME SIZE AS THE FIRESERVICE LINE.2. HORIZONTAL INSTALLATIONS MUST BE A MINIMUM OF 2'ABOVE THE FINISHED FLOOR.3. THE FIRE SERVICE RISER MUST BE A MINIMUM OF 2' CLEARFROM ANY OUTSIDE WALL, AND A MINIMUM OF 1' CLEAR FROMANY INTERIOR WALLS.4. THE INCOMING FIRE SERVICE LINE SHALL BE A MINIMUM 6.5',AND A MAXIMUM OF 7.5' BELOW THE FINISHED GRADE.5. ALL FIRE SERVICE LINE APPURTENANCES SHALL HAVE AMINIMUM PRESSURE RATING OF 175 psi.6. ALL FIRE SERVICE LINES 4" OR LARGER SHALL BE CLASS 51DUCTILE IRON PIPING.7. INSTALL THRUST BLOCKING PER COB STANDARD DETAILSNo. 02660-1 & 02660-3.8. INSTALL FIRE SERVICE LINE PER COB STANDARD DETAIL No.02660-13. FIRE SERVICE LINE IS CLASSIFICATION FORBACKFLOW PREVENTION IS CLASS I9. PROVIDE FLEXIBLE, WATER-TIGHT CONNECTION FOR ALLWALL AND FLOOR PIPE PENETRATIONS.PROCESS PIPINGFLOOR SLABPIPE SLEEVE SCHEDULEPIPE SIZESLEEVE SIZE3"4"4"6"6"8"SCH 40 PVCPIPE SLEEVE -SEE SCHEDULECAULK SEALON BACKINGMATERIAL5(',52'7<32),167$//)5200-%(1'72)/$1*($7O.S.&Y. VALVE. INSTALL NON-ADJACENTAT 2 OF THE 4 MJ BOLT HOLES.&/',3,3(INSTALL PLUMB ANDLEVEL.BLDG. F.F. ELEVATIONTOP OF SLAB (VERIFY W/ ARCH)FLANGE TO BE THREADED ON STANDPIPE. MJTO FLANGE ADAPTERS ARE NOT ACCEPTABLE.4" OSY VALVE (ENDTHIS PROJECT)4" FLANGED MUELLER O.S.&Y. RESILIENTWEDGE GATE VALVE. POSITION PARALLELWITH ADJACENT WALL.FIRE SUPRESSIONEQUIP. (BY OTHERS)EXISTING WATER MAINSEE NOTE 31' MIN., 2' MAX.ABOVE FIN. FLOOR0'10'20'30'SCALE1" = 10' HORIZ.1" = 2' VERT.3.0CSCALE: 1" = 10' 24X36SCALE: 1" = 20' 12X18FIRE SERVICEPLAN & PROFILEMONTANA PUBLIC WORKS STANDARD SPECIFICATIONS, SIXTH EDITION, APRIL, 2010 STANDARDDRAWINGS CURRENTLY IN EFFECT AND CITY OF BOZEMAN MODIFICATIONS TO MPWSS, WITH ALLADDENDUM, DATED MARCH 31, 2011.PRODUCT MATERIALS, EQUIPMENT, ETC. SUBMITTALS ARE REQUIRED TO BE PROVIDED FORAPPROVAL PRIOR TO THE PURCHASE OF SAID PRODUCT OR EQUIPMENT.NOTICE TO UTILITY COMPANIES SHALL BE GIVEN BY THE CONTRACTOR. THE NOTICE SHALLSTATE HIS CONTEMPLATED START DATE, CONSTRUCTION SCHEDULE, AND AREAS TO BEDISTURBED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PRESERVE AND PROTECT EXISTINGUTILITIES.THE CONTRACTOR IS REQUIRED TO GIVE 72-HOUR ADVANCE NOTICE TO ALL UTILITY COMPANIESWHOSE UTILITIES MAY BE WITHIN THE PROJECT AREA OF PENDING CONSTRUCTION. EXISTINGUTILITIES MAY EXIST AT LOCATIONS NOT SHOWN ON THE PLANS. A MONTANA 1-CALL SYSTEMEXISTS TO FACILITATE REQUESTS FOR UNDERGROUND FACILITY LOCATE INFORMATION.THE CONTRACTOR IS CAUTIONED THAT ALL UTILITIES ARE NOT INCLUDED WITH THE 1-CALLSYSTEM. THE 1-CALL DISPATCH NUMBER IS 1-800-424-5555.UTILITY LOCATESGOVERNING SPECIFICATIONS1. CONTRACTOR TO LOCATE EXISTING WATER AND SEWER MAINS AND VERIFY ELEVATIONSPRIOR TO STARTING PROJECT.2. GENERAL CONTRACTOR SHALL VERIFY FINISH FLOOR ELEVATION WITH ARCHITECT PRIOR TOSTARTING CONSTRUCTION.3. EXISTING INTERIOR PLUMBING FIXTURES SHALL BE MODIFIED TO MEET CURRENT PLUMBINGCODES, IF APPLICABLE.4. CONTRACTOR TO FOLLOW CITY OF BOZEMAN FIRE SERVICE LINE STANDARD, REVISED 2011,FOR INSTALLATION, LOCATION, TESTING AND FLUSHING REQUIREMENTS (NFPA 24).4. IF ANY CONFLICTS EXIST, NOTIFY ENGINEER IMMEDIATELY.MISC. NOTES:FIRE SERVICE PLAN & PROFILE STA. -0+02.19 TO STA. 0+56.250#/'$1<'/#0/106#0#
0'.510%#6'4+0)
9'56-1%*564''6$1<'/#0/6